| SPECIFICATION FOR A MICROMIST®
WATER MIST FIRE SUPPRESSION SYSTEM FOR USE WITH RHINO CONTROL
PANEL SYSTEM |
| SECTION 1 - GENERAL CONDITIONS
- SCOPE:
This specification outlines the requirements for a Fike
Micromist® Water Mist Fire Suppression System with automatic detection and control. The
work described in this specification includes all engineering, labor, materials, equipment
and services necessary, and required, to complete and test the suppression system.
- APPLICABLE STANDARDS AND PUBLICATIONS:
The design, equipment, installation, testing and
maintenance of the Water Mist Suppression System shall be in accordance with the
applicable requirements set forth in the latest edition of the following codes and
standards:
- NFPA No. 750 - Water Mist Fire Extinguishing Systems
- NFPA No. 70 - National Electrical Code
- NFPA No. 72 - National Fire Alarm Code
- Factory Mutual Approval Guide
- Fike Micromist Water Mist Design Manual, P/N 06-153.
The standards listed, as well as all other applicable codes
and standards, shall be used as "minimum" design standards. Also to be
considered are the requirements of the "Authority Having Jurisdiction" and good
engineering practices.
- REQUIREMENTS:
The Water Mist Suppression System installation shall be
made in accordance with the drawings, specifications and applicable standards. Should a
conflict occur between the drawings and the specification, the specification shall
prevail.
- EXCLUSIONS:
The work listed below shall be provided by others, or under
other sections of the specification:
- 120 VAC or 208/220 VAC power supply to the control panel.
- Interlock wiring and conduit for shutdown of HVAC, dampers
and/or electric power supplies, relays or shunt trip breakers.
- Connection to local/remote fire alarm systems, listed
central alarm station(s) or building management system.
|