Larsen Products - Page 34

 

 

DETENTION FIRE SAFETY CABINETS

GENERAL DESCRIPTION: Larsen's detention fire extinguisher, fire hose, and fire department valve cabinets provide an effective method of securing fire equipment for modern day detention facilities. Available as fully recessed or surface-mounted cabinets and designed for maximum security - these heavy gauge steel units feature one piece solid steel doors with matching trim and heavy gauge continuous piano hinges. These features combined with Larsen's mechanical security locks, fire extinguishers, valves, and hose rack units offer the hingest level of protection for any detention facility.

BOX SPECIFICATION: All recessed and surface-mounted cabinets feature 12 gauge cold-rolled steel boxes finished with a rust inhibitive baked primer. Surface-mounted cabinets with stainless steel trim and door have a box constructed entirely of 304 stainless steel with brushed finish.

TRIM AND DOOR SPECIFICATION: Steel trims and doors are manufactured entirely from 12 gauge cold-rolled steel. The doors are one piece construction. Standard finish is a rust inhibitive baked primer. Stainless steel trims and doors feature the same construction using 12 gauge 304 stainless steel with a brushed finish.


DETENTION FIRE EXTINGUISHER CABINETS & FIRE DEPARTMENT VALVE CABINETS

DEC 2409, DEC 2712 and DVC 1818 SERIES

TO SPECIFY THE DEC or DVC SERIES:

  1. Insert, after "DEC" or "DVC", the appropriate prefix for the trim and door material. If 12 gauge STEEL - use "S". If 12 gauge STAINLESS STEEL - use "SS".

  2. Select the required model number from the dimensional chart based on wall depth and interior capacity. Recessed or surface-mounted.

  3. Select "LOCK OPTION"; page 4.

  4. Select interior components: fire extinguishers and fire department valves. (See Sweet's section 10520 FIRE PROTECTION SPECIALTIES.)

  5. For detention valve cabinets, specify size and location of pipe opening. (One per cabinet standard.)

  6. OTHER OPTIONS: horizontal duo door panels (see page 3), special lettering, special finishes (white or red baked enamel), lighter gauges for medium or minimum security needs.

When specifying Larsen's Flame-Shield fire-rated cabinet option for the DEC or DVC Series, refer to the dimension chart below and select from the models with an "FS" prefix. For additional details on the Flame-Shield option, see page 3.

DIMENSIONS*

 

Model Number

Trim Style

Inside Box Dimensions
H x W x D

Outside
Trim Dimen-
sions H x W

Rough
Opening
H x W x D

Pipe Location Interior Capacity Recom-
men- ded Exting-
uisher Capa- city
  DEC2409-R Rec. Flat 23-3/4x9-3/8x6-1/8 27-1/8x13 25x10-1/2x6-3/4 N/A N/A MP2-1/2, MP5, H2-1/2, H5, MP6, MP10, H9, H13
FS DEC2409-R Rec.Flat 23-3/4x9-3/8x6-1/8 27-1/8x13 25-7/8x11- 3/4x7-1/2
  DEC2409-SM Surface Mtd. 26-5/8x12-1/2x6-5/8 27-1/8x13 ----------
  DEC2712-R Rec. Flat 26-3/4x11-3/4x8-1/4 30-1/8x15-5/16 28x13x8-7/8 N/A N/A All of the above plus PW2-1/2, MP20, H17
FS DEC2712-R Rec. Flat 26-3/4x11-3/4x8-1/4 30-1/8x15-5/16 28-7/8x13-7/8x9
  DEC2712-SM Surface Mtd. 29-11/16x14-3/4x8-5/8 30-1/8x15-5/16 -------------
  DVC1818-R Rec. Flat 17-3/4x17-3/4x8-1/4 21-3/8x21-3/8 19x19x8-7/8 Specify Size & Location One 2-1/2" Fire Dept. Valve w / Cap & Chain N/A
FS DVC1818-R Rec. Flat 17-3/4x17-3/4x8-1/4 21-3/8x21-3/8 19-7/8x19-7/8x9
  VC1818-SM Surface Mtd. 20-11/16x20-15/16x8-5/8 21-3/8x21-3/8 ------

* Other sizes available; contact factory.


DETENTION FIRE HOSE CABINETS DHC 2634 and DHC 3234 SERIES

TO SPECIFY THE DHC 2634 or DHC 3234 SERIES:

  1. Insert, after "DHC", the appropriate prefix for the trim and door material. If 12 gauge STEEL - Use"S". If 12 gauge STAINLESS STEEL - Use "SS".
  2. Select the required model number from the dimensional chart based on wall depth and interior capacity.
  3. Select "LOCK OPTION"; page 4.
  4. Select fire extinguishers, if required; and interior hose rack components. (See Sweet's section 10520 FIRE PROTECTION SPECIALTIES.)
  5. Specify size and location of pipe opening. (One per cabinet standard.)
  6. OTHER OPTIONS: horizontal duo panel doors, special lettering, special finishes (white or red baked enamel), lighter gauges for medium or minimum security needs.

DIMENSIONS*

Model Number

Trim Style

Inside Box
Dimensions
H x W x D

Outside Door Dimensions H x W

Rough Opening
H x W x D

Pipe Locations Interior Capacity
DHC2634-R Rec.Flat 33-3/4x25-3/4x8-1/4 37-1/4x29-3/8 35x27x8-7/8 Specify Size & Location One Hose Rack with 100' of Rack Hose
DHC2634-SM Surface Mtd. 36-7/16x28-15/16x8-5/8 37-1/4x29-3/8 ----------
DHC3234-R Rec. Flat 33-3/4x31-3/4x8-1/4 37-1/4x35-3/8 35x33x8-7/8 Specify Size & Location One Hose Rack Unit with 100' of Rack Hose and a Fire Extinguisher
DHC3234-SM Surface Mtd. 36-7/16x34-15/16x8-5/8 37-1/4x35-3/8 -----------

* Other sizes available; contact factory.

Request for Information / Request a Catalog from Larsen's Manufacturing Company
 
 
 
To request more information from Larsen's Manufacturing Company, please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo.com
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2010 AECinfo.com