SPECIFICATION FOR A TOTAL FLOOD CLEAN AGENT FIRE SUPRESSION  SYSTEM FOR USE WITH THE SHP™ CONTROL PANEL SYSTEM

 

SECTION 3 - ELECTRICAL REQUIREMENTS

  1. CONTROL PANEL
  1. The control panel shall be a SHP (Single Hazard Panel) Control System, P/N 10-051-X-X, manufactured by Fike Protection Systems, Blue Springs, MO.
  2. The SHP Control System, and its components, shall be UL listed and FM approved for releasing service and be suitable for Deluge Pre-action sprinkler service.
  3. The SHP Control System shall perform all functions necessary to operate the system detection, actuation and auxiliary functions, as outlined.
  4. The SHP Control System shall be capable of providing 7AH or 17AH battery standby power supplies.
  5. The SHP Control System shall be microprocessor based with hardware and software integration designed to guarantee reliability.
  6. The SHP Control System shall support Cross Zoned, Sequential, Single Detector Release and Manual Release detection/actuation methods.
  7. The SHP Control System shall provide the following capabilities and functions:
  1. Three (3) Class B (Style Y) indicating appliance circuits rated for 2.0 amps @ 24 VDC.
  2. Four (4) Class B (Style A) initiating circuits
  3. Optional Class A (Style D) module for initiating circuits
  4. Eight (8) Status LEDs plus alpha-numeric display for troubleshooting: AC normal; alarm; pre-discharge; release; supervisory; trouble; alarms silenced and system abort.
  5. Programmable pre-discharge and discharge timers
  6. Resettable and continuous auxiliary output power
  7. Five (5) optional Abort types
  8. Intelligent Transistor protection to prevent noise spikes and microprocessor failure from inadvertently activating release outputs
  9. A dedicated Disarm switch for release outputs
  10. Dedicated alarm and trouble contacts programmable for alarm, trouble, pre-discharge, discharge, abort, supervisory or waterflow functions, depending on panel configuration.
  11. Two (2) Form "C" relays, rated at 5 amps, are provided on the SHPä panel board. Installation of the optional SRM4 Relay Module (P/N 10-2176) will provide four (4) additional 5 amp relays.
  12. Multiple input power source - 120 VAC or 208/220 VAC @ 50/60 Hz
  13. 2.6 amp @ 24 VDC power supply to operate high current draw horns and strobes. Capable of allowing expansion to 8 amp external power supply for a total of 10.6 amps of available power.
  14. Available in either Red or Gray finish

 

  1. DETECTORS:

The detectors shall be spaced and installed in accordance with the manufacturer's specifications and the guidelines of NFPA No. 72 - 1993 edition.

  1. The Photoelectric detector shall be a Fike P/N 63-024, with a 4" (10mm) base or a P/N 63-025 with a 6" (15mm) base. *
  2. The Ionization detector shall be a Fike P/N 67-024, with a 4" (10mm) base, or a P/N 67-025 with a 6" (15mm) base. *
    * Additional detector and base combinations available from Fike Protection Systems.
  1. MANUAL RELEASE (Electric):

The electric manual release switch shall be a dual action device which provides a means of manually discharging the Suppression System when used in conjunction with the Fike SHP Control System.

  1. The Manual Release switch shall be a Fike P/N 10-1638 or a Manual Pull station, P/N 02-4110.
  2. The Manual Re lease switch or Manual Pull station shall be a dual action device requiring two distinct operations to initiate a system actuation.
  3. Manual actuation shall bypass the time delay and abort functions, shall cause the system to discharge and shall cause all release and shutdown devices to operate in the same manner as if the system had operated automatically.
  4. A Manual Release switch shall be located at each exit from the protected hazard and shall have an advisory sign, Fike P/N 02-3644, provided at each location.



Request for Information / Request a Catalog from Fike Protection Systems
 
 
 
To request more information from Fike Protection Systems, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.