   Hastings Industries Inc.  Heating Systems  

Heating Systems - Page 14

 

 

"I" SERIES INDOOR SYSTEMS

Blower Table - IHFAX, IMUAX & IHVAX Models with Double Bank Furnaces

IHFAX,IMUAX&IHVAX Blower Used Duct Furn. used Air Temperature Rise
20° 25° 30° 35° 40° 45°
Model NO. & MBH Input Btuh Output Ship Wt. Lbs.
CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP
510 394,800 2,110 MB-218 2) 255 18,415

1.24
2.11

10
15
14,735 1.38
1.91
7-1/2
10
12,280 1.15
1.81
5
7-1/2
10,525 .81
1.42
3
5
9,210 .99
1.62
3
5
8,185 1.14
1.77
3
5
600 468,000 2,190 MB-218 2)300 21,665 .64
1.46
10
15
17,335 .93
1.44
7-1/2
10
14,445 1.43
1.96
7-1/2
10
12,380 1.13
1.79
5
7-1/2
10,835 .77
1.37
3
5
9,630 .93
1.55
3
5
800 608,000 2,480 MB-218 2) 400 28,150 -
.55
-
20
22,520 .48
1.28
10
15
18,765 1.18
2.05
10
15
16,085 1.15
1.67
7-1/2
10
14,075 .88
1.50
5
7-1/2
12,510 1.11
1.77
5
7-1/2

Blower Table - IHFB, IMUB & IHVB Models with Double Bank Furnaces

IHFB, IMUB, IMVB Blower Used Duct Furn. used Air Temperature Rise
40° 50° 60° 70° 80° 90°
Model NO. & MBH Input Btuh Output Ship Wt. Lbs.
CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP CFM Total S.P. HP
1020 795,600 3,075 MB-218 4) 255 18,415

1.24
2.11

10
15
14,735 1.38
1.91
7-1/2
10
12,280 1.15
1.81
5
7-1/2
10,525 .81
1.42
3
5
9,210 .99
1.62
3
5
8,185 1.14
1.77
3
5
1200 936,000 3,235 MB-218 4)300 21,665 .64
1.46
10
15
17,335 .93
1.44
7-1/2
10
14,445 1.43
1.96
7-1/2
10
12,380 1.13
1.79
5
7-1/2
10,835 .77
1.37
3
5
9,630 .93
1.55
3
5
1600 1,216,000 3,815 MB-218 4) 400 28,150 -
.55
-
20
22,520 .48
1.28
10
15
18,765 1.18
2.05
10
15
16,085 1.15
1.67
7-1/2
10
14,075 .88
1.50
5
7-1/2
12,510 1.11
1.77
5
7-1/2

(*) Weights listed are for suspended units.

NOTES: Total static pressure shown in inches of water

Shaded areas require cleanable filters.

NOTES: Total static pressure shown in inches of water.

Shaded areas require cleanable filters.

Equipment Selection

IHF-SPACE HEATING

1. Select model size according to Btuh requirements.

2. Specify desired air delivery or temperature rise. For normal applications, an air delivery resulting in a 70° F temperature rise in recommended.

3. Specify motor size to deliver the selected SCFM against required TSP (total static pressure).

IMU-MAKE-UP AIR

1. Check the exhaust specifications or equipment to determine the total SCFM of fresh air required.

2. Increase the total SCFM by approximately 10% if building needs to be slightly pressurized.

3. Determine air temperature rise, usually 70° F minus winter outside design temperature.

4. Select model and motor size to deliver desired air temperature rise and SCFM against required TSP.

IHV - HEATING & VENTILATING

1. Calculate the total SCFM of outside air needed to satisfy exhaust air requirements and meet ventilation specifications.

2. Find the Btuh output needed to heat the total SCFM of outside air by multiplying SCFM X TD (room temperature minus winter outside design temperature) X 1.08.

3. Find total Btuh output by adding the space heat loss to the btuh ventilation requirement from step 2.

4. Select model and motor size to deliver total Btuh output and SCFM against required TSP. The SCFM chosen must equal or exceed the volume required for ventilation.

NOTE: Toral static pressure as found in the blower tables must overcome total system resistance. Duct furnace and accessory equipment air pressure losses are found on page 6 of this bulleting. Total system resistance is the total of these pressure drops added to the air pressure loss of all system duct work and registers.

MODEL DESIGNATION

igas14a.gif (9408 bytes)

*Request for Information / Request a Catalog
 
 
 
To request more information from Hastings Industries Inc., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com