SECTION 13850
FIRE ALARM SYSTEMS |
| 1 .6 PROJECT RECORD DOCUMENTS
- Submit under the provisions of Section 01700.
- Record actual locations of all initiating devices, signaling appliance, end-of-line
devices.
- Record actual wiring terminations.
1 .7 OPERATION AND MAINTENANCE DATA
- Submit under the provisions of Section 01700.
- Operating instructions shall be provided.
- Maintenance procedures shall be provided.
1 .8 QUALIFICATIONS
- Manufacturer:
- Company specializing in the manufacturing the products specified in this section for at
least ten years.
- The name of the manufacturer, part numbers and serial number shall appear on all major
components.
- All devices, components and equipment shall be the products of a single manufacturer.
- All devices, components and equipment shall be new and standards products of the
manufacturers latest design, suitable to perform the functions intended.
- Installation Firm:
- The system shall be installed by an experienced firm regularly engaged in the
installation of systems similar to those specified in this section. The firm shall have a
minimum of five(5) years experience in design, installation, testing and service of fire
detection and control systems.
- The installer shall be trained and certified by the manufacturer to design, install,
test and service the fire detection and control system provided under this section.
- The installation firm shall employ a NICET certified fire alarm system designer, level 2
or above, who will be responsible for this project.
- The installation firm shall show evidence of a minimum $2,000,000 liability and
completed operations insurance policy. These limits shall supersede limits required
elsewhere in this specification.
- The installation firm shall provide proof of emergency service available 24 hours a day,
seven days a week.
1 .9 REGULATORY REQUIREMENTS
- System shall conform to the requirements of NFPA 70, NFPA 72 and NFPA 101.
- Furnish products listed and classified by Underwriters Laboratory Inc. and/or
Factory Mutual Research Corporation as suitable for the purpose specified and indicated.
- System shall conform to the requirement acceptable to the authority having jurisdiction.
1 .10 MAINTENANCE SE RVICE
- Furnish service and maintenance of the fire detection and control system for a period of
five years from the Date of Substantial Completion.
- All labor and material required to maintain the system shall be included in this
contract. Any perishable item supplied, such as batteries shall be exempt from this
requirement if indicated in the submittal documents.
|