TABLE 24
RECOMMENDED UNIFORM ROOF LIVE LOADS FOR APA RATED SHEATHING(c) AND APA RATED STURD-I-FLOOR WITH STRENGTH AXIS PERPENDICULAR TO SUPPORTS(e)
Panel Span Rating

 

Minimum Panel Thickness (in.) Maximum Span (in.) Allowable Live Loads (psf)(d)
With Edge Support(a) Without Edge Support Spacing of Supports Center-to-Center (in.)
12 16 20 24 32 40 48 60
APA RATED SHEATHING(c)
12/0 5/16 12 12 30              
16/0 5/16 16 16 70 30            
20/0 5/16 20 20 120 50 30          
24/0 3/8 24 20(b) 190 100 60 30        
24/16 7/16 24 24 190 100 65 40        
32/16 15/32,1/2 32 28 325 180 120 70 30      
40/20 19/32,5/8 40 32 - 305 205 130 60 30    
48/24 23/32,3/4 48 36 - - 280 175 95 45 35  
60/32(g) 7/8 60 48 - - - 305 165 100 70 35
APA RATED STURD-I-FLOOR(f)
16 oc 19/32,5/8 24 24 185 100 65 40        
20 oc 19/32,5/8 32 32 270 150 100 60 30      
24 oc 23/32,3/4 48 36 - 240 160 100 50 30 25  
32 oc 7/8 48 40 - - 295 185 100 60 40  
48 oc 1-3/32,1-1/8 60 48 - - - 290 160 100 65 40

(a) Tongue-and-groove edges, panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center or greater), lumber blocking, or other. For low slope roofs, see Table 25.

(b) 24 inches for 15/32-inch and 1/2-inch panels.

(c) Includes APA RATED SHEATHING/CEILING DECK.

(d) 10 psf dead load assumed.

(e) Applies to panels 24 inches or wider applied over two or more spans.

(f) Also applies to C-C Plugged grade plywood.

(g) Check with supplier for availability.

Note: Shaded construction meets Code Plus recommendations

TABLE 25
RECOMMENDED MAXIMUM SPANS FOR APA PANEL ROOF DECKS FOR LOW SLOPE ROOFS(a) (PANEL STRENGTH AXIS PERPENDICULAR TO SUPPORTS AND CONTINUOUS OVER TWO OR MORE SPANS)
Grade Minimum Nominal Panel Thickness (in.) Minimum Span Rating Maximum Span (in.) Panel Clips Per Span (b) (number)
APA RATED SHEATHING 15/32,1/2 32/16 24 1
19/32,5/8 40/20 32 1
23/32,3/4 48/24 48 2
7/8 60/32(c) 60 2

(a) Low slope roofs are applicable to built-up, single-ply and modified bitumen roofing systems. For guaranteed or warranted roofs contact membrane manufacturer for acceptable deck.

(b) Edge support may also be provided by tongue-and-groove edges or solid blocking.

(c) Check with supplier for availability.



Request for Information / Request a Catalog from APA - The Engineered Wood Association
 
 
 
To request more information from APA - The Engineered Wood Association, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.