VALVE CABINETS |
VC1818 and VC2626
SERIES
TO SPECIFY THE VC1818
and VC2626 SERIES :
Insert, after
"VC", the appropriate prefix for the trim and door material (please refer to page 16). If STEEL -- Use S. If ALUMINUM -- Use AL. If STAINLESS
STEEL -- Use SS. If BRASS -- Use B. If BRONZE -- Use BZ.
Select the required model
number from the table below.
Select the door style from
the illustrations on page 16.
DIMENSIONS
| |
Model Number |
Trim
Style and Projection |
Inside Box Dimensions
H x W x D |
Outside
Door Dimens-
ions H x W*** |
Rough
Opening
H x W x D |
Knockout Locations** E
G |
Interior
Capacity |
| |
VC1818-R |
Rec.-5/16 |
18x18x18 |
21-1/2x21-
1/2 |
19x19x8-
1/4 |
9" |
4" |
One
2-1/2"
Fire Dept. valve
with cap and
chain |
| FS |
VC1818-R |
Rec.-5/16 |
18x18x18 |
21-1/2x21-
1/2 |
20-1/8x20-
1/8x9-1/8 |
---- |
|
VC1818-RK |
Semi-Rec.1-1/4 |
18x18x18 |
21-1/2x21-
1/2 |
19x19x7-1/4 |
9" |
4" |
| FS |
VC1818-RK |
Semi-Rec.1-1/4 |
18x18x18 |
21-1/2x21-
1/2 |
20-1/8x20-
1/8x9-1/8 |
---- |
|
VC1818-RL |
Semi-Rec.2-1/2 |
18x18x18 |
21-1/2x21-
1/2 |
19x19x6 |
9" |
4" |
| FS |
VC1818-RL |
Semi-Rec.2-1/2 |
18x18x18 |
21-1/2x21-
1/2 |
20-1/8x20-1/8x7 |
---- |
|
VC1818-RT |
Trimless |
18x18x18 |
---- |
--x--x8-1/2+ |
9" |
4" |
|
VC1818-SM |
Surface
Mtd. |
21-1/2x21-1/2x8-1/2 |
21-1/2x21-
1/2 |
---- |
---- |
|
VC2626-R |
Rec.-5/16 |
26x26x8 |
29-1/2x29-
1/2 |
27x27x8-1/4 |
13" |
4" |
One
2-1/2" Fire Dept. valve with cap and chain |
|
VC2626-RK |
Semi-Rec.1-1/4 |
26x26x8 |
29-1/2x29-
1/2 |
27x27x8-1/4 |
13" |
4" |
|
VC2626-RL |
Semi.-Rec.2-1/2 |
26x26x8 |
29-1/2x29-
1/2 |
27x27x6 |
13" |
4" |
|
VC2626-RT |
Trimless |
26x26x8 |
---- |
--x--x8-1/2+ |
13" |
4" |
|
VC2626-SM |
Surface
Mtd. |
29-1/2x29-1/2x8-1/2 |
29-1/2x29-
1/2 |
---- |
---- |
The VC2626 Series is designed specifically to meet fire codes which
require the continuous revolution of a 12" long spanner wrench.
| NOTE:"FS"
models denote Larsen's "Flame-Shield" fire-rated
cabinets. When specifying Larsen's "Flame-Shield" fire-rated cabinets option for
the VC1818 Series, refer to the dimension chart above and select from the models with an
"FS" prefix. No knock-outs are provided with fire-rated valve cabinets. Pipe
holes must be drilled by installer and complete instructions are supplied with each
fire-rated valve cabinet. |
VC4016 and VC3616
SERIES

| NOTE:"FS"
models denote Larsen's "Flame-Shield"
fire-rated cabinets. When specifying Larsen's "Flame-Shield"
fire-rated cabinets option for the VC1818 Series, refer to the dimension
chart above and select from the models with an "FS" prefix.
No knockouts are provided with fire-rated valve cabinets. Pipe holes
must be drilled by installer and complete instructions are supplied
with each fire-rated valve cabinet. |
Larsen's exclusive VC4016 and
VC3616 Series provide an attractive, innovative, and economical method of housing a fire
extinguisher and a fire department valve. Both the VC4016 and VC3616 support the
extinguisher with a heavy gauge shelf. The shelf in both units is located 12" up from
the bottom of the cabinet, leaving approximately 28" for the extinguisher height in
the VC4016 and 24" in the VC3616.
