Homepage  
Search
find:
search for:
   
 
Site Navigation
News / Publications
Jobs
Service
   Add this page to Google Bookmarks
   Add this page to Mister Wong
   Add this page to del.icio.us
 
   Concrete Reinforcing Steel Institute  CRSI / Engineering Data Report\Number 36 - Field Inspection of Rebar  

Field Inspection of Rebar - Page 3

 

 

PLACING TOLERANCES
Placing tolerances recognize the imprecise nature of the placing operation and allow deviation criteria. ACI 117 Indicates tolerances on clear distance to side forms and resulting concrete surfaces, and on clear distance to formed concrete soffits in the direction of the tolerance. These tolerances are:

Member Size      Tolerance
4 in. + 1/4 in., - 3/8 in.
> 4 in., 12 in. 3/8 in.
> 12 in., 24 in. 1/2 in.
> 24 in. 1 in.

The ACI 117 tolerances for concrete cover measured at right angles to the concrete surface in the direction of the tolerances are:

Member Size      Tolerance
12 in. -3/8 in.
> 12 in. -1/2 in.

    Reduction in concrete cover is permitted by ACI 117. Generally the reduction should not exceed one-third of the specified cover. For formed soffits, the reduction in cover is limited to 1/4 in.
    Uniform spacing or center-to-center distance between rebars in slabs and walls have a tolerance of 3 inches from a theoretical position. Stirrup and tie spacing in beams and columns is plus or minus 1 inch. The tolerance in the longitudinal location of bends and ends of bars in general is plus or minus 2 inches, but at a discontinuous end of a member is reduced to plus or minus 1 inch. The length of lap splices has a tolerance of minus 11/2 inches, obviously a longer splice might be considered safer, hence there is no plus tolerance. Finally the tolerance for embedded length is minus 1 inch. In terms of percentages, these tolerances may be considered liberal, and normally are easily met.
    The tolerance for beam and column forms is plus 1/2 inch, minus 3/8 inch for form dimensions larger than 12 inches. A potential problem occurs if the stirrups or ties are fabricated to the plus tolerance of 1/2 inch when the forms are made to the minus tolerance of 3/8 inch. This has the effect of reducing the clearance to 7/16 inch each side of the stirrup or tie. The inspector must determine whether or not this encroachment on cover is critical. As stated above, ACI 117 permits a reduction in concrete cover of 3/8 inch when the member size is 12 inches or less, and 1/2 inch if the member is over 12 inches in the direction of tolerance. This type of problem should be resolved with the assistance of the design engineer.
    Another example of cover encroachment is a formed footing; the form tolerance is plus 2 inches, minus 1/2 inch, while the rebar tolerance, either straight or bent is plus or minus 1 inch. Again, if the forms are 'minus' and the rebars are 'plus' the cover at each end of the bars is reduced from 3 inches to 21/4 inches. This would be acceptable since the allowed reduction in cover is 1 inch for member sizes in excess of 2 feet.
    For example, the length of a beam which is discontinuous at each end may create a problem if the formwork is 'minus' when at the same time the rebar is 'plus'. Each trade, carpenter and ironworker, can claim that their work is within tolerance, thus squarely putting it into the inspector's lap to make a decision. He must determine whether the encroachment is detrimental to the safety of the structure, or within the allowable limits of reduction in cover.
    Inspection of rebar placement in walls and slabs is usually straight forward and normally no misplacement will be found. Small openings, pipe sleeves, electrical outlets, and similar items may interfere with the exact placement of the rebar, but the ironworker usually will shift the bar to one side or the other to avoid the obstruction. ACI 117 allows a maximum deviation from the specified location of 3 inches. This normally is sufficient provided that the total number of bars in a wall or slab panel is not reduced. Recommendations for spacing of bars in slabs or walls (Appendix C in CRSI's Manual of Standard Practice) should be used to determine first bar spacing if that information is not shown in the contract documents.
    Spacing tolerance for stirrups and ties in beams and columns is also quite flexible. ACI 117 allows a deviation from the specified position equal to the least dimension of the member divided by 12, thus stirrup or tie placement in a 18-inch square beam or column could vary from the specified location by 11/2 inches.

IN-SITU BENDING AND REBENDING
    One of the more controversial construction procedures is the practice of bending and rebending installed rebar. The reasons are many. As an example, the horizontal leg of bent rebars projecting from a wall to become the top bars of a beam may have been improperly placed too low or too high, well in excess of cover and placing tolerances. These bars will require 'straightening' and then 'rebending' to the proper height horizontally. The inspector, after consultation with the engineer, should approve the procedure used to accomplish the task. CRSI's EDR No. 12 can be used as a guide to recommended practice for straightening and rebending embedded rebar.
    In some instances, the use of planned prebent dowels is requested by the contractor. The engineer should approve the procedure and notify the inspector. Similarly, a straight dowel may be planned to be field bent into place, such as an outside face wall vertical bent horizontally to become the slab end top bar. This procedure is intended to facilitate slab formwork erection. Again, the engineer should approve the procedure and notify the inspector. The inspector should discuss the bending procedure with the placing foreman to ensure that the bends conform to the ACI 315 Standard. Where large diameter bars are involved, some amount of heating may be recommended by the design engineer to avoid brittle failure.

LAP SPLICES, MECHANICAL SPLICES, AND WELDED SPLICES
    The location and length of lap splices has always been a concern of the engineer, estimator, detailer, placer, and inspector. The ACI 318 Building Code states that the design drawings shall show the location and length of lap splices, and the type and location of mechanical splices and welded splices. ACI 315 repeats the above requirement and further instructs the detailer to follow the engineer's details, thus both the placing drawing and the structural drawing should show the same location and length of lap splices. Chapter 12 of ACI 318 contains provisions for tension lap splice lengths. Lengths will vary due to concrete compressive strength, steel grade, bar spacing, epoxy coating and concrete cover. The inspector should make certain that the tabulated lengths are for the strength criteria of the material furnished to the job site, and that the placer follows them.
    Mechanical splices are not difficult to inspect. The engineer should approve the use of the splice furnished, and his drawings should show the location of all splices. If a full mechanical splice is required, the inspector should make certain that a compression only mechanical splice is not furnished in error. In all cases, inspection should verify that the manufacturer's installation procedures, and any project specification instructions are followed. Dowel bar mechanical splices and lap-splice connector systems are used to replace prebent or other types of dowels which connect two separate pours of a concrete structure. The type and location should be approved by the engineer.

*Request for Information / Request a Catalog
 
 
 
To request more information from Concrete Reinforcing Steel Institute, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com