Industrial Louvers Inc.
The ILI Louver Guide
Specialized Louvers - Page 9
The ILI Louver Guide
Specialized Louvers |
To receive the AMCA seal, louvers must meet certain test criteria. The tests are based on a 48" x 48" size.
The louvers are tested without birdscreens and must be mill finished. The water test is conducted at a rainfall
of 4" per hour during a 15- minute period. The AMCA Certified Ratings Seal applies to air capacities in the
intake mode only. See page 12 for complete free area information.
MODEL |
STYLE |
BLADE |
FRAME |
LOUVER |
FREE AREA |
Thin Line |
|||||
1516 |
Grilles |
.063" |
.063" |
1-3/8" |
9.67 sq.ft. |
150 |
Grilles |
.125" |
.063" |
2" |
11.14 sq.ft. |
236 |
Sightproof |
.081" |
.063" |
2" |
4.60 sq.ft. |
250 |
Weather-Resistant |
.063" |
.063" |
2" |
6.28 sq.ft. |
252-LW |
Storm Resistant |
.063" |
.063" |
2" |
6.3 sq.ft. |
254 |
Storm Resistant |
.063" |
.063" |
2" |
7.03 sq. ft. |
258 |
Drainable |
.063" |
.063" |
2" |
9.04 sq.ft. |
Water penetration @ .01 oz is 622 FPM. Static pressure drop W.G." is .15" @ 970 FPM. |
|||||
Sightproof |
|||||
435 |
Sightproof |
.081" |
.081" |
4" |
4.79 sq.ft. |
436 |
Sightproof |
.081" |
.081" |
4" |
4.89 sq.ft. |
537-XP |
Extra Performance Sightproof |
.081" |
.081" |
5" |
9.2 sq.ft. |
Water penetration @ .01 oz is 974 FPM. Static pressure drop W.G." is .15" @ 680 FPM. |
|||||
836 |
Sightproof |
.081" |
.081" |
8" |
8.05 sq.ft. |
837-XP |
Extra Performance Sightproof |
.081" |
.081" |
8" |
9.2 sq.ft. |
Industrial Louvers, Inc., certifies that the Models 537-SXP and 258 shown hereon are licensed to bear
the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with
AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to air performance ratings and water penetration ratings.