| FIRESET
2 LABELED SHUTTER & FIRE DOOR OPERATOR |
- Mechanical drop testing at the turn of a switch
- UL listed motor, approved for both UL & FM labeled
shutter and fire doors.
- Designed for fire doors up to 100 sq. ft.
- Designed for labeled shutter up to 120 sq.ft.
- 1/4 HP, 1 pH (115,208 or 230 VA.) 3 pH (208,230 VA.).
- All electrical components, including motor, are contained
within a ENEMA 1 enclosure.
- Unit weighs approximately 40 lbs. and the dimensions are
9-1/2'' H x 17'' W x 6''D
- Prewired for:
-3-Button control station -External interlocks
-Safety edge to reverse -Fuse -link release
-Remote test key switch - Applied or maintained alarm signal
- FIRE POWER control system is
standard/allows door to be motorized down while a fire alarm conditions exists
Note: Sensor Edge Options is required with FIRE
POWER.
AMPERAGE & HORSEPOWER
| MAX
SQ. FT. * |
| MOTOR MODEL |
LABELED SHUTTER |
FIRE DOOR |
HP |
VOLTAGE |
PHASE |
AMP |
| FSM-25 |
120sq.ft. |
100sq.ft. |
1/4 |
115 |
1 |
2.8 |
| |
|
|
1/4 |
208 |
1 |
1.5 |
| |
|
|
1/4 |
230 |
1 |
1.4 |
| |
|
|
1/4 |
208 |
3 |
1.0 |
| |
|
|
1/4 |
230 |
3 |
0.9 |
| * The actual maximum square
footage will depend on the type of endlocks, bottom bar, GA,and the height to width
selected. |
SPECIFICATIONS
1.01 Section Includes
A. Type: The motor will be Atlas Door
model FSM-25 as manufactured by Clopay Building Products.
B. Mounting: To be vertical front of hod,
1.02 Related Work
A. Electrical wires, wiring, disconnect
switches and conduit are in scope of work of other sections or trades.
2.01 Operator

Motor:Provide high torque,
intermittent-duty, squirrel-cage induction electric motor. ODP Motor 1PH, TENV motor 3 PH.
Permanent split capacitor motor for single phase applications. Operator is limited to 12
cycles per hour.
B. Reduction: To be parallel shaft gearbox
with aluminum die cast housing. Precision-machined gearing, hardened for maximum load
capability. Permanently lubricated.
C. Drive: Product shaft to be driven by 41
series roller chain to provide travel of 6'' to 12'' per second.
D. Brake: To be electrically activated
magnetic disc type brake.
E. Electrical Enclosure: All electrical
components shall be in a NEMA 1 enclosure and pre-wired to terminal black.
F. Reversing Contractor: Heavy-duty,
across-the-line reversing type with mechanical interlock. size ''00''
or equivalent.
G. Limit Switches: To be positive direct
drive screw type limit switch, enclosed in electrical control box, easily accessible for
precision setting or adjusting. Limit switches will retain settings during mechanical
governed closure.
2.02 Operation
A. Automatic Powered Closing with FIRE POWER
Control System:
If this door is in the open position and an alarm condition
occurs, the will automatically close under motor operation. In the event the door should
hit an obstruction while closing, it will reverse and return to the full open position,
and then begin closing again. If the obstruction is not removed, the door will recycle
approximately three (3) times, finally closing and stooping at the lowest possible
position. If after the door has finished the cycling mode and the obstruction is removed,
the door will proceed to the floor.
B. Automatic Closing: If the
door is in the open position and a loss of power occurs, the door will
automatically close by mechanical a governed closure. No manual reset
is required. C. Fuse Link Releases: If
the door is in the open position and the fuse link melts, the door will
automatically close by mechanical governed closure. Once the fuse link
is replaced, resetting the door is done by pressing the open button.
D. Alarm Voltage: Type and
voltage must be specified. Available in dry contact, 12 VDU, 24 VDU, 24VAC,
and 115 VA. Alarm can be maintained or applied. To maintain the maximum
fail-safe capability, maintained voltages are recommended.
E. Control Circuit: Shall be reduced to 24
VA. Pre-wired for safety edge to reverse, fuse link release, test key switch and
three-button station.
F. Control Stations: To
be on NEMA 1 surface-mount three-button station with open, close and stop
functions. Momentary contact to open, close and stop.
G. FIRESET 2
Controls: Includes NEMA 1 surface mount test key switch and fuse
link release assembly.
H. Overload Protection: Auto-resetting
overload protection.
2.03 Options
A. Battery Back-up: emergency back-up
system required to provide power to motor operator in the event of power failure.
3.01 Installation
A. Installation: To be by an Atlas Door
authorized representative in accordance with Atlas Door's standards and instructions.

 |
Clopay Building Products Company
Inc. 312 Walnut Street Suite 1600
Cincinnati,OH 45202 1-800-959-9559 |
  |
CM-ATFDSET2-98 Atlas Door is a brand of Clopay
Building Products Company, Inc.©1998 |