Industrial Louvers Inc.
The ILI Louver Guide
Extruded Aluminum Louvers - Page 5
The ILI Louver Guide
Extruded Aluminum Louvers |
MODEL |
FRAME & BLADE THICKNESS |
STYLE |
FREE AREA |
WATER PENETRATION |
STATIC PRESSURE |
Drainable Blades |
|||||
258 |
.063" |
Thin Line |
9.04 sq.ft. |
622 FPM |
.15" @ 970 FPM |
457* |
.081" |
Drainable Blade |
8.05 sq.ft. |
1,120 FPM |
.15" @ 1000 FPM |
652-DD* |
.081" |
Dual |
8.31 sq.ft. |
856 FPM |
.15" @ 1080 FPM |
653-XP* |
.081" |
High Performance |
8.77 sq.ft. |
above |
.15" @ 1000 FPM |
658* |
.081" |
Drainable Blade |
8.26 sq.ft. |
1,134 FPM |
.15" @ 955 FPM |
Extra Performance |
|||||
450-XP* |
.081" |
Extra Performance |
8.15 sq.ft. |
818 FPM |
.15" @ 880 FPM |
455-XP* |
.081" |
Extra-Performance |
8.12 sq.ft |
678 FPM |
.15" @ 910 FPM |
456-XP* |
.081" |
Extra Performance |
9.12 sq.ft. |
732 FPM |
.15" @ 940 FPM |
650-XP* |
.081" |
Extra Performance |
8.15 sq.ft. |
1,076 FPM |
.15" @ 890 FPM |
655-XP* |
.081" |
Extra Performance |
8.07 sq.ft. |
1,082 FPM |
.15" @ 885 FPM |
* Also available in heavy-duty .125" frame and blade.
To receive the AMCA seal, louvers must meet certain test criteria. The tests are based on a 48" x 48" size.
The louvers are tested without birdscreens and must be mill finished. The water test is conducted at a rainfall
of 4" per hour during a 15-minute period. The AMCA Certified Ratings Seal applies to air capacities in the
intake mode only. See page 12 for complete free area information.
Industrial Louvers, Inc., certifies that the Models 258, 457, 652-DD, 653-XP, 658, 450-XP, 455-XP,
456-XP, 650-XP and 655-XP shown hereon are licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511
and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified
Ratings Seal applies to air performance ratings and water penetration ratings.