   Atlas Door  Atlas Door Commercial  

Atlas Door Commercial - Page 31

 

 

FIRESET™ 2 LABELED SHUTTER & FIRE DOOR OPERATOR
  • Mechanical drop testing at the turn of a switch
  • UL listed motor, approved for both UL & FM labeled shutter and fire doors.
  • Designed for fire doors up to 100 sq. ft.
  • Designed for labeled shutter up to 120 sq.ft.
  • 1/4 HP, 1 pH (115,208 or 230 VA.) 3 pH (208,230 VA.).
  • All electrical components, including motor, are contained within a ENEMA 1 enclosure.
  • Unit weighs approximately 40 lbs. and the dimensions are 9-1/2'' H x 17'' W x 6''D
  • Prewired for:
    -3-Button control station -External interlocks
    -Safety edge to reverse -Fuse -link release
    -Remote test key switch - Applied or maintained alarm signal
  • FIRE POWER control system is standard/allows door to be motorized down while a fire alarm conditions exists

Note: Sensor Edge Options is required with FIRE POWER.

AMPERAGE & HORSEPOWER

MAX SQ. FT. *
MOTOR MODEL LABELED SHUTTER FIRE DOOR HP VOLTAGE PHASE AMP
FSM-25 120sq.ft. 100sq.ft. 1/4 115 1 2.8
      1/4 208 1 1.5
      1/4 230 1 1.4
      1/4 208 3 1.0
      1/4 230 3 0.9
* The actual maximum square footage will depend on the type of endlocks, bottom bar, GA,and the height to width selected.

SPECIFICATIONS

PART 1 GENERAL

1.01 Section Includes

A. Type: The motor will be Atlas Door model FSM-25 as manufactured by Clopay Building Products.

B. Mounting: To be vertical front of hod,

1.02 Related Work

A. Electrical wires, wiring, disconnect switches and conduit are in scope of work of other sections or trades.

PART 2 PRODUCT

2.01 Operator

Motor:Provide high torque, intermittent-duty, squirrel-cage induction electric motor. ODP Motor 1PH, TENV motor 3 PH. Permanent split capacitor motor for single phase applications. Operator is limited to 12 cycles per hour.

B. Reduction: To be parallel shaft gearbox with aluminum die cast housing. Precision-machined gearing, hardened for maximum load capability. Permanently lubricated.

C. Drive: Product shaft to be driven by 41 series roller chain to provide travel of 6'' to 12'' per second.

D. Brake: To be electrically activated magnetic disc type brake.

E. Electrical Enclosure: All electrical components shall be in a NEMA 1 enclosure and pre-wired to terminal black.

F. Reversing Contractor: Heavy-duty, across-the-line reversing type with mechanical interlock. size ''00'' or equivalent.

G. Limit Switches: To be positive direct drive screw type limit switch, enclosed in electrical control box, easily accessible for precision setting or adjusting. Limit switches will retain settings during mechanical governed closure.

2.02 Operation

A. Automatic Powered Closing with FIRE POWER Control System:

If this door is in the open position and an alarm condition occurs, the will automatically close under motor operation. In the event the door should hit an obstruction while closing, it will reverse and return to the full open position, and then begin closing again. If the obstruction is not removed, the door will recycle approximately three (3) times, finally closing and stooping at the lowest possible position. If after the door has finished the cycling mode and the obstruction is removed, the door will proceed to the floor.

B. Automatic Closing: If the door is in the open position and a loss of power occurs, the door will automatically close by mechanical a governed closure. No manual reset is required.

C. Fuse Link Releases: If the door is in the open position and the fuse link melts, the door will automatically close by mechanical governed closure. Once the fuse link is replaced, resetting the door is done by pressing the open button.

D. Alarm Voltage: Type and voltage must be specified. Available in dry contact, 12 VDU, 24 VDU, 24VAC, and 115 VA. Alarm can be maintained or applied. To maintain the maximum fail-safe capability, maintained voltages are recommended.

E. Control Circuit: Shall be reduced to 24   VA. Pre-wired for safety edge to reverse, fuse link release, test key switch and three-button station.

F. Control Stations: To be on NEMA 1 surface-mount three-button station with open, close and stop functions. Momentary contact to open, close and stop.

G. FIRESET™ 2 Controls: Includes NEMA 1 surface mount test key switch and fuse link release assembly.

H. Overload Protection: Auto-resetting overload protection.

2.03 Options

A. Battery Back-up: emergency back-up system required to provide power to motor operator in the event of power failure.

PART 3 EXECUTION

3.01 Installation

A. Installation: To be by an Atlas Door authorized representative in accordance with Atlas Door's standards and instructions.


Clopay Building Products Company Inc.

312 Walnut Street • Suite 1600

Cincinnati,OH 45202 1-800-959-9559

CM-ATFDSET2-98 Atlas Door™ is a brand of Clopay Building Products Company, Inc.©1998

*Request for Information / Request a Catalog
 
 
 
To request more information from Atlas Door, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com