SPECIFICATION FOR A TOTAL FLOOD CLEAN FIRE SUPPRESSION SYSTEM

FOR USE WITH RHINO™ CONTROL PANEL SYSTEM

 
  1. DETECTORS:

The detectors shall be spaced and installed in accordance with the manufacturer's specifications and the guidelines of NFPA No. 72 - 1993 edition.

  1. The Ionization detector shall be a FIKE P/N 67-024, with a 4" (10mm), or a P/N 67-025 with a 6" (15mm) base. *
  2. The Photoelectric detector shall be a FIKE P/N 63-024, with a 4" (10mm) base, or a  P/N 63-025 with a 6" (15mm) base. *
    * Additional detectors and base combinations available from Fike.
  1. MANUAL RELEASE (Electric):

    The electric manual release switch shall be a dual action device which provides a means of manually discharging the Suppression System when used in conjunction with the Fike Rhino Control System.

  1. The Manual Release switch shall be a Fike P/N 10-1638 or a Manual Pull station,  P/N 02-4110.
  2. The Manual Release switch or Manual Pull station shall be a dual action device requiring two distinct operations to initiate a system actuation.
  3. Manual actuation shall bypass the time delay and abort functions shall cause the system to discharge and shall cause all release and shutdown devices to operate in the same manner as if the system had operated automatically.
  4. A Manual Release switch shall be located at each exit from the protected hazard and shall have an advisory sign, Fike P/N 02-3644, provided at each location.
  1. ABORT STATION (Optional):

The optional Abort Station shall be the "Dead Man" type and shall be located next to each manual switch.

  1. The Abort Station shall be a Fike P/N 10-1639.
  2. The Abort Station shall be supervised and shall indicate a trouble condition at the Rhino Control Panel, if depressed, and no alarm condition exists.
  3. "Locking" or "Keyed" abort stations shall not be permitted.
  4. The (optional) Abort Station shall be located adjacent to each manual station and can be furnished in combination with a Manual Release Switch or in combination with a Manual Release Switch and (optional) Digital Countdown Timer (Fike P/N 20-046).
  1. AUDIBLE and VISUAL ALARMS:

Alarm audible and visual signal devices shall operate from the Rhino Control Panel.

  1. The Alarm Bell, Alarm Horn and Horn/Strobe devices shall be Fike P/N’s 20-XXX, or equal in quality, performance and features. An FM-200 label shall be attached to the strobe lens when required.
  2. The visual alarm unit shall be a Fike P/N 20-XXX Vertical Strobe device, or equal in quality, performance and features. An FM-200 label shall be attached to the strobe lens when required.
  3. A Strobe device shall be placed outside, and above, each exit door from the protected space. Provide an advisory sign, Fike P/N 02-3645, at each light location



Request for Information / Request a Catalog from Fike Protection Systems
 
 
 
To request more information from Fike Protection Systems, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.