Mercury Vapor And Metal Halide Checklist
Identify problem and test for cause in
numerical sequence.
|
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
K |
| Problem |
End of
Lamp
LIfe |
Incorrect
Lamp |
Open
Cap. |
Def.
Starter
(if app.) |
Incorrect
Supply
Voltage |
Photo-
Cont. |
New
Lamp
Repl. |
Line
Voltage
Dips |
Shorted
Cap. |
Burned
Ballast
Windings |
Incorrect
Ballast |
| FAILURE TO OPERATE |
1 |
5 |
3 |
4 |
2 |
|
|
|
|
|
6 |
| LAMP CYCLING |
|
1 |
|
|
2 |
3 |
|
|
|
|
|
| COLOR SHIFT |
|
|
|
|
|
|
1 |
2 |
|
|
|
| LOW LIGHT OUTPUT |
|
2 |
|
|
1 |
|
|
|
|
|
|
| TRIPPED BREAKER OR BLOWN FUSE |
|
|
|
|
|
|
|
|
1 |
2 |
3 |
A. End of Lamp Life
At lamps end of life, the voltage
requirements of the lamp exceeds the output ability of the ballast. The usual failure mode
for mercury is low light output followed by failure to operate, and for Metal Halide low
light levels, color shifts, and lamp operating instability (cycling). Replace end of life
lamp as dictated by lamp testing procedure.
B. Incorrect Lamp
Lamp wattage, voltage, burning position,
and type must be checked against the fixture label to be sure the proper lamp has been
installed.
C. Open Capacitor
This is the usual result of electrical
failure or mechanical damage. Very often the capacitor can will be bulged or distorted.
Where the capacitor is used in series with the lamp, the lamp will not operate. See tests
for capacitors or replace with a known good capacitor.
D. Defective Starter
The function of the starter is to provide a
high voltage pulse to ignite the lamp. To test, replace with a known good lamp. (Also see Ignitor/Starter
testing procedure)
E. Incorrect Supply Voltage
When investigating problems of low light output or cycling,
voltage readings first must be taken at the fixture to properly identify power
distribution problems. In the case of multiple supply type ballasts, verification that the
supply voltage is connected to the appropriate input lead is advised.
F. Photocontrol
Problems may result from electrical failure, incorrect
wiring, or from an incorrect amount of light reaching the cell. First cover the eye of the
cell with electrical tape to verify fixture and cell operation. If the fixture fails to
operate, the cell must be bypassed electrically to identify the problem source. Problems
of incorrect amount of light usually can be resolved by repositioning the fixture or by
using cell caps to regulate the light level.
G. New Lamp Replacement
New lamps, when installed, go through a period of burn-in
or seasoning which may extend for a period of 100 hours or more. The usual result is
noticeable color variation between lamps. While metal-halide lamps are noted for this, the
system will stabilize as the burn-in period ends. It is important to understand that some
variation in color may be noted between lamp manufacturers, or between old and new lamps.
H. Line Voltage Dips
When investigating voltage dips, it is important to
identify distribution system loading. The usual cause is the starting of large motors or
the use of electric welding equipment. Line voltage recorders will usually identify the
problem. It is important to understand that mild dips will cause a color shift, while
severe dips will cause the lamp to go out. Dip tolerance depends on lamp type, lamp age
and ballast type.
I. Shorted Capacitor
This is the direct result of electrical failure or
mechanical damage. The most common result of a shorted capacitor is ballast failure. In
all cases of shorted capacitors, both capacitor and transformer should be replaced. See
tests for capacitors or replace with a known good capacitor.
J.
Burned Ballast Coils
1. Burned Primary Coils
This is the usual result of fixture connection to
incorrect supply voltage. Repeated failure often in conjunction with capacitor failure may
indicate short duration high voltage spikes on the distribution system. The use of a scope
along with power company assistance is generally required to identify these spikes.
Equally important as a cause of failure is a shorted capacitor (See "I" above -
Shorted Capacitor). See tests for ballasts on preceding page and replace if necessary.
2. Burned Secondary Coils
This may be caused by a short circuit in the lamp
circuit wiring or by mechanical failure in the lamp. Carefully inspect all lamp circuit
wiring. See tests for ballasts on preceding page and replace it if necessary. In
all cases, replace the lamp.
K. Incorrect Ballast
The requires checking only a new fixture or if a recurring
problem is encountered. Carefully compare details on the transformer to the fixture label
and lamp used in the circuit. Change components as required.