A more economical option is
available for both units. As pictured at the left, the shelf can be deleted with the
valve installed at the top of the cabinet. With this option, the "F" dimension
for the knockout location (see chart above) is measured from the top of the cabinet. To
specify this unit, see below.
TO SPECIFY THE VC4016
and VC3616 SERIES:
- Insert, after "VC", the
appropriate prefix for the trim and door material (see page 16).
If STEEL - Use S. If ALUMINUM - Use AL. If STAINLESS STEEL - Use SS. If BRASS - Use B. If
BRONZE - Use BZ.
- Select the required model number from the
table below.
- Select the door style from the illustrations
on page 16. If the Gemini Door is
required and use the prefix "G" before the model number. If the Occult Door is required and use the prefix "O" before the
model number.
- If the shelf is to be deleted with the valve
installed at the top, insert the prefix "T" before "VC" and note the
appropriate knockout location.
DIMENSIONS
| |
Model Number |
Trim Style and Projection |
Inside Box Dimensions
H x W x D |
Outside Door Dimensions H x W* |
Rough Opening
H x W x D |
Knockout Locations** F
G |
Interior Capacity |
| |
VC4016-R |
Rec.-5/16 |
40x16x8 |
43-1/2x19-1/2 |
41x17x8-1/4 |
6" |
4" |
One
2-1/2" Fire Dept valve with cap and chain and a Fire Extinguisher |
|
VC4016-RK |
Semi-Rec. 1-1/4 |
40x16x8 |
43-1/2x19-1/2 |
41x17x7-1/4 |
6" |
4" |
|
VC4016-RL |
Semi-Rec. 2-1/2 |
40x16x8 |
43-1/2x19-1/2 |
41x17x6 |
6" |
4" |
|
VC4016-RT |
Trimless |
40x16x8 |
--- |
--x--x8-1/2+ |
6" |
4" |
|
VC4016-SM |
Surface Mtd. |
43-1/2x19-1/2x8-1/2 |
43-1/2x19-1/2 |
---- |
---- |
|
VC4016-R |
Rec-5/16 |
36x16x8 |
39-1/2x19-1/2 |
37x17x8-1/4 |
6" |
4" |
One
2-1/2" Fire Dept valve with cap and chain and one of the following Fire Ext. MP2-1/2,
MP5, DC2-1/2, DC5, H2-1/2, H5, MP6, MP10, DC6, DC10, H9, CD5, H13 |
| FS |
VC3616-R |
Rec.5/16 |
36x16x8 |
39-1/2x19-1/2 |
38-1/8x18-1/8x9-1/8 |
----- |
|
VC4016-RK |
Semi-Rec.
1-1/4 |
36x16x8 |
39-1/2x19-1/2 |
37x17x7-1/4 |
6" |
4" |
| FS |
VC3616-RK |
Semi-Rec.1-1/4 |
36x16x8 |
39-1/2x19-1/2 |
38-1/8x18-1/8x8-1/8 |
---- |
|
VC4016-RL |
Semi-Rec.
2-1/2 |
36x16x8 |
39-1/2x19-1/2 |
37x17x6 |
6" |
4" |
| FS |
VC3616-RL |
Semi-Rec.2-1/2 |
36x16x8 |
39-1/2x19-1/2 |
38-1/8x18-1/8x7 |
----- |
|
VC4016-RT |
Trimless |
36x16x8 |
---- |
--x--x8-1/2+ |
6" |
4" |
|
VC4016-SM |
Surface
Mtd. |
39-1/2x19-1/2x8-1/2 |
39-1/2x19-1/2 |
---- |
----- |
** No knockouts are provided for surface-mounted cabinets
unless specified.
+ Trimless cabinets must be installed before the drywall. Plaster
stop must be behind the drywall. Trimless are not recommended for block wall installation.
*** Deduct 3/4" from HxW Dimensions for Cabinets with Aluminum
Door & Trim. This does not apply to "FS" fire-rated option. |