   Lumax Industries Inc.  Recessed Tropper  

Recessed Tropper - Page 17

 

 

RG SERIES

High Performance 2x2 Troffers


PHOTOMETRIC DATA

Catalog Number : RG2U622-BE1FARS

.095 Pattern 12 acrylic lens.

Lamps: Two F40T12/U6/CW Each Rated at 2935 Lumens.

Total Luminaire Efficiency = 61.6%

Plane : O-DEG 90-DEG
Spacing Criteria : 1.2 1.3
Shielding Angles: 90 90

 

Zonal Lumen Summary
ZONE LUMENS %LAMP %FIXT
0 - 30 1213 20.7 33.5
0 - 40 1953 33.3 54.0
0 - 50 3129 53.3 86.5
0 - 90 3619 61.6 100.0

 

Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 20%

RC 80% 70% 50%
RW 70% 50% 30% 70% 50% 30% 50% 30% 10%
0 73 73 73 72 72 72 69 69 69
1 68 66 63 67 64 62 62 60 59
2 63 59 55 62 58 54 55 53 50
3 58 53 48 57 52 48 50 47 44
4 54 47 43 53 47 42 45 41 38
5 50 43 38 48 42 37 41 36 33
6 46 38 33 45 38 33 37 33 29
7 43 35 30 42 34 29 33 29 26
8 39 31 26 38 31 26 30 26 23
9 36 28 23 35 28 23 27 23 20
10 34 26 21 33 25 21 25 20 18

 

Visual Comfort Probability Table Average 100 FC, Reflectance 80/50/20
Room Size 0° Plane Ceiling Ht. 90° Plane Ceiling Ht.
W L 8.5 10.0 8.5 10.0
20 20 65 69 64 67
30 30 58 62 57 60
30 60 49 52 49 51
60 30 61 64 60 63
60 60 51 53 50 52

 

Average Luminance (Footlamberts)
Vertical Horizontal Plane
Angle 90°
45 1083. 1310.
55 865. 1050.
65 661. 716.
75 695. 711.
85 659. 703.

Catalog Number : RG2U222-OT1FARS

.095 Pattern 12 acrylic lens.

Lamps: Two FB031/35K Octron

Curvalume Each Rated 2800 Lumens.

Total Luminaire Efficiency = 70.5%

Plane : O-DEG 90-DEG
Spacing Criteria : 1.2 1.3
Shielding Angles: 90 90

 

Zonal Lumen Summary
ZONE LUMENS %LAMP %FIXT
0 - 30 1325 23.7 33.5
0 - 40 2145 38.3 54.3
0 - 50 3421 61.1 86.6
0 - 90 3951 70.5 100.0

 

Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 20%

RC 80% 70% 50%
RW 70 50 30 70 50 30 50 30 10
0 84 84 84 82 82 82 78 78 78
1 78 75 73 76 74 71 71 69 67
2 72 67 63 79 66 62 64 60 58
3 67 60 56 65 59 55 57 53 50
4 62 54 49 60 53 48 52 47 44
5 57 49 43 56 48 43 47 42 38
6 53 44 38 51 43 38 42 37 34
7 49 40 34 48 39 34 38 33 30
8 45 36 30 44 35 30 34 30 26
9 41 32 27 40 32 26 31 26 23
10 39 29 24 38 29 24 28 23 20

 

Visual Comfort Probability Table Average 100 FC, Reflectance 80/50/20
Room Size 0° Plane Ceiling Ht. 90° Plane Ceiling Ht.
W L 8.5 10.0 8.5 10.0
20 20 63 67 62 65
30 30 56 60 55 58
30 60 47 50 46 49
60 30 59 62 58 61
60 60 49 51 48 50

 

Average Luminance (Footlamberts)
Vertical Angle Horizontal Plane
  90°
45 1163. 1437.
55 911. 1099.
65 714. 762.
75 744. 763.
85 714. 781.

