M - MAKE-UP AIR
(100% OUTSIDE AIR)
The M-Make-up Air unit is designed to replace
exhausted building air with 100% outside air to prevent the many problems of "air
starvation." The replacement air is heated when the outside air is below the desired
space air temperature conditions.

Model MA
Single coil having modulating discharge air temperature
control of modulating face and by-pass damper, two position valve with mild weather air
temperature lockout and inlet air shut-off damper.

Model MB
Double coil having inlet air temperature control of
pre-heat coil with two position valve, modulating discharge air temperature control of
downstream coil with modulating valve and inlet air shut-off damper.
V - HEATING & VENTILATING
(MIXED OR 100% OUTSIDE AIR)
The V-Heating & Ventilating unit combines the control
of both make-up air and space air temperature. This sequence is equally effective for up
to 100% of either outside or return air heating and ventilating applications, or 100%
outside air only.

Model VA
Single coil having modulating space air temperature and
over-riding discharge air temperature control of face and by-pass damper, two position
valve with mild weather air temperature lockout and mixed air dampers with manual
potentiometer. Inlet air shut-off damper replaces mixing dampers with 100% outside air
applications.

Model VB
Double coil having inlet air temperature control of preheat
coil with two position valve, modulating space air temperature and over-riding discharge
air temperature control of downstream coil with modulating valve and mixed air dampers
with manual potentiometer. Inlet air shut-off damper replaces mixing dampers with 100%
outside air applications.
LEGEND
| SV -- "On-Off" Steam Valve w/Motor |
| MSV-- Modulating Steam Valve w/Motor |
| RT -- "On-Off" Room Thermostat |
| MRT -- Modulating Room Thermostat |
| DAC -- Discharge Air Temperature Controller |
| EAC -- Entering Air Temperature Controller (Mild Weather
Lockout, MA & VA Systems) |
| BDM -- Face and By-pass Damper Motor |
| SDM -- Inlet Air Shut-off Damper Motor |
| DMP -- Damper Motor w/Manual Potentiometer |
|