   Lumax Industries Inc.  Recessed Tropper  

Recessed Tropper - Page 19

 

 

RG SERIES

High Performance 2x4 Troffers


PHOTOMETRIC DATA

Catalog Number : RG44024-BE1FARS

.095 Pattern 12 acrylic lens.

Lamps: Four F40T12/CW Each Rated at 3100 Lumens.

Total Luminaire Efficiency = 70.1%

Plane : O-DEG 90-DEG
Spacing Criteria : 1.2 1.3
Shielding Angles: 90 90

 

Zonal Lumen Summary
ZONE LUMENS %LAMP %FIXT
0 - 30 2856 23.0 32.9
0 - 40 4643 37.4 53.4
0 - 50 7505 60.5 86.4
0 - 90 8687 70.1 100.0

 

Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 0.20%

RC 80% 70% 50%
RW 70% 50% 30% 70% 50% 30% 50% 30% 10%
0 83 83 83 81 81 81 78 78 78
1 77 75 72 76 73 71 70 68 66
2 72 67 63 70 65 62 63 60 57
3 66 60 55 65 59 54 57 53 50
4 61 54 48 60 53 48 51 47 43
5 56 48 42 55 47 42 46 41 38
6 52 44 38 51 43 37 42 37 33
7 48 39 34 47 39 33 38 33 29
8 44 35 30 43 35 29 34 29 26
9 41 32 26 40 31 26 31 26 22
10 38 29 23 37 29 23 28 23 20

 

Visual Comfort Probability Table Average 100 FC, Reflectance 80/50/20
Room Size 0° Plane Ceiling Ht. 90° Plane Ceiling Ht.
W L 8.5 10.0 8.5 10.0
20 20 62 65 61 63
30 30 55 58 54 57
30 60 46 48 46 48
60 30 57 61 57 60
60 60 47 49 47 50

 

Average Luminance (Footlamberts)

Vertical Horizontal Plane
Angle 90°
45 1305. 1506.
55 977. 1142.
65 753. 803.
75 801. 791.
85 786. 739.

Catalog Number : RG43224-OT1FARS

.095 Pattern 12 acrylic lens.

Lamps: Four Octron F032/35K Each

Rated at 2900 Lumens.

Total Luminaire Efficiency = 75.6%

Plane : O-DEG 90-DEG
Spacing Criteria : 1.2 1.3
Shielding Angles: 90 90

 

Zonal Lumen Summary
ZONE LUMENS %LAMP %FIXT
0 - 30 2885 24.9 32.9
0 - 40 4687 40.4 54.4
0 - 50 7573 65.3 86.3
0 - 90 8772 75.6 100.0

 

Coefficients of Utilization - Zonal Cavity Method Effective Floor Cavity Reflectance 20%

RC 80% 70% 50%
RW 70% 50% 30% 70% 50% 30% 50% 30% 10%
0 90 90 90 88 88 88 84 84 84
1 84 81 78 82 79 76 76 74 72
2 77 72 68 75 71 67 68 65 62
3 71 65 59 70 63 59 61 57 54
4 66 58 52 64 57 52 55 51 47
5 61 52 46 59 51 45 50 45 41
6 56 47 41 55 46 40 45 40 36
7 52 42 36 51 42 36 41 35 32
8 48 38 32 47 38 32 37 31 28
9 44 34 28 43 34 28 33 28 24
10 41 31 25 40 31 25 30 25 21

 

Visual Comfort Probability Table Average 100 FC, Reflectance 80/50/20
Room Size 0° Plane Ceiling Ht. 90° Plane Ceiling Ht.
W L 8.5 10.0 8.5 10.0
20 20 61 65 60 63
30 30 55 58 54 57
30 60 46 48 46 48
60 30 57 61 57 60
60 60 47 50 47 49

 

Average Luminance (Footlamberts)

Vertical Horizontal Plane
Angle 90°
45 1317. 1527.
55 984. 1165.
65 757. 813.
75 810. 801.
85 770. 765.

ORDERING GUIDE

 

EXAMPLE: RG23224-E01FARS (Static)

Select designators from chart to construct catalog number. Example shown is for a static fixture. No air handling designators are used. For an air model, use appropriate designators.

Examples:

RGT23224-E01FARA (Top slots)

RGS23224-E01FABS (Side slots)

RGC23224-E01FABS (Top and side)

For control vanes, add 'V'

RGT23224-E01FARA

(RGCV units fixtures furnished with side vanes only)

LAMPS:

40 - F40ES 32 - F032

BALLASTS:

BE - 430 ma Rapid Start Energy Saving

ET - 430 ma Electronic

CT - 430 ma Electronic (3 lamp)

OT - 265 ma Magnetic Octron

EO - 265 ma Electronic Octron

CO - 265 ma Electronic Octron (3 or 4 lamp)

Note: 3 or 4 lamp electronic fixtures, CO designates a single 3 or 4 lamp ballast in fixture. CT designates one 3 lamp ballast. ET and EO designate 2 ballasts in fixture, with inboard lamp(s) wired separately.

LENSES/LOUVERS:

FA - Pattern 12 Clear Acrylic .095" Lens

FB - Pattern 12 Clear Acrylic .125" Lens

HA - Holophane 8224 Lens

SP - 1/2" Sq. Molded Silver Parabolic Louver

Refer to RG 2x2 page or Lens/Louver Options page for complete listing.

DOOR FRAMES:

RS - Full White Steel Door, Flush

RA - Heat Removal White Steel Door, Flush

BS - Floating White Steel Door, Flush

RH - Full White Aluminum Door, Regressed

Refer to RG 2x2 page or Door Frame Selection Guide For complete listing.

OPTIONS:

Use the following suffix for:

-F1 Fusing, one per fixture

-F2 Fusing, one pr ballast

-RF1 Radio Interference Filter, one per fixture

-RF2 Radio Interference Filter, one per ballast

-FX1 Flex - 3/8 x 6 ft., 18/3 with two straight connectors

Emergency Ballast - Please consult options page for complete listings.

Dimming Ballast - Please Consult the Factory.


DIMENSIONS

 

specifications and dimensional data subject to change without notice.

 

Ceiling Opening for Flanged Models: 24-1/8" x 48-1/8"

LUMAX INDUSTRIES, INC.

UTRASPEC.697

Request for Information / Request a Catalog from Lumax Industries Inc.
 
 
 
To request more information from Lumax Industries Inc., please complete the form below.
 
*Name:    
*Email:    
Company:    
*Company type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     






Printable version Bookmark this page Notify a colleague or friend about this pageHome | Terms of Use | Privacy Statement | Link to AECinfo
AECinfo is a member of Docu Group, the world's largest building products information network.



Copyright © 1996–2008 AECinfo.com