SPECIFICATION FOR A MICROMIST WATER MIST FIRE SUPRESSION SUPPRESSION SYSTEM FOR USE WITH RHINO™ CONTROL PANEL SYSTEM

 
  1. LIQUID LEVEL DEVICE:

The water cylinder shall be equipped with a liquid level device which shall be wired to a FRCM which shall indicate a trouble/supervisiory condition if the cylinder water level drops and the contacts on the level switch close.

  1. AUDIBLE and VISUAL ALARMS:

Alarm audible and visual signal devices shall operate from the CHEETAH Control Panel.

  1. The Alarm Bell, Alarm Horn and Horn/Strobe devices shall be Fike P/N’s 20-XXX, or equal in quality, performance and features.
  2. The visual alarm unit shall be a Fike P/N 20-XXX Vertical Strobe device, or equal in quality, performance and features.
  3. A Strobe device shall be placed outside and above each exit door from the protected space, and a "Flashing Light" sign, Fike P/N 02-3645, shall be provided at each strobe location.
  1. AUXILIARY PANELS: (Optional)
  1. A Graphic Annunciator panel shall be mounted near the CHEETAH control panel. The graphic annunciator shall show a scale layout of the protected area(s) and have indicator lamps to locate each system detector and/or other system components. The panel shall have a lamp test switch located on the panel face. Other panel options shall be available. Scale shall not be less than 1/8" = 1’-0" or 1:100 m.
  1. SYSTEM and CONTROL WIRING:

All system wiring shall be furnished and installed by the contractor.

  1. All wiring shall be installed in electrical metallic tubing (EMT), or conduit, and must be installed and kept separate from all other building wiring.
  2. All system components shall be securely supported independent of the wiring. Runs of conduit and wiring shall be straight, neatly arranged, properly supported, installed parallel and perpendicular to walls and partitions.
  3. The sizes of the conductors shall be those specified by the manufacturer. Color coded wire shall be used. All wires shall be tagged at all junction points and shall be free from shorts, earth connections (unless so noted on the system drawings), and crosses between conductors. Final termination’s between the CHEETAH control panel and the system field wiring shall be made under the direct supervision of a factory trained representative.
  4. All wiring shall be installed by qualified individuals, in a neat and workmanlike manner, to conform to the National Electrical Code, Article 725, and Article 760, except as otherwise permitted for limited energy circuits, as described in NFPA 72 -1993 edition. Wiring installation shall meet all local, state, province and/or country codes.
  5. The complete system electrical installation, and all auxiliary components, shall be connected to earth ground in accordance with the National Electrical Code.



Request for Information / Request a Catalog from Fike Protection Systems
 
 
 
To request more information from Fike Protection Systems, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.