   Airline Products Co.  Louvers, Dampers, & Penthouses  

Extruded Drainable Blade Louvers

 

 

Extruded Drainable Blade Louvers

Applications

Airline offers the designer a range of depths and blade angles in stationary blade drainable louvers. These models are designed for applications where minimum water penetration and high free area are required. The 45º model has a front gutter to catch falling water, draining it away through channels in the jambs. For extra protection against storm conditions, the 35 models have a center water baffle in addition to the front gutter.

These models are also available with a concealed mullion design. To specify, use a prefix "C" on the model number.

 

 

MODEL

XWD-4

XWD4-45

XWD-6

Blade Type

Drainable

Drainable

Drainable

Frame Depth

4"

4"

6"

Frame Thickness

.125" 

.125"

.125"

Blade Thickness

.018"

.081"

.081"

Blade Angle

35º

45º

35º

Blade Spacing

2-1/2"

4"

3-1/2"

Free Area (48" x 48") Sq. Ft. (%) 

6.66 (42%)

7.54 (47%)

8.13 (51%)

Velocity @ Beginning Point of Water Penetration (ft./min.)*†

1195

740

1075

Pressure Drop @ Max. Intake Velocity (in. wg.)

.16

.07

.12

Max. Intake Volume Flow Rate, 4' x 4' Unit (cfm)7959

8152

5580

8740

Exhaust Velocity @ 0.15" wg. Pressure Drop (ft./min.)

1046

1012

1050

Exhaust Volume Flow Rate @ 0.15" wg., 4' x 4' Unit (cfm)

6963

7632

8537

*AMCA defines the beginning point of water penetration to be .01 oz./ft.2 free area.
†When designing intake louvers, this should be the maximum velocity.

Louver Sections & Details

 

Suggested Specification

Furnish and install, where indicated on the drawings, Model XWD-6 Stationary Extruded Drainable Louver, as manufactured by Airline Products Company, Hagerstown, Maryland. Louvers shall be 6" deep with jambs fabricated from .125" thick (8 gauge) extruded aluminum, alloy 6063-T52. Head, sill and blades shall be .081" thick (12 gauge) extruded aluminum, same alloy. Assembly of members shall be by welding or with stainless steel fasteners. Blades will have an integral gutter for drainage of water, be set at an angle of 35° and be spaced on 3-1/2" centers.

Louvers shall meet the following criteria for testing and performance:

A 48" x 48" louver shall have a minimum free area of 8.13 ft2 (51%).

The free area velocity at the beginning point of water penetration shall be 1075 fpm.

The pressure drop at this velocity shall not exceed .12" water gauge.

At an exhaust free area velocity of 1050 fpm, pressure drop shall not exceed .15" water gauge.

*Request for Information / Request a Catalog
 
 
 
To request more information from Airline Products Co., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free bi-monthly AECnews e-Newsletter.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996-2008 AECinfo.com