| UL SPECIFIED RECEPTACLE
CONFIGURATIONS |
| NAMEPLATE RATING |
WALL
RECEPTACLE NUMBER |
RECEPTACLE
CONFIGURATION |
| VOLTS |
MAX
UNIT AMPS* |
|
|
| 230/208 |
12.0 |
NEMA6-15R |
 |
| 230/208 |
16.0 |
NEMA
6-20R |
 |
| 230/208 |
24.0 |
NEMA
6-30R |
 |
| All
265 volt units must be permanently connected. Conduit assembly, factory or field-supplied,
can be wired directly to the unit. |
* This is normally the electric heating amps, except
for cooling only models.
| TE/TH GUIDE SPECIFICATIONS |
The supplier will furnish packaged terminal air
conditioners or heat pumps in the capacities shown on the specifications. The minimum
efficiency levels shall be no less than____ EER.
Units shall be certified in accordance with ARI Standard
310 for air conditioners and ARI Standard 380 for heat pumps. All units shall be UL
listed.
Basic unit dimensions shall not exceed 42 in. wide and 16
in. high. Overall depth of the unit from the rear of the wall sleeve to the front of the
front panel shall not exceed 18-½ in. Overall depths of the unit from the rear of the
wall sleeve to the front of the front panel shall not exceed 20-½ in. (NOTE: Deep wall
sleeve extension may add up to 4 in. additional depth on all models.)
Refrigeration System
The refrigeration system shall consist of a hermetically
sealed rotary compressor that is externally mounted on vibration isolators, condenser and
evaporator coils constructed of copper tubes and aluminum plate fins and capillaries as
refrigerant expansion devices.
The coils shall be of a draw-through design to facilitate
cleaning. The compressor and fan motor shall be located in a separate compartment that is
isolated from condensate splatter.
Air Handling Section
The indoor and outdoor fans shall consist of tangential
blower wheels driven by one permanently lubricated split capacitor motor.
Air flow shall be directed into the room by a
polycarbonate discharge grille that is factory preset to provide maximum air circulation
into the room. The grille shall be owner adjustable to 10 degrees off the vertical. A fine
mesh screen shall be used in the ventilation air stream.
Controls
Covered controls on the top-front of the unit shall include
a push button mode selector switch, rotary thermostat control and a rocker switch to
select the fan speed.
The thermostat knob and the push buttons shall not be
removable by the user. The buttons on the switch shall be sized and spaced to prevent the
possibility of depressing two buttons at one time.
The control panel shall be easy to read and understand with
the markings for the mode selection no smaller than 14 point type. International symbols
shall be used. A room temperature limiting device, inaccessible to the user, shall be
owner adjustable.
Restricted to the user, but accessible without removing the
front panel, shall be the fan cycle switch, the vent control, and the emergency heat
compressor override switch (on heat pump models). The fan cycle switch shall select
continuous or intermittent fan operation, whereby the blowers cycle with the compressor or
heater.
General Construction
The wall sleeve shall be constructed of 18 ga. G90
zinc-coated steel. It shall be prepared by a process where it is zinc phosphate pretreated
and sealed with a chromate rinse, then electrostatically coated with a polyester finish,
and oven cured for durability. It shall be insulated for thermal efficiency. The sleeve
shall be shipped with a protective weatherboard and a structural center support.
The outdoor grille shall be shipped separately. The grille
shall be fabricated from stamped or extruded anodized aluminum. Louvers shall be in a
horizontal pattern.
The front panel shall lock to the chassis, thereby
providing a tamper-resistant design. The front panel shall have a contoured air discharge
with no sharp corners. The air filter shall be a slide-out, top-mount design and removable
without opening or removing the front panel.
The unit shall be capable of mounting flush with the carpet
and shall possess a recessed, front return to provide toe-space clearance.
All 265 volt units shall possess an integral over-current
time-delay protective device.
Limited Warranty
First Year: Parts and labor on the entire unit. Second
through Fifth year: Parts and labor on the sealed refrigeration system and Flex Drive®
systems. See the warranty document for complete details.
SPECIFICATION SUBJECT TO CHANGE WITHOUT NOTICE |