"R" SERIES INDOOR SYSTEMS
Engineers Specifications
Furnish and install the following Hastings (Natural)
(Propane) gas fired equipments
| Item no. |
Model no. |
Btuh Input |
SCFM |
Ext.S.P |
Motor HP |
Motor Volts and
Phase |
Equipment Casing and
Base
- Casing shall be constructed of high quality
aluminized steel to insure long rust-free life.
- Access panels shall be provided to allow easy access to
motor, filters (if ordered) and electrical controls.
- Casing shall have a rinse primer and an enamel finish.
- Base frame channels shall be constructed of 12 gauge
aluminized steel for all models through the 214 blower units, 218 units shall have a
1/4" hot rolled system base frame.
Blower Section :
- Blower wheels shall be statically and dynamically
balanced, forwardly curved double width double inlet class 1.
- Blower wheels shall be mounted on a solid ground shaft with
keyway for driven sheave.
- Bearings shall be ball bearing self-aligning, greasable.
- Blower scrolls, bearings, and adjustable motor base shall be
mounted and properly reinforced to insure rigidity and quiet operation.
- Cabinet shall be of 16 gauge aluminized steel with a primed
and enamel finish
- The driver and driven sheaves shall be of the keyed hub
type. The driven sheave shall be of a fixed pitch diameter and the driver sheave shall be
of variable pitch diameter through 10 HP and fixed pitch above 10 HP, V-belt drives shall
be sized for 135% of motor horsepower.
Furnace Section :
- Heat exchanger9s) shall have all electric welded
construction with -
- Aluminized steel tubes and header plates with stainless
steel internal baffles
or
- Type 409 stainless steel tubes and header plates with
stainless steel internal baffles.
or
Type 321 (chrome-nickel) stainless steel
tubes and wither type 321 or 409 header plates with stainless steel internal baffles.
Burners shall be made of 18 gauge aluminized
steel with type 430 stainless steel ribbon inserts.Optional 18 gauge 430 stainless steel
complete burners available.
Burner tray shall be so constructed as to slide out
from compartment for easy service and maintenance.
Gas and electrical components shall consist
of not less than the following : 24 volt combination gas valve containing main and pilot
gas cocks, main and pilot gas pressure regulators, redundant solenoid gas valves, pilot
solenoid gas valve and 100% safety shut-off, also high limit control and 115/24 volt
control transformer.
Temperature controls shall consist of :
RHF Models.
(a) Basic "on-off-auto" blower operation,fan time delay relay and on-off room
thermostat.
(b) Optional two stage gas valve and two stage room thermostat.
(c) Optional MS-2 " Selectra" space heating package added to basic
system. Solid state electronic modulation, down to 30% of rated input, provides
continuous blower operation and extremely close control of space temperature.
- RMU Models
(a) Basic system with non-electric modulating gas valve which modulated down to 30% of
rated input and maintains desired leaving air temperature. Higher turn-down rates
available on multiple unit applications. Optional remote control station available
with operating switches and indicating lights.
(b) Optional MS-1 "Selectra" make-up air package replacing basic non-electric
gas valve. Solid state electronic modulation, down to 30% of rated input, provides
constant leaving temperature. A temperature selector mounted in the control cabinet
or remote from unit permits adjustment of leaving air temperature from a convenient
location.
- RHV Models
(a) Basic system with non-electric modulating gas valve which modulates down to
30% of rate input and maintains desired leaving air temperature. Higher turn-down rates
available on multiple unit applications. A by-pass gas valve furnished to override
the modulating valve and controlled by an on-off space thermostat to maintain
pre-determined room temperature. Optional remote control station available with
operating switches and indicating lights.
(b) Optional MS-3 "Selectra" make-up air and space heating package replacing
basic non-electric gas valve and by-pass gas valve. Solid state electronic
modulation, down to 30% of rated input, provides constant leaving air temperature. A
temperature selector mounted in the control cabinet or remote from unit permits adjustment
of leaving air temperature from a convenient location. Space temperature is
controlled by an on-off room thermostat.
F. Cabinet side panels shall be of 20 gauge cold rolled
steel and drain pans of 20 gauge aluminized steel. Side panels and drain pans to be
finished with enamel.
G. "G" model units shall be equipped with a
gravity vent cap on each heater.
H. "V" model units shall be equipped with power
venter on each heater.
Motor :
A T-frame, ODP, 1800 RPM prelubricated ball bearing type
motor shall be furnished for voltage and scheduled.
Assembly :
The system shall be factory assembled and wired with the
exception of controls that are remote to the unit.
Options and Accessories :
The following items are to be furnished (select
from page 3 of this bulletin)
In order to maintain our policy of continuous product
improvement, we reserve the right to change prices, specifications, ratings or dimensions
without notice or obligation.

|