SPECIFICATION FOR A TOTAL FLOOD CLEAN AGENT FIRE SUPRESSION  SYSTEM FOR USE WITH THE SHP™ CONTROL PANEL SYSTEM

 

SECTION 1 - GENERAL CONDITIONS

  1. SCOPE:

This specification outlines the requirements for a "Total Flood" Clean Agent Fire Suppression System with automatic detection and control. The work described in this specification includes all engineering, labor, materials, equipment and services necessary, and required, to complete and test the suppression system.

  1. APPLICABLE STANDARDS AND PUBLICATIONS:

The design, equipment, installation, testing and maintenance of the Clean Agent Suppression System shall be in accordance with the applicable requirements set forth in the latest edition of the following codes and standards:

  1. NFPA No. 2001 - Clean Agent Fire Extinguishing Systems
  2. NFPA No. 12A - Halon 1301 Fire Extinguishing Systems
  3. NFPA No. 70 - National Electrical Code
  4. NFPA No. 72 - Standard For Protective Signaling
  5. Factory Mutual Approval Guide
  6. U.L Listings
  7. Requirements of the Authority Having Jurisdiction (AHJ)

The standards listed, as well as all other applicable codes and standards, shall be used as "minimum" design standards. Also to be considered are the requirements of the "Authority Having Jurisdiction" and good engineering practices.

  1. REQUIREMENTS:

The FM-200 Suppression System installation shall be made in accordance with the drawings, specifications and applicable standards. Should a conflict occur between the drawings and specifications, the specifications shall prevail.

  1. EXCLUSIONS:

The work listed below shall be provided by others, or under other sections of this specification:

  1. 120 VAC or 208/220 VAC power supply to the control panel.
  2. Interlock wiring and conduit for shutdown of HVAC, dampers and/or electric power supplies, relays or shunt trip breakers.
  3. Connection to local/remote fire alarm systems, listed central alarm station(s) or sprinkler preaction/deluge valve actuation.



Request for Information / Request a Catalog from Fike Protection Systems
 
 
 
To request more information from Fike Protection Systems, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.