| Search |
|
|
|
| |
| Site Navigation |
|
|
|
| News / Publications |
|
|
|
| Jobs | |
|
|
| Service |
|
|
|
|
|


|
| |
|
| |
Hastings Industries Inc. Gas Units Gas Units - Page 15
 Dimensions

Engineers Specifications
- Furnish and install the following (natural gas)
(propane) fired unit heaters as manufactured by Hastings Industries, Inc.
| Item No.
|
Model
No. |
Btuh Onput
|
Temp.
Rise |
Pressure
Drop |
- Heat exchangers shall have all electric welded
construction with (18 gauge tubes and 16 gauge header plates of aluminized steel)
(.004" tubes and .050" headers plates of type 409 stainless steel) (.041"
tubes and .50" header plates of type 321 stainless steel tubes and .060 type 409
header plates.)
- Burners shall be made of 18 gauge aluminized steel
with type 430 stainless ribbon inserts.
- Gas and electrical components shall consists of not
less than the following 24 volt combination gas valve containing main and pilot gas cocks,
main and pilot gas pressure regulators, redundant solenoid gas valve, and safety shut-off;
also high limit control, fan control and 115/24 volt control transformer.
- Cabinet side panels shall be of 20 gauge
cold rolled steel and drain pans of (20) (18) gauge aluminized steel. Side panels and
drain pans to be finished with enamel. Furnace shall be complete with slip-joint type duct
flanges on both air intake and discharge and (adjustment two point suspension) (fixed four
point) hangers.
- Duct furnaces shall be A.G.A
- The following options and accessories shall be
provided: (select from page 3 of the bulletin).
- All venting shall be done according to state/local
codes.
In order to maintain our policy of continuous product
improvement, we reserve the right to change prices, specifications, rating or dimensions
without notice or obligation.
 |
|