architecture - engineering - construction
AECinfo.com
Printable version Bookmark this page Notify a colleague or friend about this page Bookmark and Share
  GS Metals   GLOBETRAY  

GLOBETRAY - Solid Bottom Straight Section - Aluminum

   

GLOBETRAY

GLOBETRAY®  CABLE TRAY SYSTEMS

SOLID-BOTTOM STRAIGHT SECTIONS

ALUMINUM
3, 4 & 6-IN.
Nominal Depths
(use with GLOBETRAY Trough Fittings)

 

AVAILABLE PRODUCTS

Inside Depth: 3-1/2", 4-1/2", 6-1/2"
Inside Width: 6", 9", 12", 18", 24", 30", 36"
Length: 12 ft. (up to 24 ft. lengths available on inquiry)
Nominal Thickness: .080" min.
Options: PVC or other special coating upon written request.

 

gbt034a.gif (23505 bytes)

 

gbt034b.gif (15061 bytes)

gbt034c.gif (12037 bytes)

 

CATALOG
NO.
6 FT. 8 FT. 10 FT. 12 FT.
LOAD
LBS. / FT.
DEFL.
-IN.
LOAD
LBS. / FT.
DEFL.
-IN.
LOAD
LBS. / FT.
DEFL.
-IN.
LOAD
LBS. / FT.
DEFL.
-IN.
AS00-SS00-0600-3
AS00-SS00-0900-3
AS00-SS00-1200-3
AS00-SS00-1800-3
AS00-SS00-2400-3
AS00-SS00-3000-3
AS00-SS00-3600-3
212
212
212
170
126
102
84
.12
.12
.12
.10
.07
.06
.05
171
171
171
170
126
102
84
.26
.26
.26
.26
.19
.16
.13
110
110
110
110
110
102
84
.42
.42
.42
.42
.42
39
.32
77
77
77
77
77
77
77
.61
.61
.61
.61
.61
.61
.61
Deflection for
One Lb. / Lin. Ft.
1 .0006 1 .0015 1 .0038 1 .0079
AS00-SS00-0600-4
AS00-SS00-0900-4
AS00-SS00-1200-4
AS00-SS00-1800-4
AS00-SS00-2400-4
AS00-SS00-3000-4
AS00-SS00-3600-4
376
336
252
169
127
101
84
.16
.14
.11
.07
.05
.04
.04
213
213
213
169
127
101
84
.29
.29
.29
.23
.17
.14
.12
137
137
137
137
127
101
84
.45
.45
.45
.45
.42
.34
.28
96
96
96
96
96
96
84
.65
.65
.65
.65
.65
.65
.57
Deflection Ft.
One Lb. / Lin. Ft.
1 .0004 1 .0014 1 .0032 1 .0068
AS00-SS00-0600-6
AS00-SS00-0900-6
AS00-SS00-1200-6
AS00-SS00-1800-6
AS00-SS00-2400-6
AS00-SS00-3000-6
AS00-SS00-3600-6
453
336
252
169
127
101
84
.07
.05
.04
.02
.02
.01
.01
256
256
252
169
127
101
84
.11
.11
.11
.07
.05
.04
.04
164
164
164
164
127
101
84
.17
.17
.17
.17
.13
.11
.09
116
116
116
116
116
101
84
.25
.25
.25
.25
.25
.22
.18
Deflection for
One Lb. / Lin. Ft.
1 .0002 1 .0004 1 .0010 1 .0022

Side Rail Governs
Bottom Governs

Allowable loads and deflections are applicable to cable tray supported as a simple span and without splice connectors located in the span. See load reduction factors to be used when splice connectors occur at midspan.