Minuet Asymmetry |
2 T8 - Direct / Indirect |
PHOTOMETRY
OPTICAL SETTING A:
Lower wall brightness plus maximum uniformity on wall

| Report# |
2100607 |
| Efficiency |
68.7% |
| Peak Candela Value |
1217 @ 142.5° |
| Peak Zenith Ratio |
1.4:1 |
| Asymmetric Effectiveness* |
38.1% |
CANDELA DISTRIBUTION
| Vert.
Angle |
Horizontal Angle |
Zonal
Lumens |
| 0 |
45 |
90 |
135 |
180 |
| 0 |
286 |
286 |
286 |
286 |
286 |
|
| 5 |
276 |
278 |
283 |
292 |
295 |
27 |
| 15 |
254 |
254 |
260 |
293 |
311 |
76 |
| 25 |
217 |
216 |
227 |
272 |
293 |
110 |
| 35 |
160 |
167 |
182 |
218 |
235 |
118 |
| 45 |
118 |
106 |
108 |
132 |
161 |
94 |
| 55 |
95 |
40 |
20 |
46 |
71 |
42 |
| 65 |
22 |
9 |
2 |
4 |
1 |
8 |
| 75 |
6 |
7 |
0 |
0 |
0 |
3 |
| 85 |
4 |
4 |
0 |
0 |
0 |
1 |
| 90 |
7 |
5 |
0 |
0 |
0 |
|
| 95 |
144 |
141 |
30 |
5 |
0 |
90 |
| 105 |
557 |
537 |
158 |
310 |
274 |
377 |
| 115 |
990 |
815 |
310 |
412 |
501 |
565 |
| 125 |
1143 |
929 |
457 |
481 |
563 |
613 |
| 135 |
1197 |
1021 |
590 |
553 |
606 |
595 |
| 145 |
1217 |
1071 |
705 |
631 |
654 |
523 |
| 155 |
1187 |
1065 |
795 |
705 |
706 |
406 |
| 165 |
1094 |
1012 |
857 |
770 |
763 |
252 |
| 175 |
956 |
935 |
890 |
851 |
839 |
86 |
| 180 |
895 |
895 |
895 |
895 |
895 |
|
COEFFICIENTS OF UTILIZATION (%)
| Ceiling
Wall RCR |
80 |
70 |
50 |
0 |
| 70 |
50 |
30 |
10 |
70 |
50 |
30 |
50 |
30 |
10 |
0 |
| 0 |
67 |
67 |
67 |
67 |
59 |
59 |
59 |
42 |
42 |
42 |
8 |
| 1 |
61 |
59 |
56 |
54 |
53 |
51 |
49 |
37 |
36 |
35 |
7 |
| 2 |
56 |
51 |
48 |
44 |
49 |
45 |
42 |
33 |
31 |
29 |
6 |
| 3 |
51 |
45 |
41 |
37 |
44 |
40 |
36 |
29 |
27 |
25 |
6 |
| 4 |
47 |
40 |
35 |
31 |
41 |
35 |
31 |
26 |
23 |
21 |
5 |
| 5 |
43 |
36 |
30 |
27 |
37 |
31 |
27 |
23 |
20 |
18 |
4 |
| 6 |
39 |
32 |
27 |
23 |
34 |
28 |
24 |
21 |
18 |
16 |
4 |
| 7 |
36 |
29 |
24 |
20 |
32 |
25 |
21 |
19 |
16 |
14 |
3 |
| 8 |
34 |
26 |
21 |
17 |
29 |
23 |
19 |
17 |
14 |
12 |
3 |
| 9 |
31 |
23 |
19 |
15 |
27 |
21 |
17 |
15 |
13 |
11 |
3 |
| 10 |
29 |
21 |
17 |
14 |
25 |
19 |
15 |
14 |
11 |
9 |
3 |
Based on a floor reflectance of 0.2
OPTICAL SETTING B:
Higher wall brightness with maximum efficiency &
more backlight

