| POWER VENTERS
MOTOR
CHARACTERISTICS
| Venter
Model |
PV2 |
PV3 |
PV4 |
PV5 |
| Horsepower |
1/70 |
1/20 |
1/15 |
1/6 |
| RPM |
1550 |
3000 |
1550 |
3450 |
| Volts/Phase |
115/1 |
115/1 |
115/1 |
115/1 |
| Amps(115
Volts) |
0.61 |
1.80 |
1.82 |
4.40 |
| Motor
Type |
Shaded Pole |
Shaded Pole |
Shaded Pole |
Shaded Pole |
| Description |
Open |
Open |
Open |
Open |
| Bearing |
H-Temp Ball |
H-Temp Ball |
H-Temp Ball |
H-Temp Ball |
ADAPTER DIMENSIONS

Oil Fired Heaters
| Heater Model |
A |
B |
C |
D |
| UFO-25 P-20 & 25 (PV3) |
9 |
4 |
1 3/4 |
1 |
| UFO-50 P-35 & 50 (PV5) |
12 |
6 |
2 |
2 |
INSTALLATION
INSTRUCTIONS
INSTALLATION
- Installation of venter must be made so that motor shaft is
in a horizontal position. Discharge must be horizontal or any angle of up-flow
- Attach venter adapter to heater flue outlet using four #10
sheet - metal screws
- In orifice is required, remove the three screws which hold
the venter inlet collar in place. Insert proper orifice (see table on this page) under the
collar and replace screws. Orifice limits draft to capacity of heater
- Attach inlet collar of venter to adapter collar using four
sheet-metal screws.
VENT PIPING :
Chart on page 2 of this bulletin shows sizes and
permissible length of vent pipes. Use type "B" vent (metalbestos, metalvent or
equal) on outside of building with appropriate flue for positive pressure venting inside
building. Use suitable cap to keep out ran, snow, birds, etc.
MOTOR OILING:
Oil is not required Motors have sealed, lubricated ball
bearings.
OPERATION:
Thermostat or other control energizes venter motor. Proving
switch completes circuit to gas valve.
ORIFICE OR INLET
RING DIMENSIONS
| MODEL |
PV2 |
PV3 |
PV4 |
| MBH Input |
A |
B |
A |
B |
A |
B |
| 50 |
4 7/8 |
2 |
4 7/8 |
1 5/8 |
|
|
| 100 |
4 7/8 |
2 3/4 |
4 7/8 |
1 7/8 |
|
|
| 120 |
4 7/8 |
3 1/4 |
4 7/8 |
2 |
|
|
| 160 |
|
|
4 7/8 |
2 1/4 |
|
|
| 200-215 |
|
|
4 7/8 |
2 13/16 |
|
|
| 300 |
|
|
4 7/8 |
2 13/16 |
|
|
| 400 |
|
|
|
|
6 1/8 |
4 3/4 |

Note : Orifice limits draft to capacity of heater.
All dimensions in inches
ADAPTER DIMENSIONS
 
| MBH Input |
Venter Model |
Dimension "A" |
Description |
| 100 - 120 |
PV2 |
6 1/16" |
6 to 4 Adapter |
| 160 |
PV3 |
7 1/16" |
7 to 4 Adapter |
| 200 - 255 |
PV3 |
8 1/16" |
8 to 4 Adapter |
| 300 |
PV3 |
(10" Oval) |
10 to 4 Adapter |
| 400 |
PV4 |
See Below* |
 
Special draft hood outlet box with 5" round flue
discharge is furnished with 400 MBH gas furnaces and unit heaters when PV4 power venter
ordered.
In order to maintain our policy of continuous product
improvement, we reserve the right to change price, specifications, ratings or dimensions
without notice or obligation.

|