INTELLIGENT TURBINE PUMP (VARIABLE SPEED)
SPECIFICATIONS
- The controller shall have a constant green light illuminated
on front cover of enclosure to indicate power is on. A green light flashing shall indicate
the motor is running.
- The controller shall have an RS 485 communications port for
connection compatibility to electronic line leak detection / point of sale units
manufactured by others, or other PC monitoring means.
- Dual Manifold Master Slave Operation
The controller shall have the capability to start a second variable speed turbine on
demand that is manifolded to the same discharge line. On dual manifold systems, one
turbine shall be operated as the "Master." The master will run until such time
that it can no longer support the pre-determined flow rate and shall automatically start
the second turbine (slave).
- The variable frequency controller shall operate on 200
250 volt, single or 3 phase, 50 or 60 HZ.
- The pump and controller shall be manufactured by FE
Petro, Inc., McFarland, WI.
INSTALLATION AND MAINTENANCE
The pump shall have a three-wire field connection and an
easy access ground wire terminal, and shall incorporate a wire seal plug which will
accommodate three wires, plus ground.
The pump shall incorporate a port for line pressure
testing that shall be sealed with a 1/4" NPT pipe plug.
The pump unit shall have a fully extractable head in
order to permit removal of the pump motor assembly without disturbing the discharge piping
or the electrical wiring.
- The product in the pipelines shall be held in place by a
line check valve that shall have a minimum sealing force of 170 lbs. (77 kgs.) when the
pump is not running and a minimum 30 psi of pressure in the pipeline.
- The line check valve shall be independent of the removable
head and shall be easily accessible.
- The removal of the extractable portion of the pump shall not
disturb product in the pipelines downstream of the check valve.
- During the removal of the extractable portion of the pump,
product contained in the discharge manifold of the pump shall drain automatically into the
storage tank.
- The head of the pump shall contain a manual pressure relief
screw to bleed static line pressure to zero through a flow path into the tank. This
feature is required to avoid product escaping into the environment from opening the piping
system for service when the piping is pressurized.
- The pump shall be available with an optional variable
telescoping length feature such that the pump length can be field adjustable from 88"
(223 cm) to 150" (380 cm) in length without disturbing the UL label. Pumps required
shorter or longer than this range shall be accommodated with a shorter or longer variable
length model. This variable length feature shall be standard on all units with model
designations beginning with "IST".
OPERATION
The pump shall have an air / vapor elimination system
that returns air or vapors to the underground storage tank through a tube discharging near
the top of the pump motor assembly.
- The pump unit shall contain a built-in expansion relief
value that relieves pressure above pumping pressure but below 50 psi (345 kpa).
- The pump motor shall utilize the product being pumped for
lubrication of the motor bearings and for cooling the stator, and this fluid shall
discharge into the underground storage tank at the top of the motor.
- The pump shall have syphon capability built into the pump.
- The pump head have a 2" NPT threaded opening for the
installation of mechanical line leak detectors or pressure used in certain electrical line
leak detectors.
|