| FAN PERFORMANCE CURVES The following fan curves were developed from test data taken in
accordance with AMCA standards for forward curved fans. Belt losses are not included. For
TSP greater than listed on the individual fan curves shown, contact factory for backward
incline fan selections.
FAN SELECTION EXAMPLE
PROBLEM:
Select SB ventilating unit and motor horsepower to deliver
6,000 SCFM at 1.50" w.c. total static pressure. Desired motor type is single speed,
1800 RPM, drip-proof.
SOLUTION:
- Check fan performance curves for smallest SB model which
will handle the specified air flow and total static pressure. This proves to be the
SB-115.
- Locate 6,000 SCFM on the horizontal axis of the SB-115 fan
performance curve and move vertically to the point of intersection with the 1.50"
w.c. total static pressure line. This defines the operating point; fan speed wil be 920
RPM and the motor will draw 3.5 HP. The next larger size motor, 5 HP, is required.
- From the Reference Table on this page, we find that the 5
HP, 1800 RPM, dripproof motor has a 184T frame size. This size is smaller than the maximum
motor frame size of 213T shown on SB-115 fan performance curve, so selection is
acceptable.
- From the SB-115 performance curve, the fan outlet velocity
is shown to equal SCFM/2.28. At the operating point of the selected unit, the outlet
velocity is 6,000/2.28 or 2,632 FPM.
MOTOR FRAME SIZE REFERENCE TABLE
MOTOR HP |
MOTOR TYPE |
| 1800 RPM
Dripproof or TEFC |
1800/900
RPM One Winding |
1800/1200
RPM Two Winding |
| Dripproof |
TEPC |
Dripproof |
TEFC |
| 1.5 |
145T |
145T |
145T |
145T |
145T |
| 2 |
145T |
145T |
145T |
182T |
182T |
| 3 |
182T |
182T |
182T |
184T |
184T |
| 5 |
184T |
184T |
184T |
215T |
215T |
| 7.5 |
213T |
213T |
215T |
254T |
254T |
| 10 |
215T |
215T |
215T |
256T |
256T |
| 15 |
254T |
256T |
256T |
284T |
284T |
| 20 |
256T |
284T |
284T |
286T |
286T |
| 25 |
284T |
286T |
286T |
324T |
324T |
| 30 |
286T |
286T |
324T |
324T |
326T |
| 40 |
324T |
324T |
326T |
326T |
364T |
| 50 |
326T |
326T |
364T |
365T |
365T |
| 60 |
364T |
365T |
365T |
404T |
404T |
| 75 |
365T |
405T |
405TS |
405T |
444T |
| 100 |
404T |
405T |
444T |
444T |
445T |
| 125 |
405T |
444T |
445T |
445T |
445T |
NOTES:
1) All motors are three phase.
2) Motors less than 1.5 HP have frame sizes that will fit
within any SB model ventilating unit cabinet.
3) SB-240 maximum frame size, 405T. For larger frame sizes
consult factory.
STANDARD ENERGY EFFICIENT MOTOR
REFERENCE TABLE
| NOMINAL
FULL-LOAD EFFICIENCY |
MOTOR HP |
1800 RPM |
| |
Dripproof |
TEFC |
| 1.5 |
84.0 |
84.0 |
| 2 |
84.0 |
84.0 |
| 3 |
86.5 |
87.5 |
| 5 |
87.5 |
87.5 |
| 7.5 |
88.5 |
89.5 |
| 10 |
89.5 |
89.5 |
| 15 |
91.0 |
91.0 |
| 20 |
91.0 |
91.0 |
| 25 |
91.7 |
92.4 |
| 30 |
92.4 |
92.4 |
| 40 |
93.0 |
93.0 |
| 50 |
93.0 |
93.0 |
| 60 |
93.6 |
93.6 |
| 75 |
94.1 |
94.1 |
| 100 |
94.1 |
94.5 |
| 125 |
94.5 |
94.5 |
|