   Hastings Industries Inc.  Gas Units  

Gas Units - Page 10

 

 

Optional Items

Electronic Ignition systems:

a. Intermittent pilot with non-100% shut-off - When room thermostat calls for heat, pilot valve opens and pilot is spark ignited. Then when pilot is proven, main gas valve opens, when room thermostat is satisfied, main gas valve and pilot valve are de-energized.

b. Intermittent pilot with 100% shut-off - Same as non-100% shut-off except the system with lockout and require manual starting if the pilot fails to ignite in a given time period. Electronic ignition with propane must be 100% shut-off.

Room thermostats -Several models of 24 volt thermostats available.

Fan time delay relay - Used to energize system blower motor or controller.

Two-stage gas valve - Provides both 100% and 50% gas input to yield two firing rates. Two stage thermostat is a required extra. (Natural gas only). Electric igniting required. Not available on DU-50.

Modusnap gas Valve - For applications requiring only make-up air. Direct-acting non-electric valve modulation gas flow to provide constant leaving air temperature, with a modulation range of 100% down to 30% of rated input. Not available for DU-50.

"Selectra" modulation systems (Not available for DU-50)

MS-1: For applications requiring only make-up air. Maxitrol solid state electronic modulating system provides constant leaving air temperature. Wall mounted "Selectrastat" permits adjustment of discharge temperature from convenient location.

MS-2: For space heating only applications. Maxitrol solid state electronic modulating system provides continuous blower operation and extremely close control of space temperature.

MS-3: For make-up air and space heating applications. Same as MS-1, but with two-position Overriding room thermostat for space heating as well as make-up air.

Notes: "Selectra" systems modulate down to 30% of rated input. MS-1 and MS-3 require a minimum of 6 foot discharge duct for field mounting temperature sensor.

High fuel pressure regulators (field installed):

a. 1/2 to 5 lb. line pressure (specify gas pressure)

b. 6 lb. to 40 lb. lie pressure ( specify gas pressure)

Power venters - Are generally required with gas duct furnaces where:

  1. Negative pressure exists inside the building
  2. Flue pipes have downward or long horizontal runs
  3. Heaters are vented directly through a side wall with no vertical stack
  4. Heat exchangers or stacks are extremely cold and will not provide adequate draft on start-up.

Power venters and companion adapters are shipped for field installation.

Dual-Fuel manifold - Natural/LP gas kit includes dual-fuel manifold, spuds and LP gas controls. Pilot remains on natural gas except on units with electronic ignition systems. Available only for field installation.

Note: Dual-fuel manifold and power venters are not A.G.A. / C.G.A. design certified.

PERFORMANCE

 

 

High CFM Type "H"

Standard Type
Air Temp. Rise - F 20 30 40 50 50 60 70 80 90 100
Pressure Drop Inches W.C. DU-50 .31 .14 .09 .06 .38 .25 .17 .15 .12 .10
SD-100 thru 160 .28 .14 .09 .06 .30 .21 .16 .13 .10 .08
SD-215 thru 800 .23 .12 .07 .05 .24 .17 .12 .09 .08 .06
Model No. And MBH Input Btuh Output Shipping Weight - Lbs. Airflow (SCFM)
DU-50 37,500 130 1,740 1,160 870 695 695 580 500 435 390 350
SD-100 78,000 190 3,615 2,410 1,810 1,445 1,445 1,205 1,030 905 800 725
SD-120 93,600 205 4,330 2,890 2,165 1,735 1,735 1,445 1,240 1,085 965 865
SD-160 124,800 245 5,780 3,850 2,890 2,310 2,310 1,925 1,650 1,445 1,285 1,155
SD-215 167,700 300 7,760 5,180 3,880 3,105 3,105 2,590 2,220 1,940 1,725 1,555
SD-255 198,900 350 9,210 6,140 4,605 3,685 3,685 3,070 2,630 2,305 2,045 1,845
SD-300 234,000 390 10,840 7,220 5,420 4,335 4,335 3,610 3,095 2,710 2,410 2,170
SD-400 304,000 535 14,080 9,380 7,040 5,630 5,630 4,690 4,025 3,520 3,130 2,815
SD-510 397,800 700 18,420 12,280 9,210 7,370 7,370 6,140 5,260 4,605 4,090 3,685
SD-600 468,000 780 21,680 14,440 10,840 8,670 8,670 7,220 6,190 5,420 4,820 4,335
SD-800 608,000 1,070 28,160 18,760 14,080 11,260 11,260 9,380 8,050 7,040 6,260 5,630

NOTES: 1. Ratings shown ae for elevations up t 2,000 ft. For over 2,000 ft. reduce ratings 4% for each 1,000 ft. above sea level.

2. All duct furnaces are A.G.A./C.G.A. design certified for installation downstream from cooling coils. Add suffix "D" to model DU-50.

3. Normal leaving air temperature should not exceed 180 F. Contact your Hastings sales representative for "process heating" applications.

4. Model SD-510, SD-600 and SD-800 consist of two duct furnaces shipped as one assembly. A.G.A./C.G.A. design certification applies to individuals furnaces only.

5. A.G.A./C.G.A. design certification only applies on installations on the positive side of air supply.

*Request for Information / Request a Catalog
 
 
 
To request more information from Hastings Industries Inc., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free bi-monthly AECnews e-Newsletter.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996-2008 AECinfo.com