| SECTION 2 - AGENT REQUIREMENTS
- SYSTEM DESCRIPTION AND OPERATION:
The system shall be a Total Flood FM-200 Suppression
System supplied by:
FIKE Protection Systems
704 South 10th Street
Blue Springs, MO. 64015
The system shall provide an FM-200 minimum design
concentration of __ %, by volume, in all areas and/or protected spaces, at the minimum
anticipated temperature within the protected area. System design shall not exceed the
NOAEL value of 9.0%, adjusted for maximum space temperature anticipated, unless provisions
for room evacuation, before agent release, are provided.
The system shall be complete in all ways. It shall
include all mechanical and electrical installation, all detection and control equipment,
agent storage containers, FM-200 agent, discharge nozzles, pipe and fittings, manual
release and abort stations, audible and visual alarm devices, auxiliary devices and
controls, shutdowns, alarm interface, caution/ advisory signs, functional checkout and
testing, training and all other operations necessary for a functional, U.L. Listed and/or
F.M. approved FM-200 Clean Agent Suppression System.
Provide two (2) inspections during the first year of
service. Inspections shall be made at 6 month intervals commencing when the system is
first placed into normal service.
The general contractor shall be responsible for sealing and
securing the protected spaces against agent loss and/or leakage during the 10 minute
"hold" period.
The system(s) shall be actuated by a combination of
ionization and/or photoelectric detectors installed at a maximum spacing of 250 sq. ft.
(23.2 sq. mtr) per detector, in both the room, underfloor and above ceiling protected
spaces. If the air flow is one air change per minute, photoelectric detectors only shall
be installed at a spacing not to exceed 125 sq. ft. (11.6 sq. mtr) per detector. (Ref.
NFPA No. 72 - Chapter 5 - 1993 edition)
Detectors shall be wired in FIKE'S "Sequential
Detection" method of operation, standard Cross-Zoned detection, or single detector
release, using either a Class "A" or Class "B" wiring arrangement. No
other detection / wiring arrangements will be acceptable.
Automatic operation of each protected area shall be as
follows:
- Actuation of one (1) detector, within the system, shall:
- Illuminate the "ALARM" lamp on the control panel
face.
- Energize an alarm bell and/or an optional visual indicator.
- Transfer sets of 5 Amp rated auxiliary contacts which
can perform auxiliary system functions such as:
- Operate door holder/closures on access doors.
- Transmit a signal to a fire alarm system.
- Shutdown HVAC equipment.
- Light an individual lamp on an optional graphic annunciator.
- Actuation of a 2nd detector, within the system, shall:
- Illuminate the "PRE-DISCHARGE" lamp on the control
panel face.
- Energize an predischarge horn or horn/strobe device.
- Shut down the HVAC system and/or close dampers.
- Start time-delay sequence (not to exceed 60 seconds).
- System abort sequence is enabled at this time.
- Light an individual lamp on an optional graphic annunciator.
- After completion of the time-delay sequence, the FM-200
Clean Agent system shall discharge and the following shall occur:
- Illuminate a "SYSTEM FIRED" lamp on the control
panel face.
- Shutdown of all power to high-voltage equipment
- Energize a visual indicator(s) outside the hazard in which
the discharge occurred.
- Energize a "System Fired" audible device.
(Optional)
- The system shall be capable of being actuated by manual
discharge devices located at each hazard exit. Operation of a manual device shall
duplicate the sequence description above except that the time delay and abort functions
SHALL be bypassed. The manual discharge station shall be of the electrical actuation type
and shall be supervised at the main control panel.
|