| RG SERIES High Performance 1x4 Troffers |

|
Catalog Number : RG24014-BE1FARS
.095 Pattern 12 acrylic lens.
Lamps: Two F40T12/CW Each Rated at 3100 Lumens.

Total Luminaire Efficiency = 68.5%
| Plane : |
O-DEG |
90-DEG |
| Spacing Criteria : |
1.2 |
1.3 |
| Shielding Angles: |
90 |
90 |
| Zonal
Lumen Summary |
| ZONE |
LUMENS |
%LAMP |
%FIXT |
| 0 - 30 |
1492 |
24.1 |
34.9 |
| 0 - 40 |
2392 |
38.6 |
56.0 |
| 0 - 50 |
3720 |
60.0 |
87.1 |
| 0 - 90 |
4270 |
68.9 |
100.0 |
Coefficients of Utilization - Zonal Cavity Method Effective Floor
Cavity Reflectance 20% |
| RC |
80% |
70% |
50% |
| RW |
70 |
50 |
30 |
70 |
50 |
30 |
50 |
30 |
10 |
| 0 |
82 |
82 |
82 |
80 |
80 |
80 |
77 |
77 |
77 |
| 1 |
76 |
74 |
71 |
74 |
72 |
70 |
69 |
67 |
65 |
| 2 |
70 |
66 |
62 |
69 |
62 |
61 |
62 |
59 |
57 |
| 3 |
65 |
59 |
55 |
64 |
58 |
54 |
56 |
53 |
49 |
| 4 |
61 |
53 |
48 |
59 |
53 |
48 |
51 |
47 |
43 |
| 5 |
56 |
48 |
43 |
55 |
47 |
42 |
46 |
41 |
36 |
| 6 |
52 |
44 |
38 |
51 |
43 |
38 |
42 |
37 |
34 |
| 7 |
48 |
39 |
34 |
47 |
39 |
34 |
38 |
33 |
30 |
| 8 |
44 |
36 |
30 |
43 |
35 |
30 |
34 |
29 |
26 |
| 9 |
41 |
32 |
27 |
40 |
32 |
26 |
31 |
26 |
23 |
| 10 |
38 |
29 |
24 |
37 |
29 |
24 |
28 |
24 |
20 |
| Visual
Comfort Probability Table Average 100 FC, Reflectance 80/50/20 |
Room Size |
0° Plane
Ceiling Ht. |
90° Plane
Ceiling Ht. |
| W |
L |
8.5 |
10.0 |
8.5 |
10.0 |
| 20 |
20 |
60 |
64 |
61 |
65 |
| 30 |
30 |
53 |
57 |
54 |
57 |
| 30 |
60 |
44 |
47 |
45 |
48 |
| 60 |
30 |
56 |
59 |
56 |
60 |
| 60 |
60 |
46 |
48 |
47 |
49 |
| Average
Luminance (Footlamberts) |
| Vertical
Angle |
Horizontal
Plane |
| |
0° |
90° |
| 45 |
1496. |
1425. |
| 55 |
1099. |
1021. |
| 65 |
818. |
779. |
| 75 |
879. |
835. |
| 85 |
819. |
748. |
Catalog Number : RG23214-EO1FARS
.095 Pattern 12 acrylic lens.
Lamps: Two F32T8-SP41 Rated 2900 Lumens.

