ACCESSORY ITEMS



| DISCHARGE DAMPER |
DISCHARGE LOUVERS*** |
(*) Use Intake Damper (LxM) for SB-222, 227, 233 &
240
(**) Base Channel on SB-222, 227, 233 & 240 Only.
6" on SB-240.
(***) 2 Lourvers Required on SB-215 thru SB-240 (****)
Coil Section
| Model |
A |
B |
C |
D |
E |
F |
G |
H |
J |
K |
L |
M |
N |
P |
Q |
R |
S |
T |
U |
V |
| SB-112 |
26-1/2 |
33 |
35- 7/8 |
24- 3/8 |
39- 1/2 |
8- 7/8 |
7- 1/4 |
12 |
27 |
4- 4/8 |
23- 3/8 |
29- 7/8 |
12 |
13- 1/2 |
16- 1/4 |
4" |
8" |
8- 5/8" |
16- 1/4 |
28 |
| SB-115 |
35 |
40 |
43- 3/4 |
26 |
44- 3/4 |
7 |
9- 1/2 |
16 |
30- 1/2 |
4- 3/4 |
31- 7/8 |
36- 7/8 |
12 |
16- 5/8 |
19- 3/4 |
4" |
8" |
8- 5/8 |
19- 3/4 |
28 |
| SB-215 |
35 |
75-1/8 |
43- 3/4 |
26 |
61- 3/4 |
18- 1/2 |
3 |
29 |
64 |
7- 5/8 |
31- 7/8 |
72 |
12 |
18- 1/4 |
55- 3/8 |
4" |
8" |
8- 5/8" |
19- 3/4 |
28 |
| SB-218 |
39 |
79-1/8 |
47- 1/4 |
26 |
61- 3/4 |
18- 1/2 |
5 |
29 |
68 |
7- 5/8 |
35- 7/8 |
76 |
12 |
18- 7/8 |
58- 3/8 |
4" |
8" |
8- 5/8" |
21- 7/8 |
28 |
| SB-222 |
49 |
96-5/8 |
56- 3/8 |
30 |
76- 3/4 |
- |
- |
29- 1/8 |
87- 1/2 |
13- 1/8 |
45- 7/8 |
93- 5/8 |
12 |
24- 1/4 |
76 |
4" |
8" |
8- 5/8" |
27- 3/4 |
28 |
| SB-227 |
58 |
114-3/8 |
59- 3/8 |
30- 7/8 |
89- 3/8 |
- |
- |
40- 7/8 |
105- 1/4 |
13- 1/8 |
54- 7/8 |
111- 1/4 |
12 |
34- 1/4 |
89 |
4" |
8" |
8- 5/8" |
34- 1/4 |
28 |
| SB-233 |
67 |
141 |
58- 7/8 |
30- 3/4 |
99- 3/4 |
- |
- |
51- 3/8 |
131- 3/4 |
13- 1/8 |
63- 7/8 |
137- 7/8 |
12 |
34- 1/4 |
115 |
4" |
8" |
8- 5/8" |
44- 3/4 |
28 |
| SB-240 |
80 |
186 |
66 |
36 |
111 |
- |
- |
56- 3/8 |
176- 3/4 |
13- 5/8 |
76- 7/8 |
182- 7/8 |
12 |
40- 7/8 |
(2)53- 3/4 |
4" |
8" |
8- 5/8" |
53- 3/4 |
28 |
(1) All dimensions in inches.
(2) Approximate pressure drop for accessory items: Filter
(dirty) 1/4" intake hood 1/8", birdscreen 1/8", discharge louver 1/4".
Damper resistance may be ignored.
EQUIPMENT SPECIFICATIONS
| SECTION |
DESCRIPTION |
SB-112 |
SB-115 |
SB-215 |
SB-218 |
SB-222 |
SB-227 |
SB-233 |
SB-240 |
| BLOWER |
Discharge Arrangement |
Horizontal Unit with Choice of
HR-1 (Horizontal) or HR-2 (Down) |
| Construction |
Aluminized Steel Casing -
Bolted Construction |
| Casing Gauge |
18 |
18 |
16 |
16 |
16 |
16 |
16 |
14 |
| Outside Surface Finish |
Primed with Zinc-Chromate, Finish
Coat of Enamel |
| Type of Fans |
Centrifugal,Forward Curved , DWDI
,Class of Enamel |
| Number of Fans |
1 |
1 |
2 |
2 |
2 |
2 |
2 |
2 |
| Outlet Area (Sq. Ft.) |
1.53 |
2.28 |
4.99 |
5.73 |
9.33 |
16.35 |
21.19 |
30.51 |
| Ball Bearings |
Self Aligned and Prelubricated
Pillow Block or Flange Mounted |
| Lubrication |
Means for
Relubrication |
| Bearing Size (Inches) |
1 |
1 3/16 |
1 11/16 |
1 11/16 |
1 7/16 |
1 11/16 |
1 15/16 |
2 7/16 |
| Shaft Diameter (Inches) |
1 |
1 3/16 |
1 11/16 |
1 11/16 |
1 7/16 |
1 11/16 |
1 15/16 |
2 7/16 |
| Motor Location |
Internal
Mounting |
| Drives |
Ajustable
Standard thru 10 HP; Fixed Standard above 10 HP, Adjustable Optional |
| General |
Wheels Statically
& Dynamically Balanced, Mounted on Seperate Frame |
| FILTER (OPTIONAL) |
Arrangement |
V-Bank |
| Casing Gauge |
18 |
18 |
18 |
18 |
16/18 |
14/16 |
14/16 |
14/16 |
| Number of Filters |
4 |
8 |
12 |
12 |
24 |
30 & 6 |
49 |
49 & 7 |
| Size (Inches) |
16x20x2 |
20x20x2 |
20x25x2 |
20x25x2 |
16x25x2 |
20x25x2 and 16x25x2 |
20x25x2 |
24x24x2 and 12x24x2 |