SECTION 13850

FIRE ALARM SYSTEMS

 

1 .6 PROJECT RECORD DOCUMENTS

  1. Submit under the provisions of Section 01700.
  2. Record actual locations of all initiating devices, signaling appliance, end-of-line devices.
  3. Record actual wiring terminations.

1 .7 OPERATION AND MAINTENANCE DATA

  1. Submit under the provisions of Section 01700.
  2. Operating instructions shall be provided.
  3. Maintenance procedures shall be provided.

1 .8 QUALIFICATIONS

  1. Manufacturer:
  1. Company specializing in the manufacturing the products specified in this section for at least ten years.
  2. The name of the manufacturer, part numbers and serial number shall appear on all major components.
  3. All devices, components and equipment shall be the products of a single manufacturer.
  4. All devices, components and equipment shall be new and standards products of the manufacturer’s latest design, suitable to perform the functions intended.
  1. Installation Firm:
  1. The system shall be installed by an experienced firm regularly engaged in the installation of systems similar to those specified in this section. The firm shall have a minimum of five(5) years experience in design, installation, testing and service of fire detection and control systems.
  2. The installer shall be trained and certified by the manufacturer to design, install, test and service the fire detection and control system provided under this section.
  3. The installation firm shall employ a NICET certified fire alarm system designer, level 2 or above, who will be responsible for this project.
  4. The installation firm shall show evidence of a minimum $2,000,000 liability and completed operations insurance policy. These limits shall supersede limits required elsewhere in this specification.
  5. The installation firm shall provide proof of emergency service available 24 hours a day, seven days a week.

1 .9 REGULATORY REQUIREMENTS

  1. System shall conform to the requirements of NFPA 70, NFPA 72 and NFPA 101.
  2. Furnish products listed and classified by Underwriter’s Laboratory Inc. and/or Factory Mutual Research Corporation as suitable for the purpose specified and indicated.
  3. System shall conform to the requirement acceptable to the authority having jurisdiction.

1 .10 MAINTENANCE SERVICE

  1. Furnish service and maintenance of the fire detection and control system for a period of five years from the Date of Substantial Completion.
  2. All labor and material required to maintain the system shall be included in this contract. Any perishable item supplied, such as batteries shall be exempt from this requirement if indicated in the submittal documents.



Request for Information / Request a Catalog from Fike Protection Systems
 
 
 
To request more information from Fike Protection Systems, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.