SBD --100% FRESH AIR
APPLICATIONS

The basic SBD system is designed to heated 100% outside air
into a building to replace that amount of air which is exhausted. It is often desirable to
bring in an excess of make-up air over that exhausted to insure a positive pressure in the
area. This eliminates the many problems of negative pressure.
Normally the exhaust system is interlocked with the SBD
make -up air system so that the units are in operation at the same time.
During operation of the SBD, air flow is continuous with
discharge of air temperature regulated by modulating controls. The air temperature
controls can either be nonelectric modulating gas valves, modulating gas butterfly valves
or electronic gas flame modulation. Each of these control systems allow the burner to
operate at any point on its turndown range to provide a constant heater air discharge
temperature.
The SBD system, in addition to its primary function as a
make -up air heater, can also serve as a space heater. In many industrial and commercial
applications it is practical and economically sound to use a single source of space heat
and make -up air. In these instance, over -riding space air temperature controls are added
to the basic discharge air temperature control system.
SBDF -- DUCT FURNACE

The SBDF system consists of the basic SBD direct gas-fired burner
section without a blower section. The burner section is applied as a duct furnace in field
- fabricated ventilation systems.
All control and gas manifold options listed for the SBD systems are
available with the SBDF direct gas - fired duct furnaces. Such accessories as filters,
dampers and intake hoods can also be furnished with the furnaces.
To avoid stratifications of the heated make -up air, the SBDF duct
furnace should be located on the suction side of the blower to take advantage of the
mixing effect of the fans.
While the performance data of the SBDF duct furnace is the
same as that listed for the SBD and SBDR systems, a smaller size duct furnace may often be
used with a field-fabricated ventilation application.The burner section size is no longer
predicated on the physical size of the SBD blower section. Consult your local Hastings
sales representative for selection and dimensional information. |