Total Luminaire Efficiency = 68.5%
| Plane : |
O-DEG |
90-DEG |
| Spacing Criteria : |
1.2 |
1.3 |
| Shielding Angles: |
90 |
90 |
| Zonal
Lumen Summary |
| ZONE |
LUMENS |
%LAMP |
%FIXT |
| 0 - 30 |
1369 |
23.6 |
34.5 |
| 0 - 40 |
2195 |
37.8 |
55.3 |
| 0 - 50 |
3427 |
59.1 |
86.3 |
| 0 - 90 |
3973 |
68.5 |
100.0 |
Coefficients of Utilization - Zonal Cavity Method Effective
Floor Cavity Reflectance 0.20 |
| RC |
80% |
70% |
50% |
| RW |
70 |
50 |
30 |
10 |
70 |
50 |
30 |
10 |
50 |
30 |
10 |
| 0 |
82 |
82 |
82 |
82 |
80 |
80 |
80 |
80 |
76 |
76 |
76 |
| 1 |
76 |
73 |
70 |
68 |
74 |
71 |
69 |
67 |
69 |
67 |
65 |
| 2 |
70 |
65 |
61 |
58 |
68 |
64 |
60 |
57 |
62 |
59 |
56 |
| 3 |
65 |
59 |
54 |
50 |
63 |
58 |
53 |
50 |
56 |
52 |
49 |
| 4 |
60 |
53 |
48 |
44 |
59 |
52 |
47 |
43 |
50 |
46 |
43 |
| 5 |
55 |
47 |
42 |
38 |
54 |
47 |
42 |
38 |
45 |
41 |
37 |
| 6 |
51 |
43 |
37 |
33 |
50 |
42 |
37 |
33 |
41 |
37 |
33 |
| 7 |
48 |
39 |
33 |
29 |
46 |
38 |
33 |
29 |
37 |
33 |
29 |
| 8 |
44 |
35 |
30 |
26 |
43 |
35 |
29 |
26 |
34 |
29 |
26 |
| 9 |
40 |
32 |
26 |
23 |
40 |
31 |
26 |
23 |
30 |
26 |
22 |
| 10 |
38 |
29 |
24 |
20 |
37 |
28 |
23 |
20 |
28 |
23 |
20 |
| Visual
Comfort Probability Table Average 100 FC, Reflectance 80/50/20 |
| Room
Size |
0°
Plane Ceiling Ht. |
90°
Plane Ceiling Ht. |
| W |
L |
8.5 |
10.0 |
13.0 |
16.0 |
| 20 |
20 |
60 |
65 |
79 |
78 |
| 30 |
30 |
53 |
57 |
62 |
67 |
| 30 |
60 |
43 |
46 |
49 |
53 |
| 60 |
30 |
55 |
59 |
63 |
67 |
| 60 |
60 |
45 |
48 |
49 |
52 |
Luminance in Candela Per Square Meter |
| Angle in Deg |
Average 0-Deg |
Average
45-Deg |
Average
90-Deg |
| 0 |
6083. |
6083. |
6083. |
| 45 |
4649. |
4709. |
4590. |
| 55 |
3472. |
4554. |
3283. |
| 65 |
2612. |
2315. |
2513. |
| 75 |
2659. |
2052. |
2497. |
| 85 |
2926. |
2245. |
2766. |
EXAMPLE : RG23214-EO1FARS (Static)
Select designators from chart to construct catalog number.
Example shown is for a static fixture. No air handling designators are used.
For an air model, use appropriate designators.
Examples:
RG23214-EO1FARS (Static)
RGT23214-EO1FARA (Top slots)
RGS23214-E01FABS (Side slots)
RGC23214-EO1FABS (Top and side)
For control vanes, add 'V'
RGTV23214-E01FARA
(RGCV units furnished with side vanes only)
LAMPS:
40 - F40ES 32 - F032
BALLASTS:
BE - 430 ma Rapid Start Energy Saving
ET - 430 ma Electronic
CT - 430 ma Electronic (3 lamp)
OT - 265 ma Magnetic Octron
EO - 265 ma Electronic Octron
CO - 265 ma Electronic Octron (3 lamp)
Note: On 3 lamp electronic fixtures, CO
designates a single 3 lamp ballast in fixture. CT designates one 3 lamp ballast.
ET and EO designate 2 ballasts in fixture, with inboard lamp(s) wired separately.
LENSES/LOUVERS:
FA - Pattern 12 Clear Acrylic .095" Lens
FB - Pattern 12 Clear Acrylic. 125" Lens
HA - Holophane 8224 Lens
SP - 1/2" Sq. Molded Silver Parabolic Louver
Refer to RG 2x2 page or Lens/Louver Options page for
complete listing.
DOOR FRAMES:
RS - Full White Steel Door, Flush
RA - Heat Removal White Steel Door, Flush
BS - Floating White Steel Door, Flush
RH - Full White Aluminum Door, Regressed
Refer to RG 2x2 page or Door Frame Selection Guide for
complete listing.
OPTIONS:
Use the following suffix for:
-F1 Fusing, one per fixture
-F2 Fusing, one per ballast
-RF1 Radio Interference Filter, one per fixture
-RF2 Radio Interference Filter, one per ballast
-FX1 Flex - 3/8 x 6 ft., 18/3 with two straight connectors
Emergency Ballast - Please consult options page for
complete listings.
Dimming Ballast - Please Consult the Factory.
For fixtures with lamps installed consult options page.
Ceiling opening for flanged models:
12-1/8" x 48-1/8."
specifications and dimensional data subject to change
without notice
LUMAX INDUSTRIES, INC.
RG.697 |