counterflo
INDIRECT-FIRED INDUSTRIAL HEATERS
Air Throw From Nozzles

The air throws listed below are based on
air volumes shown in this bulletin for standard floor mounted heater with standard
discharge and inlets. They are also base on all discharge outlets being in the same
direction, no obstruction between the heater and the area of throw, no interference form
the building ceiling or roof, and standard ambient conditions. As the throw from a heater
is subject to many variables, the figures listed below should be used only as a guide.
Nozzles are optional items.
| COUNTERFLO |
Average Air Throw (feet) |
COUNTERFLO |
Average Air Throw (feet) |
| Model No. |
Floor Mounted Units |
Model No. |
Floor Mounted Units |
| 40 |
80 |
225 |
225 |
| 55 |
100 |
250 |
250 |
| 60 |
120 |
275 |
200 |
| 85 |
150 |
300 |
225 |
| 100 |
160 |
325 |
250 |
| 125 |
200 |
350 |
275 |
| 150 |
200 |
400 |
300 |
| 175 |
225 |
450 |
325 |
| 200 |
200 |
|
|
Engineers Specifications
Furnish and install the following Hastings
Counterflo indirect-fired industrial heater:
| Model No. |
MBH Output |
SCFM |
Total ESP |
Blower
Motor HP |
Voltage
Phase |
Gas-Fired |
Oil-Fired
Feed System |
| Type Gas |
Gas Pressure |
Suction (2-pip) |
Pressure (1-pipe) |
Oil Pressure |
GENERAL Each unit
shall be factory assembled and wired, flame tested at the factory and shipped as a
packaged assembly. Stack, external wiring and piping shall be furnished and installed by
the contractor.
CASING The cabinet shall
be fabricated of 16 gauge Alm./CRS, heavily reinforced to assure
rigidity, and backed by an internal radiation shield. The casing shall be primed ad
finished with a coat of enamel. The heater shall have air inlet screens and are furnished
with (duct discharge collar) or optional (air discharge nozzles).
FANS AND DRIVES Each
heater shall be equipped with centrifugal fans, statically and dynamically balanced, and
mounted on a heavy-duty, cold-rolled steel shaft of a size limiting first critical speed
to at least 25% above maximum operating speed. The fans shall be driven by a fixed sheave
V-belt arrangement sized 35% greater than the required brake horsepower. the three phase,
open dripproof motor shall have an adjustable mount. Fan bearing shall be 200,000 hour
self-aligning, pillow block, ball/needle bearing with lubrication fittings.
COMBUSTION SECTION The
primary combustion chamber shall be of all welded, 400 series stainless steel
construction, with a minimum of 16 gauge material. The chamber shall be designed for a
minimum of two-pass flame travel within the chamber and the amount of heat transfer shall
be approximately 75% of the total heat output. A port of observing the main flame shall be
provided on the same end of the combustion chamber as the burner.
The third and fourth combustion product
flow passes shall be made in the secondary heat exchanger through two staggered, mild
steel, tube sections.
FLUE GAS EXHAUSTER The
combustion exhaust gas system shall included a heavy-duty exhaust fan, three phase motor,
adjustable V-belt drive and heat singer, Remote grease lines for lubrication of bearings.
BURNER The burners shall
be (On-Off) (Hi-Lo-Off) (Modulating) type for burning (natural gas) (propane) (#2 oil)
(combination gas/#2 oil) ( insert burner description shown on page 4 of this bulletin.)
CONTROLS Controls shall be
factory mounted and include a control transformer, prepare timer, fan/limit switch, draft,
air flow switch, combustion air switch (except some oil burners), burner switch, blower
starter, pilot flame safeguard and all necessary relays and switches. Space thermostat
shall be furnished for field mounting and wiring. Control Current shall be 115 volt.
TESTING and SERVICE
Heater(s) shall be piped, wired and flame tested before leaving factory. Start-up service
and instructions to owner's personnel shall be furnished by unit manufacturer's field
service engineer.
OPTIONS and ACCESSORIES
The following options and accessories shall be provided: (select from pages 4 and
5 of this bulletin).
In order to maintain our policy of
continuous product improvement, we reserve the right to change prices, specifications,
ratings or dimensions without notice or obligation.

|