   Industrial Louvers Inc.  The ILI Louver Guide  

Extruded Aluminum Louvers - Page 5

 

 

 Extruded Aluminum Louvers

 

MODEL

FRAME & BLADE THICKNESS

STYLE

FREE AREA
4' X 4' LOUVER

WATER PENETRATION
@.01 OZ.

STATIC PRESSURE
DROP W.G."

Drainable Blades

258

.063"

Thin Line
Drainable Blade 

9.04 sq.ft.
(56%) 

622 FPM

.15" @ 970 FPM

457*

.081"

Drainable Blade

8.05 sq.ft.
(50%) 

1,120 FPM

.15" @ 1000 FPM

652-DD*

.081"

Dual
Drainable Blade 

8.31 sq.ft.
(52%) 

856 FPM

.15" @ 1080 FPM

653-XP*

.081"

High Performance
Drainable Blade 

8.77 sq.ft.
(55%) 

above
1,250 FPM 

.15" @ 1000 FPM

658*

.081"

Drainable Blade

8.26 sq.ft.
(52%) 

1,134 FPM

.15" @ 955 FPM

Extra Performance

450-XP*

.081"

Extra Performance
Weather-Resistant 

8.15 sq.ft.
(51%) 

818 FPM

.15" @ 880 FPM

455-XP*

.081"

Extra-Performance
Storm-Resistant 

8.12 sq.ft
(51%) 

678 FPM

.15" @ 910 FPM

456-XP*

.081"

Extra Performance
Storm / Weather-Resistant 

9.12 sq.ft.
(57%) 

732 FPM

.15" @ 940 FPM

650-XP*

.081"

Extra Performance
Weather-Resistant 

8.15 sq.ft.
(51%) 

1,076 FPM

.15" @ 890 FPM

655-XP*

.081"

Extra Performance
Storm-Resistant 

8.07 sq.ft.
(50%) 

1,082 FPM

.15" @ 885 FPM

 * Also available in heavy-duty .125" frame and blade.

To receive the AMCA seal, louvers must meet certain test criteria. The tests are based on a 48" x 48" size. The louvers are tested without birdscreens and must be mill finished. The water test is conducted at a rainfall of 4" per hour during a 15-minute period. The AMCA Certified Ratings Seal applies to air capacities in the intake mode only. See page 12 for complete free area information.

Industrial Louvers, Inc., certifies that the Models 258, 457, 652-DD, 653-XP, 658, 450-XP, 455-XP, 456-XP, 650-XP and 655-XP shown hereon are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings and water penetration ratings.

Request for Information / Request a Catalog from Industrial Louvers Inc.
 
 
 
To request more information from Industrial Louvers Inc., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com