Alkco Lighting
ST Series - Supplemental Surgical Lighting
ST Series - Supplemental Surgical Lighting - Page 3
ST Series - Supplemental Surgical Lighting
ALKCO ST Series
Supplemental Surgical Lighting
PHOTOMETRIC DATA
Catalog # ST8240-3 Luminaire Efficiency: 59.3% Lamps: (6) F032 T8, 2950 lumens each Input Wattage: 219 watts Ballast Type:
Magnetic Ballast Factor: .97 Report Ref: ITL45096.
COEFFICIENTS OF UTILIZATION (floor reflectance at 20%) |
|||||||||||
|
|||||||||||
% Ceiling Reflectance |
80 |
70 |
50 |
||||||||
|
|||||||||||
% Wall Reflectance |
70 |
50 |
30 |
70 |
50 |
30 |
50 |
30 |
10 |
||
|
|||||||||||
Room Cavity Ratio |
0 |
|
71 |
71 |
71 |
69 |
69 |
69 |
66 |
66 |
66 |
1 |
65 |
63 |
60 |
64 |
61 |
59 |
59 |
57 |
56 |
||
2 |
60 |
56 |
52 |
59 |
55 |
51 |
52 |
50 |
47 |
||
3 |
55 |
50 |
45 |
54 |
49 |
45 |
47 |
43 |
41 |
||
4 |
51 |
44 |
40 |
50 |
44 |
39 |
42 |
38 |
35 |
||
5 |
47 |
40 |
35 |
46 |
39 |
35 |
38 |
34 |
31 |
||
6 |
44 |
36 |
31 |
43 |
36 |
31 |
35 |
31 |
27 |
||
7 |
41 |
33 |
28 |
40 |
33 |
28 |
32 |
28 |
25 |
||
8 |
38 |
30 |
25 |
37 |
30 |
25 |
29 |
25 |
22 |
||
9 |
35 |
28 |
23 |
35 |
28 |
23 |
27 |
23 |
20 |
||
10 |
33 |
26 |
21 |
33 |
26 |
21 |
25 |
21 |
18 |
||
CANDLEPOWER DISTRIBUTION |
||||||
|
||||||
Angle |
0 |
45 |
90 |
180 |
||
|
||||||
Room Cavity Ratio |
0 |
|
4357 |
4357 |
4357 |
4357 |
5 |
4338 |
4353 |
4345 |
4323 |
||
15 |
4279 |
4257 |
4213 |
4265 |
||
25 |
4118 |
4023 |
3920 |
4118 |
||
35 |
3884 |
3772 |
3495 |
3722 |
||
45 |
2799 |
3034 |
2894 |
1729 |
||
55 |
791 |
1180 |
2184 |
1099 |
||
65 |
572 |
528 |
1026 |
865 |
||
75 |
469 |
352 |
322 |
722 |
||
85 |
176 |
110 |
59 |
161 |
||
90 |
0 |
0 |
0 |
0 |
||
ZONAL LUMEN SUMMARY |
|||||
|
|||||
Lumens |
% Lamp |
% Fixture |
|||
|
|||||
Zone |
0.30 |
|
3471 |
19.6 |
33.1 |
0.40 |
5759 |
32.5 |
54.9 |
||
0.60 |
9130 |
51.6 |
87.0 |
||
0.90 |
10497 |
59.3 |
100 |
||
LUMINANCE (candela /sq Metres) |
||||
|
||||
Degree |
0 |
90 |
||
|
||||
45 |
|
6454 |
6673 |
|
55 |
2249 |
6209 |
||
65 |
2207 |
3959 |
||
75 |
2955 |
2029 |
||
85 |
3293 |
1104 |
||
Suggested Written Specification
Use the following written specification to ensure that the fluorescent lighting you specify meets the requirements of the application into surgical
suites: 2’ x 4’ recessed fluorescent luminaire with six F32T8 lamps and a dual distribution symmetric/asymmetric low brightness linear
prism lens. Lamps are to be circuited in pairs to provide a symmetric/asymmetric light distribution which can be controlled by wall switches (by
others) to produce 33%, 66%, or 100% light levels. Each circuit is to be protected by a separate radio suppressor in compliance with the
CEO3 conducted EMI test limits of Mil-Std 461 C&D. The fixture must be clearly labeled for inspection that it complies with the MIL-STD 461
C&D for the control of radiated and conducted EMI. The height of the housing shall be no greater than 4%" and be constructed such that it can
contain up to three ballasts, three radio suppressors, and one 2-lamp emergency battery back-up ballast as specified without increasing the
height. Grid style luminaires shall be designed to fit in up to 1½" Tee grids without special ordering. Simple field conversion from grid to flange
and flange to grid style housings shall be possible without having to ship replacement fixtures. Door frame shall be one-piece 20 gauge steel,
powder-coated after fabrication (or brushed stainless steel). Door frames/lens assembly to be warranted to perform for the life of the
installation.
Typical Layouts |
Ordering Information |
||||
Catalog #: |
Description |
L |
W |
D |
2x4 Symmetric/Asymmetric Control Lens, (6)F32T8 Lamps |
||||
ST8240-1 |
1 suppressor |
47¾" |
23¾" |
4½" |
ST8240-2 |
2 suppressors |
47¾" |
23¾" |
4½" |
ST8240-3 |
3 suppressors |
47¾" |
23¾" |
4½" |
2x2 Symmetric/Asymmetric Control Lens, (2)FB031 T8 Lamps |
||||
ST8220-1 |
1 suppressor |
23¾" |
23¾" |
4½" |
1 x4 Asymmetric Control Lens, (3)F32T8 Lamps |
||||
ST8140-1 |
1 suppressor |
47¾" |
11¾" |
6" |
ST8140-2 |
2 suppressors |
47¾" |
11¾" |
6" |
|
||||
MOUNTING STYLE (must specify as suffix example: ST8240-2-G) |
||||
G |
For lay-in grid ceiling (1" - 1½" Tees) |
|||
F |
Flanged housing for dry-wall ceilings |
|||
|
||||
CONSTRUCTION OPTIONS |
||||
/SS |
Stainless steel door frame |
|||
/WHS |
20 gauge steel housing powder coated after fabrication |
|||
|
||||
OPTIONAL PLASTER FRAME FOR FLANGE HOUSINGS |
||||
F8240 |
Plaster frame for ST8240 |
|||
F8220 |
Plaster frame for ST8220 |
|||
F8140 |
Plaster frame for ST8140 |
|||
|
||||
OPTIONAL ELECTRICAL EQUIPMENT |
||||
/BIAX |
F40BX/RS bi-axial lamps substituted for T8 lamps |
|||
/T12 |
T12 lamps substituted for T8 lamps |
|||
/277 |
277 volts |
|||
/ECB |
Electronic Ballast (does not meet M/L-STD 461 C or D) |
|||
/Slo-Blo |
CMF Slow Blow Fuse and Fuse Holder |
|||
/STD RSP |
Economy Radio Suppressor substituted for custom suppressor (does not meet M/L-STD 461 C or D) |
|||
/EM -1 |
Single Lamp Emergency Battery Back-up |
|||
/EM-2 |
Two Lamp Emergency Battery Back-up |
|||
/GEN-1 |
Single Lamp 5-minute Interim Battery Back-up (eliminates time delay when switching to generator back-up circuit) |
|||
![]()
where quality comes to light™
A JJI Lighting Group Company
11500 Melrose Avenue,
Franklin Park, Illinois 60131-8389
Phone: 847 451-0770
Fax: 847 451-7512
Website: www.aIkco.com