HID Lamp Performance Data
| Wattage |
ANSI
Code |
AVG.
Rated Life (Hrs) |
Startup
Time (Min) |
Restrike
Time (Min) |
Initial
Lumens |
Initial
Lumens/
Lamp Watt |
Mean
Lumen
Rating |
| HIGH PRESSURE SODIUM (CLEAR) |
| 35 |
S76 |
16,000 |
3-4 |
1 |
2250 |
64 |
2025 |
| 50 |
S68 |
24,000 |
3-4 |
1 |
4000 |
80 |
3600 |
| 70 |
S62 |
24,000 |
3-4 |
1 |
5800 |
83 |
5220 |
| 100 |
S54 |
24,000 |
3-4 |
1 |
9500 |
95 |
8550 |
| 150 |
S55 |
24,000 |
3-4 |
1 |
16,000 |
107 |
14,400 |
| 200 |
S66 |
24,000 |
3-4 |
1 |
22,000 |
110 |
19,800 |
| 250 |
S50 |
24,000 |
3-4 |
1 |
27,500 |
110 |
24,750 |
| 310 |
S67 |
24,000 |
3-4 |
1 |
37,000 |
119 |
33,300 |
| 400 |
S51 |
24,000 |
3-4 |
1 |
50,000 |
125 |
45,000 |
| 600 |
S106 |
30,000 |
3-4 |
|
92,000 |
157 |
88,360 |
| 1000 |
S52 |
24,000 |
3-4 |
1 |
140,000 |
140 |
126,000 |
Note: Check specific lamp manufacturer's literature
for correct data and any restrictions in use. This information intended as general in
nature and to be used as a guide only. Mean lumen based on use of CWA type ballast.
| Wattage |
ANSI
Code |
AVG.
Rated Life (Hrs) |
Startup
Time (Min) |
Restrike
Time (Min) |
Initial
Lumens |
Initial
Lumens/
Lamp Watt |
Mean
Lumen
Rating |
| HIGH
PRESSURE SODIUM (DIFFUSE) |
| 35 |
S76 |
16,000 |
3-4 |
1 |
2150 |
61 |
1935 |
| 50 |
S68 |
24,000 |
3-4 |
1 |
3800 |
76 |
3420 |
| 70 |
S62 |
24,000 |
3-4 |
1 |
5400 |
77 |
4860 |
| 100 |
S54 |
24,000 |
3-4 |
1 |
8800 |
88 |
7920 |
| 150 |
S55 |
24,000 |
3-4 |
1 |
15,000 |
100 |
13,500 |
Note: Check specific lamp manufacturer's literature
for correct data and any restrictions in use. This information intended as general in
nature and to be used as a guide only. Mean lumen based on use of CWA type ballast.
| Wattage |
ANSI
Code |
AVG.
Rated Life (Hrs) |
Startup
Time (Min) |
Restrike
Time (Min) |
Initial
Lumens |
Initial
Lumens/
Lamp Watt |
Mean
Lumen
Rating |
| METAL
HALIDE (CLEAR) |
| 70 |
|
6000 |
|
10-15 |
5000 |
71 |
4500 |
| 100 |
|
7500 |
13 |
5-10 |
7800 |
78 |
6240 |
| 150 |
|
15,000 |
1 |
10-15 |
11,250 |
75 |
10,125 |
| 175 |
|
10,000 |
2 |
10 |
14,000 |
80 |
10,800 |
| 250 |
|
10,000 |
2 |
10 |
20,500 |
82 |
17,00 |
| 400 |
|
20,000 |
2 |
10 |
36,000 |
90 |
28,800 |
| 400 |
|
20,000 |
2 |
10 |
40,000 |
100 |
32,000 |
| 400 |
|
10,000 |
2 |
10 |
34,000 |
85 |
30,600 |
| 750 |
|
5000 |
3 |
10-15 |
83,000 |
111 |
74,700 |
| 1000 |
|
12,000 |
4 |
10-15 |
110,000 |
110 |
99,000 |
| 1500 |
|
3000 |
5 |
10-15 |
155,000 |
103 |
139,500 |
Note: Check specific lamp manufacturer's literature
for correct data and any restrictions in use. This information intended as general in
nature and to be used as a guide only. Mean lumen based on use of CWA type ballast.
| Wattage |
ANSI
Code |
AVG.
Rated Life (Hrs) |
Startup
Time (Min) |
Restrike
Time (Min) |
Initial
Lumens |
Initial
Lumens/
Lamp Watt |
Mean
Lumen
Rating |
| METAL
HALIDE (PHOSPHOR COATED) |
| 175 |
M57 |
10,000 |
2 |
10 |
14,000 |
80 |
12,600 |
| 250 |
M58 |
10,000 |
2 |
10 |
7800 |
85 |
6240 |
| 400 |
M59PK |
20,000 |
2 |
10 |
36,000 |
90 |
27,700 |
| 400 |
M59PK |
20,000 |
2 |
10 |
40,000 |
100 |
31,000 |
| 1000 |
M47 |
12,000 |
4 |
10-15 |
105,000 |
105 |
94,500 |
Note: Check specific lamp manufacturer's literature
for correct data and any restrictions in use. This information intended as general in
nature and to be used as a guide only. Mean lumen based on use of CWA type ballast.
| Wattage |
ANSI
Code |
AVG.
Rated Life (Hrs) |
Startup
Time (Min) |
Restrike
Time (Min) |
Initial
Lumens |
Initial
Lumens/
Lamp Watt |
Mean
Lumen
Rating |
| MERCURY
VAPOR (DELUXE WHITE) |
| 100 |
H38 |
10,000 |
5-7 |
3-6 |
4500 |
45 |
3650 |
| 175 |
H39 |
10,000 |
5-7 |
3-6 |
8600 |
49 |
7200 |
| 250 |
H37 |
20,000 |
5-7 |
3-6 |
13,000 |
52 |
11,000 |
| 400 |
H33 |
20,000 |
5-7 |
3-6 |
23,000 |
58 |
20,100 |
| 1000 |
H36 |
12,000 |
5-7 |
3-6 |
63,000 |
63 |
48,500 |
Note: Check specific lamp manufacturer's literature
for correct data and any restrictions in use. This information intended as general in
nature and to be used as a guide only. Mean lumen based on use of CWA type ballast.
| Wattage |
ANSI
Code |
AVG.
Rated Life (Hrs) |
Startup
Time (Min) |
Restrike
Time (Min) |
Initial
Lumens |
Initial
Lumens/
Lamp Watt |
Mean
Lumen
Rating |
| TUNGSTEN
HALOGEN |
| 150 |
ETH |
2000 |
0 |
0 |
2700 |
18 |
2500 |
| 250 |
ESM |
2000 |
0 |
0 |
4850 |
19 |
4700 |
| 500 |
|
2000 |
0 |
0 |
11,100 |
22 |
10,750 |
| 1000 |
|
2000 |
0 |
0 |
21,500 |
22 |
20,850 |
| 1500 |
DKX |
1000 |
0 |
0 |
41,000 |
27 |
36,900 |
| 1500 |
|
2000 |
0 |
0 |
38,800 |
24 |
34,700 |
Note: Check specific lamp manufacturer's literature
for correct data and any restrictions in use. This information intended as general in