| SECTION 15360
CARBON DIOXIDE
EXTINGUISHING SYSTEMS |
| 2.03 ELECTRICAL COMPONENTS
- Detection System, Single Zone:
- The control panel used shall be a Fike model SHP P/N
10-051-X-X or Rhino P/N 10-2161-X where an automatic control system is required to
activate the fixed carbon dioxide system.
- The control system is used to operate a single fixed
fire suppression or alarm system based on inputs received from approved detection devices.
- Detection circuits to be configured using cross-zone,
verified detection or single input release concepts.
- System shall have an adjustable pre-discharge time delay
circuit to allow evacuation of the protected area prior to the discharge of carbon
dioxide.
- System shall be U.L. listed and F.M. approved and shall
comply with all requirements of NFPA Standards 12, 71, 72A and 72D.
- Detection System, Multi-Zone:
- The control system used shall be a Fike INTELLA-SCAN II or
Cheetah multi-zone control system where an automatic system is required to activate and
coordinate multiple zones of fixed carbon dioxide systems.
- All inputs shall be analog or addressable; configured as
cross-zone, verified detection or single input release concepts.
- System shall have an adjustable pre-discharge time delay
circuit to allow evacuation of the protected area prior to the discharge of carbon
dioxide.
- System shall be microprocessor based and field programmable
using a computer/software interface.
- System shall be capable of remote site status reporting via
fiber-optic or modem communication means.
- System shall be capable of providing addressable output
functions.
- System shall be U.L. listed and F.M. approved and shall
comply with all requirements of NFPA Standards 12, 71, 72A and 72D.
PART 3 EXECUTION
3.01 INSTALLATION
- The contractor shall install the system in accordance with
the manufacturers design, installation, recharge and maintenance instructions by a
factory trained and authorized distributor.
- The system shall be installed in accordance with all
applicable NFPA 12 requirements.
3.02 EXAMINATION
- Verification of Conditions: The contractor shall verify that
the hazard is being protected by a carbon dioxide system that meets the requirements of
NFPA 12.
- Functional Testing:
- After system installation is complete, a functional test of
the control devices shall be performed without actually firing the cylinder(s).
- Verification of all system auxiliary functions shall be
made.
- A thorough inspection of the distribution piping, supports
and nozzles shall be made.
3.03 FIELD TESTING
- Field testing of the system shall be conducted by personnel
that are trained and authorized by the system manufacturer.
Field testing can be waived by the authority having
jurisdiction. Delete Article 3.03 if testing is not required.
3.04 TRAINING
- Instruct the owners personnel in the operation of the
[equipment] [system] under the provisions of Section [01670.] [ _______.]
|