High Pressure Sodium Service Checklist
Identify problem and test for cause in
numerical sequence.
|
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
| Problem |
End of
Lamp
LIfe |
Incorrect
Supply
Voltage |
Incorrect
Lamp
|
Shorted
Capacitor |
Photo-
Cont. |
Line
Voltage
Dips
|
Defective Lamp |
Defective Starter |
Open Capacitor |
Burned
Ballast
Windings |
| LAMP CYCLING SINGLE FIXTURE |
1 |
3 |
2 |
|
4 |
|
|
|
|
|
| LAMP CYCLING GROUP OF FIXTURES |
|
|
|
|
2 |
1 |
|
|
|
|
| FAILURE TO START |
|
2 |
3 |
|
|
|
4 |
1 |
5 |
6 |
| LOW LIGHT OUTPUT |
|
2 |
3 |
1 |
|
|
4 |
|
|
|
A. End
of Lamp Life
At a lamps end of life, the operating voltage
requirements of the lamp exceed the output ability of the ballast. This results in the
lamp cycling off and on. It is important to understand that in the early stages of
failure, the lamp may operate for several hours before cycling off. As the lamp nears
total failure, the on time will decrease until the lamp fails to ignite at all. Cycling
lamps should immediately be replaced to avoid starting aid damage. See lamp tests or
replace with known good lamp.
B. Incorrect Supply Voltage
When investigating problems of low light output, cycling,
or failure to start, voltage readings must be taken at the fixture to properly identify
distribution system problems. For multiple supply type ballasts, proper lead connection
must be verified.
C. Incorrect Lamp
Lamp wattage, voltage, burning position, and type must be
checked against fixture label to be sure the proper lamp has been installed in the
fixture.
D.
Shorted Capacitor
This is the direct result of electrical failure or
mechanical damage. The most common result is low light output; cycling may also occur.
E. Photocontrol
Problems may result from electrical failure or from an
incorrect amount of light reaching the cell. First cover the eye of the cell with
electrical tape, to verify fixture and cell operation. If the fixture fails to operate,
the cell must be bypassed electrically to identify the problem source. Problems of
incorrect amount of light usually can be resolved by repositioning the fixture or by using
cell caps to regulate the light level. Occasionally, the cell will see light from the
fixture reflected off a nearby object and turn itself off. Repositioning the cell or
reflecting object may be required.
F. Line Voltage Dip
When investigation voltage dips, it is important to
identify distribution system loading. The usual cause is the starting of large motors or
the use of electric welding equipment. Line voltage recorders will usually identify the
problem. It is important to understand that lamps nearing end of life will be more
susceptible to voltage dips than new lamps, and lamp operating on reactor ballasts are
more sensitive to voltage dips than those on regulating ballasts.
G. Defective Lamp
This is normally the result of some mechanical failure in
the lamp. This can often be determined by brown or silver coating on the lamp outer
jacket, or by deposits at the base of the lamp. See lamp testing procedures or replace
with a known good lamp.
H.
Defective Starter
The function of the starter is to provide a high voltage
pulse to ignite the lamp. Failure to operate generally results from electrical failure in
the starter. See tests for starters or replace with a known good starter.
I. Open Capacitor
This generally results from electrical failure or
mechanical damage. Very often the capacitor can will be
bulged or distorted. When the capacitor is used in the secondary (lamp) circuit, the
fixture will not operate. See tests for capacitors or replace with a known good capacitor.
J. Burned Ballast Windings
This is often the result of fixture being connected to
incorrect supply voltage. Repeated primary winding failures often in conjunction with
capacitor failures may indicate short duration high voltage spikes on the distribution
system. The use of a scope in conjunction with power company assistance is generally
required to identify these spikes. See tests for ballasts and replace if necessary.
Light Output Service Checklist
( Investigate In numerical sequence )
| A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
| Voltage |
Socket
Position |
Lamps |
Reflector |
Reflectance |
Obstruct. |
Light
Meters |
Dirt |
Line Current
Harmonics |
Spacing & Mount. Height |
| 2 |
6 |
3 |
7 |
4 |
8 |
1 |
9 |
10 |
5 |
A. Voltage
Measurements must be checked a) at the fixture b) at the
end of the distribution line. Confirm correct ballast voltage tap connection to supply
voltage.
B. Socket Position
If adjustable, check fixture instructions and confirm
correct position has been selected.
C. Lamps
Check for (a) correct wattage (b) correct burn position (c)
high output vs. standard (d) does color appear to be correct. (after burn in)
D. Reflector
Has the correct reflector been installed? If adjustable,
has the proper mounting position been selected? Verify whether reflector should be open or
enclosed.
E. Reflectance
Recheck original calculations and confirm correct
reflectance was used for walls, ceiling and floor. Ratio of incident light to reflected
light is a measure of reflectance.
F.
Obstructions
Note obstructions in the air and at the floor level that
would restrict normal light distribution. In the air this would include piping, heating,
crane rails, steel structure, fog, or other airborne contaminants. At floor level work in
progress, racks, cabinets, machinery and partitions. In addition consideration must be
given to guards, visors and other fixtures.
G. Light Meters
Use a second meter to confirm out of spec readings. Be sure
the meter is not shadowed, not receiving reflected light, and held in the correct plane,
and calibrated.
H. Dirt
Be sure the reflector lamp and lens (if involved) are clean
and free of construction dust.
I. Current/Wave Form
Check for hot panels, conduit and feeder wiring indicating
harmonics and overloading.
J. Spacing & Mounting Height
Confirm the installation is per the original design for
fixture spacing mounting height and aiming (if involved). Check for pole spacing, pole
heights, and setbacks. |