A/D Fire Protection Systems, Inc.
A/D FireBarrier Firestop Systems
A/D FireBarrier Firestop Systems - Page 5
A/D FireBarrier Firestop Systems
Fire Stop Systems
| 1. PRODUCT NAME A/D FIREBARRIER SILICONE 2. PRODUCT DESCRIPTION A primerless single component silicone sealant. The sealant cures to a durable, flexible, silicone rubber when exposed to atmospheric moisture. Basic Use: Composition and Materials: Packaging: Application Limitations
Standards:
3. TECHNICAL DATA: A/D FIREBARRIER SILICONE is listed by ULC, ULI, Warnock Hersey and Factory Mutual. For details of rated firestop systems see ULC's List of Equipment and Materials, Volume 111, ULI's Fire Resistance Directory, Volume 11, Warnock Hersey's Listings Book and Factory Mutual's Approval Guide. ULC Systems: SP159, SP160, SP161, SP162, JF9, JF14, JF29, SP163, SP324, SP325, SP326, SP365, SP383, SP384, SP385, SP386, SP394, SP395, SP396. ULI Systems: CAJ-001 7, -0029, - 1116, -1117, -1129, -5027, -8028, WL- 1050, -1066, -3042, -5031, - 8005, -8006, FC 10 11, FC3014, FC5007. FM Designs: 83, 85, 86,87, 88, 89, 204,206,235,236. Warnock Hersey's Designs: AD/PHV 180-04, -05, -06, -07, -08, AD/PSH 180-04, -05, -06, AD/PV 60-01, 120- 01. |
|||||||
| PHYSICAL PROPERTIES |
|||||||
| Properties |
Results |
||||||
| Uncured | |||||||
| Tool/Work Time | 5 minutes | ||||||
| Skin Over Time @ 25°C (77°F) 50% R.H. | Less than 60 minutes | ||||||
| Curing Time @ 25°C (77°F) 50% R.H. | 48 hours | ||||||
| Flow, Sag, or Slump | Nil | ||||||
| Specific Gravity | 1.13 | ||||||
| Cured | 7 days @ 25°C (77°C), 50% R.H. | ||||||
| Hardness (A) (ASTM D2240) | 12 | ||||||
| Tear Strength (ASTM D624, Die B) | 3.5 kN/m (20 ppi) | ||||||
| Elongation at Break (ASTM D412) | 600% | ||||||
| Shrink Factor | Negligible | ||||||
* Values given above are not intended to be used in specification preparation.
|
|||||||
| 4. INSTALLATION Clean all openings to be firestopped by removal of foreign matter and contaminants such as oil, dust, grease, frost, water, surface dirt, old sealants or glazing compounds and any protective coating. Priming: A/D FIREBARRIER SILICONE generally does not require priming. In view of the unpredictability of surface characteristics, it is recommended that a test sample of sealant be applied on the surface to test adhesion. Masking: Areas adjacent to openings to be firestopped can be masked to assure a neat appearance. The masking tape should not be allowed to touch the clean surfaces to which the silicone is to adhere. Remove masking tape immediately. A/D FIREBARRIER Mineral Wool is the required backup material for firestops. This material allows a thin bead of sealant to be applied for maximum economy. Install backup material as specified. Application of 6mm (1/4") of A/D FIREBARRIER SILICONE to the facing of a 100mm (4") depth of A/D FIREBARRIER Mineral Wool provides up to a 3-hour fire rated firestop assembly. Surfaces of mineral wool to receive sealant should be recessed in the opening a depth equal to the required thickness of sealant. Apply A/D FIREBARRIER SILICONE in a continuous operation to fill and seal the opening. Tool the sealant to spread it against the backup material and the opening surfaces. Individual penetrations through drywall do not require a backing material for the silicone. Simply fill the annular space to a depth equal to the thickness of the gypsum board and form a smooth bead or crown at the surface. Excessive sealant should be dry-wiped from glass, metal, and plastic surfaces while still uncured, following with a commercial solvent such as xylol, toluol, or methl ethyl ketone. CURED SEALANT IS USUALLY VERY DIFFICULT TO REMOVE WITHOUT ALTERING OR DAMAGING THE SURFACE TO WHICH THE SEALANT HAS BEEN MISAPPLIED. Precaution: A/D FIREBARRIER SILICONE uses a netural cure system. No acetic acid or objectionable byproducts are evolved during application. On direct contact, uncured sealant may irritate eyes. Flush with water and call a physician. Avoid prolonged contact with skin. Keep out of reach of children. To safely use this product, read and abide by Material Safety Data Sheet. Shelf Life: When stored in original and unopened container at or below 32°C (90°F), A/D FIREBARRIER SILICONE has a shelf life of six months from date of shipment. 5. MAINTENANCE No maintenance should be needed. It silicone sealant becomes damaged, replace damaged portion. Clean surfaces in damaged areas, and repair with fresh A/D FIREBARRIER SILICONE.
|
|||||||
A/D FIRE
PROTECTION SYSTEMS INC. |