Hastings Industries Inc. Heating Systems Heating Systems - Page 11
"I" SERIES INDOOR SYSTEM
| The "I" series rooftop systems
feature the package concept in commercial and industrial gas heating units. Hastings
A.G.A. design certified type SD gas furnaces are incorporated into factory assembled,
wired and testing heating systems. Three temperature control sequences are available to
meet the requirements of most heating applications. |
IHF-SPACE HEATING
(100% RETURN AIR)

| Application and Operating Sequence The IHF unit is designed for 100% return air room heating
applications with the air temperature being controlled from the heated space. The IHF
operating sequence is not recommended for ventilating applications.
The "On" position of the "On-Off-Auto"
blower switch provides continuous blower operating. The "Auto" position allows
blower operating whenever the room thermostat calls for heat. The room thermostat cycles
the automatic gas valve to maintain the desired space air temperature. |
RMU-MAKE UP AIR
(100% RETURN AIR)

| The IMU make-up air unit is designed to
replace exhausted building air with 100% outside air to prevent the many problems of
"air starvation". This replacement air is heated when the outside air
temperature is below the desired space air conditions. The "On" position of the "On-Off" blower switch provides
continuous blower operation. The "Winter" position of the
"Summer-Off-Winter" season switch energizes the gas furnace(s). A modulating
non-electric gas valve with bulb in the leaving air stream (and discharge air controller
on 400 MBH furnaces) maintains a constant discharge air temperature. Standard discharge
temperature range is 60° to 100° F adjustable.
With the "Summer-Off-Winter" season switch in the
"Summer" position, gas furnace(s) is de-energized and blower operates to provide
summer ventilation. |
RHV-HEATING &
VENTILATING
(MIXED OR 100% OUTSIDE AIR)
| The IHV combines the control of both make-up
air and space temperature. This sequence is equally effective for up to 100% of either
outside or return air heating and ventilating application, or 100% of either outside or
return air heating and ventilating applications, or 100% outside air only. The "On" position of the "On-Off-Auto" blower
switch provides continuous blower operation. The "Auto" position allows blower
operation whenever the room thermostat calls for heat. The "Winter" position of
the "Summer-Off-Winter" season switch energizes the gas furnace(s). On call for
heat in the space, the room thermostat opens the by-pass gas valve to provide full gas
input. If room thermostat is satisfied, the modulating non-electric gas valve (and
discharge air controller on 400 MBH furnaces) maintains a constant discharge air
temperature. Standard discharge temperature range is 60° to 100° F adjustable.
With the "Summer-Off-Winter" season switch in the
"Summer" position, gas furnace(s) is de-energized and blower operates to provide
summer ventilation. |