The Spectron ILS System Difference |
Self-Testing/Self-Diagnostics
The Spectron ILS difference starts with self-testing/self-diagnostic
electronics that feature:
- Monitoring of over 160 system parameters
- Logging into memory the 20 most recent alarms and inverter
events
- Automatic weekly subsystems testing
It also offers:
- Programmable monthly and annual discharge tests
- Year 2000 compatibility
- 1998 UL 924 testing requirements approval
|
| Spectron ILS Systems adjust
automatically to support all load combinations |
|
Electronic Features And Benefits
In addition to self-testing/self-diagnostics, factor in these
exceptional electronic features:
Inverter Type
Ferroresonant-design, "no-break" AC output
Output Ratings
1.25 to 15KVA (single phase)
Available Operating Voltages
120, 208, 240, 277, 347 and 480VAC
Design Reliability
Over 160,000-hour mean time between failure (MTBF)
Operating Environment
32° to 104° F (0° to 40° C)
Voltage Regulation
5% to -8.3% of nominal maximum
Inverter Frequency
60 Hz ± 0.005 Hz maximum
Waveform
Sine wave with 5% or less total harmonic distortion at 100% resistive load
Safety Protection
Automatic overload, short circuit, lightning, surge, back feed and
transient protection
Battery Charger
Programmable, software-controlled, three-step charger available in
5-, 10- and 20-amp sizes
Battery
Battery choices include:
- Sealed lead-calcium (10-year)
- Long-life, sealed lead-calcium (20-year)
- Wet cell nickel-cadmium (25-year)
Compliances
UL 924 and UL 924A listed
UL 1778 Listed
cUL Listed to CSA C22.2 #107.1-M91
FCC Class A
Meets NEC, OSHA and Life Safety Code
Warranty
Unit
- Two-year full warranty on cabinet(s) and electronics
Battery
- Lead-calcium: 1 year full plus 9 years pro-rata
- Long-life lead-calcium: 1 year full plus 14 years pro-rata
- Nickel-cadmium: 1 year full plus 14 years pro-rata
|