Catalog Number : RG24T22-BH1FARS

.095 Pattern 12 acrylic lens.

Lamps: Two Biax F40BX/SPX35/RS

Each Rated 3150 Lumens.

Total Luminaire Efficiency = 71.4%

Plane : O-DEG 90-DEG
Spacing Criteria : 1.2 1.4
Shielding Angles: 90 90

 

Zonal Lumen Summary
ZONE LUMENS %LAMP %FIXT
0 - 30 1517 24.1 33.7
0 - 40 2457 39.0 54.6
0 - 50 3899 61.9 86.7
0 - 90 4497 71.4 100.0

 

Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 20%

RC 80% 70% 50%
RW 70% 50% 30% 70% 50% 30% 50% 30% 10%
0 85 85 85 83 83 83 79 79 79
1 79 76 73 77 74 72 71 70 68
2 73 68 64 71 67 63 64 61 58
3 68 61 56 66 60 55 58 54 51
4 63 55 50 61 54 49 52 48 44
5 58 49 44 56 49 43 47 42 39
6 53 45 39 52 44 39 43 38 34
7 49 40 35 48 40 34 39 34 30
8 46 36 31 44 36 30 35 30 26
9 42 33 27 41 32 27 32 27 23
10 39 30 24 38 29 24 29 24 20

 

Visual Comfort Probability Table Average 100 FC, Reflectance 80/50/20
Room Size 0° Plane Ceiling Ht. 90° Plane Ceiling Ht.
W L 8.5 10.0 8.5 10.0
20 20 61 64 59 62
30 30 53 57 52 56
30 60 44 46 43 46
60 30 55 59 55 58
60 60 45 48 45 47

 

Average Luminance (Footlamberts)
Vertical Horizontal Plane
Angle 90°
45 1329. 1609.
55 1043. 1220.
65 808. 863.
75 846. 868.
85 826. 893.

Catalog Number : RG34T22-bh1FARS

.095 Pattern 12 acrylic lens.

Lamps: Three Biax F40BX/SPX35/RS

Each Rated 3150 Lumens.

Total Luminaire Efficiency = 69.3%

Plane : O-DEG 90-DEG
Spacing Criteria : 1.3 1.2
Shielding Angles: 90 90

 

Zonal Lumen Summary
ZONE LUMENS %LAMP %FIXT
0 - 30 2275 24.1 34.8
0 - 40 3641 38.5 55.6
0 - 50 5690 60.2 86.9
0 - 90 6546 69.3 100.0

 

Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 20%

RC 80% 70% 50%
RW 70% 50% 30% 70% 50% 30% 50% 30% 10%
0 82 82 82 81 81 81 77 77 77
1 77 74 71 75 72 70 69 68 66
2 71 66 62 69 65 61 63 60 57
3 66 60 55 64 59 54 57 53 50
4 61 54 48 59 53 48 51 47 43
5 56 48 43 55 47 42 46 41 38
6 52 44 38 51 43 38 42 37 34
7 48 40 34 47 39 34 38 33 30
8 45 36 30 43 35 30 34 30 26
9 41 32 27 40 32 27 31 26 23
10 38 29 24 37 29 24 28 24 20

 

Visual Comfort Probability Table Average 100 FC, Reflectance 80/50/20

Room Size 0° Plane Ceiling Ht. 90° Plane Ceiling Ht.
W L 8.5 10.0 8.5 10.0
20 20 50 54 51 55
30 30 43 46 44 47
30 60 34 37 35 37
60 30 46 50 46 50
60 60 36 38 37 39

 

Average Luminance (Footlamberts)

Vertical Horizontal Plane
Angle 90°
45 2221. 1975.
55 1722. 1517.
65 1216. 1163.
75 1256. 1226.
85 1239. 1195.

LUMAX INDUSTRIES, INC.

RG-2x2.697

Request for Information / Request a Catalog from Lumax Industries Inc.
 
 
 
To request more information from Lumax Industries Inc., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com