| How Does The I/D System
Works?
On a call for cooling, the control
dampers are positioned to introduce outside air fan, to the VARI-COOL indirect
evaporative cooling units, which functions as first stage of cooling. The air is sensibly
cooled (no moisture added) as it passes through the tubes (dry-side)of the indirect unit.
This cooling process is achieved by water distributed which wets the outside surface of
the heat exchange tubes.Secondary (wet-side)fan(s) move a separate air stream across the
exterior of the wetted tube surface forcing evaporation and cooling the tubes
adiabatically. Heat is transferred from the tube to the secondary air stream and rejected
to the outside.
The leaving dry-side air, from the first stage
indirect unit, passes through a highly efficient direct evaporative cooling unit which, as
stage two, further cools the air. The process is adiabatic whereby the dry-bulb
temperature is reduced while the wet-bulb temperature remains constant.
The leaving air from the direct evaporative
unit is the cooled supply air is used to perform the cooling work in the space.
The temperature of the supply air will be a
function of the ambient temperature (DB & WB) of the outdoor entering air, and the
efficiency of the indirect and direct units. At the recommended design temperatures for
many geographical areas, the leaving air temperature will be low enough to produce the
total required cooling by two stage evaporation alone. No additional (third stage)
refrigerated booster cooling will be required. The I/D two stage system will maintain
satisfactory room conditions. Note that the supply air is relatively saturated (usually
90% plus) similar to the condition of the air leaving a conventional cooling coil.
Following the psychrometric process, room sensible heat ratio and supply air quantity will
determine the heat removal as well as resultant room temperature and relative humidity.
When a lower supply air temperature is
required a booster third stage conventional cooling coil may be incorporated in the system
to produce the required added temperature drop. Optionally, this coil may be located in
the air leaving the indirect unit or leaving the direct unit.
During the non-cooling or heating cycle the
damper positions are reversed whereby the return air damper is fully open and the outside
air damper is set at a minimum position for ventilation. The system is on a return air
cycle and the indirect unit is bypassed. The indirect and direct unit pumps and indirect
unit wet-side fans are de-energized. The heating apparatus is energized if required. If
required, a bypass humidistat can be incorporated to energize the direct evaporative unit
pump during the heating cycle to increase humidity.
I/D units may be applied to provide cooling
only. In this case no recirculated air would be required as part of the system mode. A
short connecting duct section is provided to connect the indirect and direct units and no
return air connection or return and outdoor air dampers are provided. |