   Hastings Industries Inc.  Vari-Cool Evaporative  

Vari-Cool Evaporative - Page 8

 

 

Physical Data

INDIRECT UNIT
I/D Model No. Nominal S.A.CFM Model No. (1) Nomin  Effic (1) Primary Air S.P. H20 Secondary Side Nominal CFM Secondary Air S.P. H20 (2)
2S 2000 I-2S 60% .2" 1700 .17"
3S 3000 I-3S 60% .2" 2500 .17"
4S 4000 I-4S 60% .2" 3400 .17"
5S 5000 I-5S 60% .2" 4200 .17"
6S 6000 I-6S 60% .2" 5100 .17"
7S 7000 I-7S 60% .2" 5900 .17"
8S 8000 I-8S 60% .2" 6800 .17"

 

DIRECT UNIT  
Model No. Nominal Face Vel. Nomin  Effic (1) S.P H20 Filters 2" Pleated (inches) Unit S. P. H20 (3) R.A Dampers Estimated Oper. Weight (4)
D-2S 400FPM 90% .13" (2)16X25 .5" 12"X30" 1810 lbs.
D-3S 400FPM 90% .13". (4)16X20 .5" 18"X30" 2040  lbs.
D-4S 400FPM 90% .13" (4)16X25 .5" 18"X30" 2260  lbs.
D-5S 400FPM 90% .13" (2)16X25

(4)16X20

.5" 24"X30" 2520  lbs.
D-6S 400FPM 90% .13" (6)16X25 .5" 30"X30" 2780  lbs.
D-7S 400FPM 90% .13" (4)16X25

(4) 16X20

.5" 36"X30" 3030  lbs.
D-8S 400FPM 90% .13" (8)16X25 .5" 42"X30" 3280  lbs.

 

Notes :

(1) Percent of wet-bulb depression

(2) Includes factory furnished inlet louvers

(3) Total includes filter sections, does not include accessory coil section(s)

(4) approximate operating weights include indirect unit accessories, direct unit, economizer duct section and Base.

Approximate water content indirect unit=45 gallons.  Direct unit = 20 gallons.

Pumps : the indirect and direct units include factory furnished submersible pumps.  Each has a nominal capacity of 9GPM @ 11' head.

115V-60C-10-Nameplate=300 Watts

Water bleed assembly. Factory furnished from pump discharge to overflow fitting and will bleed approximately .4GPM.

I/D™ SYSTEM CONTROL

The following are suggested control sequences :

Two and three stage cooling only systems and 100% outdoor systems (no return air provisions or economizer dampers)using room, or supply air duct thermostat control.

  • #1 - 1st stage cooling energizes the direct unit secondary fan and pump
  • #2 - 2nd stage cooling energizes the direct unit pump.
  • #3 - 3rd stage cooling 9alternate) energizes the conventional cooling coil control valve.

100% outdoor air systems may have heating apparatus in the supply air downstream of the direct unit, which will require a heating side of the thermostat function.

Two and three stage systems with economizer dampers (R.A and O.A proportional damper control)

  • No call for cooling :

#1 - Return air damper 100% open

#2 - Outdoor air damper at minimum ventilation position

#3 - No pumps or secondary air fans in operation.

#4 - System heating apparatus may be energized.

  • 1st Stage cooling :

#1 Return air damper is closed

#2 outdoor air damper is opened 100%. Note override thermostat in the S.A duct may modulate dampers to mixed air if outdoor air temperature is too low.

#3 - 1st stage control channeled thorough outdoor air temperature allowing indirect unit secondary fan and pump to be energized only when outdoor air temperature is above set point.

  • 2nd stage cooling :

Energizes direct unit pump.

  • 3rd Stage cooling (optional)

Energizes the conventional cooling coil control valves.

Request for Information / Request a Catalog from Hastings Industries Inc.
 
 
 
To request more information from Hastings Industries Inc., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com