CANDELA DISTRIBUTION
| Vert.Angle |
Horizontal
Angle |
ZonalLumens |
| 0 |
45 |
90 |
135 |
180 |
| 0 |
270 |
270 |
270 |
270 |
270 |
|
| 5 |
264 |
262 |
266 |
273 |
277 |
26 |
| 15 |
242 |
240 |
246 |
273 |
289 |
72 |
| 25 |
206 |
205 |
214 |
252 |
275 |
106 |
| 35 |
155 |
159 |
171 |
203 |
222 |
112 |
| 45 |
122 |
103 |
101 |
123 |
153 |
90 |
| 55 |
97 |
41 |
19 |
43 |
66 |
42 |
| 65 |
27 |
9 |
2 |
5 |
2 |
9 |
| 75 |
5 |
5 |
0 |
1 |
4 |
4 |
| 85 |
3 |
5 |
0 |
0 |
0 |
1 |
| 90 |
8 |
6 |
0 |
0 |
0 |
|
| 95 |
113 |
121 |
40 |
5 |
0 |
88 |
| 105 |
533 |
524 |
207 |
318 |
283 |
393 |
| 115 |
983 |
857 |
404 |
498 |
573 |
628 |
| 125 |
1203 |
1009 |
595 |
627 |
698 |
719 |
| 135 |
1294 |
1145 |
772 |
753 |
802 |
724 |
| 145 |
1362 |
1242 |
921 |
876 |
900 |
657 |
| 155 |
1377 |
1270 |
1040 |
987 |
992 |
519 |
| 165 |
1316 |
1260 |
1122 |
1081 |
1070 |
331 |
| 175 |
1219 |
1207 |
1167 |
1138 |
1139 |
114 |
| 180 |
1171 |
1171 |
1171 |
1171 |
1171 |
|
COEFFICIENTS OF UTILIZATION (%)
| Ceiling
Wall RCR |
80 |
70 |
50 |
0 |
| 70 |
50 |
30 |
10 |
70 |
50 |
30 |
50 |
30 |
10 |
0 |
| 0 |
78 |
78 |
78 |
78 |
67 |
67 |
67 |
48 |
48 |
48 |
7 |
| 1 |
71 |
68 |
65 |
62 |
61 |
59 |
57 |
42 |
41 |
40 |
7 |
| 2 |
65 |
59 |
55 |
51 |
56 |
52 |
48 |
37 |
35 |
33 |
6 |
| 3 |
59 |
52 |
47 |
43 |
51 |
45 |
41 |
33 |
30 |
28 |
5 |
| 4 |
54 |
46 |
40 |
36 |
47 |
40 |
36 |
29 |
26 |
24 |
5 |
| 5 |
49 |
41 |
35 |
31 |
43 |
36 |
31 |
26 |
23 |
20 |
4 |
| 6 |
45 |
36 |
31 |
26 |
39 |
32 |
27 |
23 |
20 |
18 |
4 |
| 7 |
42 |
33 |
27 |
23 |
36 |
29 |
24 |
21 |
18 |
15 |
3 |
| 8 |
39 |
30 |
24 |
20 |
33 |
26 |
21 |
19 |
16 |
13 |
3 |
| 9 |
36 |
27 |
21 |
18 |
31 |
24 |
19 |
17 |
14 |
12 |
3 |
| 10 |
33 |
24 |
19 |
15 |
29 |
21 |
17 |
16 |
13 |
11 |
2 |
Based on a floor reflectance of 0.2
SPECIFICATIONS
Housing:
6063 T5 extruded aluminum.
Optical system:
Constructed of highly specular aluminum, and a highly
reflective 24 ga. metal, to produce a semi-indirect distribution.
Row ends:
Mitered aluminum extrusion sculptured end caps.
Joints & Intersections:
All joints shall be accomplished using TwinLock
joining system. Optional intersections in "L", "T", or "X"
configu-rations,
shall be mitered aluminum extrusion.
Mounting:
Brackets attach to existing structure anywhere behind
fixture. Fully adjustable mounting brackets to provide up to 1/8"
wall variance and allow for vertical fixture leveling.
Electrical:
All luminaire sections shall be factory pre-wired to
section ends. Optional quick connect plugs are available.
Ballast:
Electronic: rapid start.
Approvals:
Certified to UL & CSA standards.
Finish:
Thermosetting polyester, electrostatically applied meeting
AAMA 603.8. Available in Ledalite standard white and in a full architectural spectrum of
colors. Medium gloss finish as standard.
*Asymmetric efficiency refers to the percentage of lamp
lumens distributed on the room side of the luminaire, above 90 degrees.

©1997 Ledalite Architectural Products Inc. 9087A - 198th
Street, Langley, B.C., Canada, V1M 3B1
Phone: 604-888-6811 Toll Free Fax: 1-800-665-LEDA
(5332) Email: info@ledalite.com WWW:
http://www.ledalite.com
Note: Specifications subject to change without notice. |