FE Petro Products
| HOW TO
ORDER VARIABLE LENGTH MODELS |
| SPECIFY MODEL VL1, VL2 OR VL3 FROM
CHART BELOW
MODEL LENGTH = ETD + riser - bottom
clearance
DETERMINING MODEL LENGTH
Effective Tank Diameter (ETD) is the combination of any of
all of the following:
Tank Diameter (to top of 4" bung) + Manway + Sump
Adapter
Riser to be determined by bury depth
BURY
DEPTH |
RISER
LENGTH |
| MIN. |
MAX. |
| 2' |
7" |
7" |
| 2.5' |
7" |
11" |
| 3' |
7" |
17" |
| 4' |
7" |
29" |
| 5' |
7" |
41" |
| 6' |
7" |
53" |
| 7' |
7" |
65" |
Note: Above ground tanks have a minimum riser length of
7".

Note: The VL2 length can be used in 94%
of all known installations. The following information indicates certain installations
where a VL1 or VL3 is required.
| 1/3
HP |
USE VL2 IF MODEL
LENGTH IS 84-147".
Use VL1 if model length is shorter than 84 down to
52".
Use VL3 if model length is longer than 147 up to 209".
|
| 3/4
HP |
USE VAL2 IF MODEL
LENGTH IS 86-149".
Use VL1 if model length is shorter than 86 down to
54".
Use VL3 if model length is longer than 149 up to 211".
|
| 1-1/2
HP |
USE VAL2 IF MODEL
LENGTH IS 89-152".
Use VL1 if model length is shorter than 89 down to
57".
Use VL3 if model length is longer than 152 up to 213".
|
1-1/2
HP
HIGH
PRESSURE |
USE VAL2 IF MODEL
LENGTH IS 90-153".
Use VL1 if model length is shorter than 90 down to
58".
Use VL3 if model length is longer than 149 up to 211".
|
2
HP
VARIABLE
SPEED |
USE VAL2 IF MODEL
LENGTH IS 88-150".
Use VL1 if model length is shorter than 88 down to
56".
Use VL3 if model length is longer than 150 up to 212".
|
|
| HOW
TO ORDER STANDARD EXACT LENGTH UNITS |
| To size pump correctly, the
following information is needed: 1. Pump
Model/Horsepower?
2. Effective tank (Inside) Diameter?
3. Steel or Fiberglass Tank?
4. If Fiberglass:
- Manufacturer?
- Single Wall or Double Wall?
- Will pump mount on tank or on manway?
5. Bury Depth?
6. Containment Sump?
The FE Petro Model Number is designated STP-A-B-C, using
the critical dimensions shown above, where:
A = pump horsepower
B = Model Length
C = Riser Length
Minimum riser length=7". |
|
|

FE Petro, Inc. 4805 Voges
Road P.O.Box 139 McFarland, WI 53558
(608) 838-8786 1-800-225-9787
Fax: (608) 838-6433
|
|