MODEL DESIGNATION
| Compressor
Make and Type C- Copeland Accessible Hermetic
F- Copeland Full Hermetic |
Compressor
Number S- Single
D- Dual |
Base Model
(HP-total) |
FEATURES
HASTINGS Air Cooled Condensing Units have been
designed to offer a complete family of units to cover high temperature air cooled
condensing unit requirements from 3 through 80 tons. Polyphase fan motors are used
for high reliability and minimum maintenance. Fans are aluminum bladed, direct drive, and
selected for minimum noise. Compressors are matched to condensers for optimum efficiency.
CABINET is constructed entirely of mill galvanized sheet
steel panels and formed steel channel base. All panels are removable for access and
service.
MOTORS are three phase, 1140 RPM, specifically designed for
vertical shaft, direct drive fan application and utilize permanently lubricated ball
bearings. Corrosion resistant steel rod mounting brackets reduce air turbulence and
eliminate vibration.
FANS are direct drive propellor type with steel hubs and
aluminum blades. Vertical air discharge through a formed venturi minimizes noise
generation and air recirculation.
CONDENSER COILS are constructed with seamless copper tubes
arranged in a staggered row pattern and mechanically expanded into plate type configured
aluminum fins with full collars. A separate sub-cooling coil, integral with the
condenser, is provided on each circuit to eliminate the possibility of liquid
flashing and to increase unit efficiency.
COMPRESSORS for the "F" Series are full hermetic,
direct drive by 2 pole motor, complete with inherent overload protection. Motor Compressor
units have internal suspension system to eliminate vibration. Compressors are mounted on
rubber shock mounts, and are standard with crankcase heaters.
COMPRESSORS for the "C' Series are accessible
hermetic, direct drive by 4 pole motor, complete with overload protection, automatic
reversing, oil pump, oil strainer, oil sight glass, suction and
discharge service valves. All Compressors are mounted on rubber shock mounts, and
all have crankcase heaters. Compressor mufflers are standard for noise elimination.
STANDARD EQUIPMENT
- Direct Drive Condenser Fans
- Liquid Line Shut Off Valve
- Refrigerant Charging Valve
- High Pressure Safety
- Low Pressure Operating Control
- Crankcase Heater
- Fan Guard
- Auto Pumpdown Switch
- Time Delay Between Compressors (Dual Units)
- Low Profile
- Sub Cooling Circuit
- Compressor Overload Protection
- Fan Motor Overload Protection
- Fused Control Circuit
- Compressor Contactor
- Fan Motor Contactor
- Removable Access Panels
- Prewired Controls
- Hinged Control Panel Access
- Rigging Points
- Compressor Service Valves
- Oil Failure Control - "C" only
- Low ambient operation by fan cycling to + 20
deg. F.
- Compressor Fusing (Dual Units)
OPTIONS and ACCESSORIES
- Low ambient operation by fan cycling to ) deg F.
- Low ambient operation by flood control above 20 deg F
(A20).
- Low ambient operation by flood control below 20
deg F (B20).
- Liquid line solenoid mounted and wired.
- Liquid line drier and sight glass mounted.
- High pressure gauge with shut off valve.
- Low pressure gauge with shut off valve.
- Oil pressure gauge with shut off valve ('C series only).
- Control circuit transformer.
- Painted cabinet - Acid etched surface, zinc rich primer and
air dried enamel.
- Standard hot gas bypass. Includes regulator and
solenoid mounted, wired, and stubbed for field connection to the evaporator.
- Capacity modulation by cylinder unloading
- 3 Minute guaranteed off timer for each compressor motor.
(Fixed )
- Manual lead lag switch to sequence starting of compressors.
- Low ambient lockout to preset ambient temperature at which
the machine will not operate.
- Unit fused discount - mounted, wired and ready for incoming
electrical service.
- Contact factory for other options.
- Liquid receiver w/fusible plug.
- Discharge vibrasorber `C' only.
- Suction vibrasorber `C' only
Note: Multiple compressor units are available up to
160 HP, Contact your local Hastings sales representative for information.
In order to maintain or policy of continuous product
improvement, we reserve the right to change price, specifications, ratings or dimensions,