| INSTALLATION Surface Preparation: Concrete shall be in place for
7 days(minimum) after forms are removed and must be dry. Surface shall have a smooth
finish (broom finish is not acceptable) and be free of voids, sharp protrusions and form
release agents. Curing agents must be approved by Carlisle. Remove forms as quickly as
possible. When metal decking is used for forms, it must be vented.
Fill holes or voids with non-shrink grout.
Grind or scrape protrusions and outside corner edges. Block or brick walls shall have
mortal joints struck flush. a parget coat may be required for every rough surfaces.
Refer to Carlisle 701 series drawings for
detailed information.
Saw cut cracks greater than 1/16" wide
to 1/4" X 1/4". Clean saw cuts and expansion joints less than 1" wide.
(Contact Carlisle Representative regarding primer). Install backer rod into expansion
joint, fill joints and cracks with approved sealant. Tool sealant flush; allow to cure
over-night.
Install a 1" fillet in all inside
corners. Fillet may be formed with a non-shrink grout or approved sealant.
Apply CCW Primer and allow to dry. Apply
CCW-701 Membrane: 8" wide over sealed cracks, joints, hairline, cracks and cold
joints; 12" wide centered on axis corners.
Penetrations and protrusions should be
water proofed using CCW-703V Liquiseal in accordance with Carlisle 701 series details.
Priming: Stir primer thoroughly.
Apply CCW-702 by spray or with a long nap roller at 250 to 300 ft2
per gallon. At 70º F allow primer to dry; 1 hr (min). Prime only areas to be
waterproofed the same way. Reprime if area becomes dirty. If using CCW-714 Water-based
primer, apply with a low pressure spray at 400-600 ft2
per gallon and allow to thoroughly dry (2-4 hours minimum at 75º F). Primer has a
satisfactory cure when it will not transfer when touched.
Application on Horizontal Surfaces: Apply
CCW-701 Sheet from low to high point, so that laps will shed water. overlaps edge seams
2-1/2", end seams 4" and staggered. Snap a chalk line for a starting point. Pull
2+ feet of release paper and place adhesive side of membrane along chalk line. As the roll
is dispensed, simultaneously roll the release paper and maintain alignment along the chalk
line. immediately after installation, roll sheet with a metal roller wrapped with a
resilient material. Roller should be 18' -24" wide and weigh at least 100 lbs.
Application on Vertical Surfaces:
Apply CCW-701 Sheet Membrane in lengths of 8' or less. Overlaps edge seams 2-1/2". On
walls above 8', apply in 8' sections, starting at the lowest point with the higher section
overlapping the lower section 4". Use a suitable roller to press membrane firmly
against wall.
Terminations: Consult Carlisle
701-9 details for proper terminations. CCW-701 Sheet Membrane should be installed over the
top of a wall; over the edge of a slab. If the membrane must terminate on a vertical
surface, use a reglet, termination bar or counter flashing. Roll terminating edge firmly.
CCW-701 Sheet Membrane shall be installed
on the base of the foundation wall, over the edge of the footing and the terminating edge
pressed firmly against the vertical surface of the footing.
Apply CCW-704 Mastic to all vertical and
horizontal terminations. Apply to raps at angle changes, extending 9" in each
direction.
Note: Failure to use adequate pressure
at terminating edges will result in a poor seal and potential leak. The use of mastic is
not a substitute for a good seal.
Repairs: Inspect all membrane for
tears, punctures, fishmouths, air bubbles or voids due to misalignment at seams. Slit
fishmouths and overlap the edges. Remove damaged membrane. Prime exposed concrete and
allow primer to die. Apply CCW-701 Sheet over damaged area, extending onto sound membrane
6" on all sides. Firmly press and roll repair section to ensure a good seal. apply
CCW-704 Mastic or CCW-703 V Liquiseal to terminating edges of patch.
Protection: CCW-701 Sheet Membrane
must be protected from damage by future operations and other trades. The applicator shall
install suitable protection course material to protect the membrane. The protection course
may be CCW SURE-DRAIN (H or V) or CCW PROTECTION BOARD (H or V).
Install protection course on vertical walls
immediately after installation of the CCW-701 Sheet Membrane. Install protection course on
horizontal application immediately following flood test. If flood test is delayed, install
a temporary covering to protect membrane from damage by other trades.
Flood Test: Plug drains and
provide necessary barriers to contain flood water. Flood deck with a 1" head of water
and allow to stand for 24 hours. Check for leaks and immediately make repairs if required.
Retest after repairs have been made.
Backfill as soon as possible after
successful flood testing.
Storage: Protect materials from excessive
heat and cold. Store materials away from flames or sparks. Outside storage; protect from
rain, direct sunlight or harmful environmental conditions.
LIMITED WARRANTY
CARLISLE COATINGS AND WATERPROOFING INCORPORATED (CARLISLE)
warrants this product to be free of defects in workmanship and materials only at the time
of shipment from our factory. If any CARLISLE materials prove to contain manufacturing
defects that substantially affect their performance, CARLISLE will, at its option, replace
the material or refund the purchase price.
This limited warranty is the only warranty extended by
CARLISLE with respect to its materials. There are no other warranties, including the
implied warranties of merchantability and fitness for a particular purpose. CARLISLE
specifically disclaims liability for any incidental, consequential, or other damages,
including but not limited to, loss of profits or damages to a structure or its contents,
arising under any theory of law whatsoever.
The dollar value of CARLISLE'S liability and buyer's remedy
under this limited warranty shall not exceed the purchase price of the CARLISLE material
in question.