SECTION 13850
FIRE ALARM SYSTEMS |
| 1 .3 REFERENCES
- NFPA 70 - National Electrical Code.
- NFPA 72 - National Fire Alarm Code.
- NFPA 101 - Life Safety Code
1 .4 SYSTEM DESCRIPTION
- The fire alarm system shall be a micro-processor based control system suitable for use
as a local fire alarm system with releasing device service using automatic and manual
initiating devices.
- The system shall provide an 80 character LCD display to indicate all information
associated with the Fire Alarm condition, including type of alarm and location within the
protected premise.
- The system shall provide a non-volatile history buffer to log the time and date of each
occurrence. The history buffer shall be large enough to log all potential alarms without
losing any alarm initiations.
- The system shall activate all control functions within three seconds after receipt of
alarm condition.
- All components shall be U.L. Listed and/or F.M. approved for the intended application.
- All components furnished shall be guaranteed against defect in design, material and
workmanship for a period no less than five years (60 months) provided documented proof of
a service contract by an authorized service contractor covering the full warranty period
is provided upon acceptance of the installation.
|