SECTION 13850
FIRE ALARM SYSTEMS |
1 .5 SUBMITTALS
- General
- Submit under the provisions of Section 01300.
- All references to manufacturers model numbers and other pertinent information
herein is intended to establish minimum standards of performance, function and quality.
Equivalent equipment from other manufacturers may be substituted for the specified
equipment as long as the minimum standards are met.
- For equipment other than specified, the contractor shall supply proof that such
substitute equipment equals or exceeds the features, functions, performance and quality of
the specified equipment.
- Manufacturers Product Data Sheets.
- Material and equipment information shall include manufacturers catalog data sheets
and any pertinent technical data for each component or device used on the system. This
shall include the following:
- Control panel
- Analog smoke sensors
- Manual discharge stations
- Abort stations
- Contact monitoring devices
- Releasing Devices
- Addressable relays
- Addressable supervised output modules
- Graphic Annunciators
- Shop Drawings
- Sufficient information, clearly presented, shall be included to determine compliance
with drawings and specifications.
- Include manufacturers name, model numbers, ratings, power requirements, equipment
layout, device arrangement, complete point-to-point wiring diagrams and conduit layout.
- Complete sequence of operation for all control functions provided by the fire alarm
control panel.
- Show annunciator layout, configuration and terminations.
- Manufacturer's Installation Instructions
- Submit simultaneously with shop drawings, complete operating and maintenance manual.
- Indicate application conditions and limitations of use stipulated by product testing
agency
|