architecture - engineering - construction
Fike Protection Systems
Fike Protection Systems
Fike Protection Systems - Page 6
Fike Protection Systems
SECTION 13850
FIRE ALARM SYSTEMS |
| 2 PRODUCTS
2 .1 MANUFACTURERS
- Fike Protection Systems, Blue Springs, Missouri.
2 .2 CONDUIT AND WIRE
- Conduit
- Conduit shall be installed in accordance with the National Electric Code, NFPA 70.
- All wiring shall be installed in a conduit or raceway. Conduit fill shall not exceed 40
percent of the interior cross sectional area where three or more cables are included
within a single conduit.
- Cables must be separated from any open conductors of Class 1 circuits and shall not be
placed in any conduit, junction box or raceway containing Class 1 cables.
- Wiring for low voltage control, alarm notification, emergency communication and similar
power-limited auxiliary functions may be installed in the same conduit as initiating and
signaling line circuits. The system shall be designed to permit simultaneous operation of
all circuits without interference or loss of signals.
- Conduits shall not enter the control panel or any other component provided except where
entry is specified by the manufacturer.
- Conduit shall be 3/4 inch minimum.
- Wire
- All fire alarm system wiring shall be new.
- Wiring shall comply with local, state and national codes and as recommended by the
manufacturer. Number and size of conductors shall be as recommended by the manufacturer,
but shall be not less than 18 AWG for initiating device and signaling line circuits, and
14 AWG for notification appliance circuits.
- All wiring and cable shall be listed and/or approved by a recognized testing agency for
use with a protective signaling system.
- All field wiring shall be supervised for open circuits, short circuits and grounded
conditions.
- The control panel shall be connected to a separate dedicated branch circuit with a
separate dedicated disconnect switch. This circuit shall be labeled FIRE ALARM.
|