| RG SERIES High Performance 2x4 Troffers |

|
Catalog Number : RG44024-BE1FARS
.095 Pattern 12 acrylic lens.
Lamps: Four F40T12/CW Each Rated at 3100 Lumens.

Total Luminaire Efficiency = 70.1%
| Plane : |
O-DEG |
90-DEG |
| Spacing Criteria : |
1.2 |
1.3 |
| Shielding Angles: |
90 |
90 |
| Zonal
Lumen Summary |
| ZONE |
LUMENS |
%LAMP |
%FIXT |
| 0 - 30 |
2856 |
23.0 |
32.9 |
| 0 - 40 |
4643 |
37.4 |
53.4 |
| 0 - 50 |
7505 |
60.5 |
86.4 |
| 0 - 90 |
8687 |
70.1 |
100.0 |
Coefficients of Utilization - Zonal Cavity Method Effective
Floor Cavity Reflectance 0.20% |
| RC |
80% |
70% |
50% |
| RW |
70% |
50% |
30% |
70% |
50% |
30% |
50% |
30% |
10% |
| 0 |
83 |
83 |
83 |
81 |
81 |
81 |
78 |
78 |
78 |
| 1 |
77 |
75 |
72 |
76 |
73 |
71 |
70 |
68 |
66 |
| 2 |
72 |
67 |
63 |
70 |
65 |
62 |
63 |
60 |
57 |
| 3 |
66 |
60 |
55 |
65 |
59 |
54 |
57 |
53 |
50 |
| 4 |
61 |
54 |
48 |
60 |
53 |
48 |
51 |
47 |
43 |
| 5 |
56 |
48 |
42 |
55 |
47 |
42 |
46 |
41 |
38 |
| 6 |
52 |
44 |
38 |
51 |
43 |
37 |
42 |
37 |
33 |
| 7 |
48 |
39 |
34 |
47 |
39 |
33 |
38 |
33 |
29 |
| 8 |
44 |
35 |
30 |
43 |
35 |
29 |
34 |
29 |
26 |
| 9 |
41 |
32 |
26 |
40 |
31 |
26 |
31 |
26 |
22 |
| 10 |
38 |
29 |
23 |
37 |
29 |
23 |
28 |
23 |
20 |
| Visual
Comfort Probability Table Average 100 FC, Reflectance 80/50/20 |
| Room
Size |
0°
Plane Ceiling Ht. |
90°
Plane Ceiling Ht. |
| W |
L |
8.5 |
10.0 |
8.5 |
10.0 |
| 20 |
20 |
62 |
65 |
61 |
63 |
| 30 |
30 |
55 |
58 |
54 |
57 |
| 30 |
60 |
46 |
48 |
46 |
48 |
| 60 |
30 |
57 |
61 |
57 |
60 |
| 60 |
60 |
47 |
49 |
47 |
50 |
Average Luminance (Footlamberts) |
| Vertical |
Horizontal
Plane |
| Angle |
0° |
90° |
| 45 |
1305. |
1506. |
| 55 |
977. |
1142. |
| 65 |
753. |
803. |
| 75 |
801. |
791. |
| 85 |
786. |
739. |
Catalog Number : RG43224-OT1FARS
.095 Pattern 12 acrylic lens.
Lamps: Four Octron F032/35K Each
Rated at 2900 Lumens.

Total Luminaire Efficiency = 75.6%
| Plane : |
O-DEG |
90-DEG |
| Spacing Criteria : |
1.2 |
1.3 |
| Shielding Angles: |
90 |
90 |
| Zonal
Lumen Summary |
| ZONE |
LUMENS |
%LAMP |
%FIXT |
| 0 - 30 |
2885 |
24.9 |
32.9 |
| 0 - 40 |
4687 |
40.4 |
54.4 |
| 0 - 50 |
7573 |
65.3 |
86.3 |
| 0 - 90 |
8772 |
75.6 |
100.0 |
Coefficients of Utilization - Zonal Cavity Method Effective
Floor Cavity Reflectance 20% |
| RC |
80% |
70% |
50% |
| RW |
70% |
50% |
30% |
70% |
50% |
30% |
50% |
30% |
10% |
| 0 |
90 |
90 |
90 |
88 |
88 |
88 |
84 |
84 |
84 |
| 1 |
84 |
81 |
78 |
82 |
79 |
76 |
76 |
74 |
72 |
| 2 |
77 |
72 |
68 |
75 |
71 |
67 |
68 |
65 |
62 |
| 3 |
71 |
65 |
59 |
70 |
63 |
59 |
61 |
57 |
54 |
| 4 |
66 |
58 |
52 |
64 |
57 |
52 |
55 |
51 |
47 |
| 5 |
61 |
52 |
46 |
59 |
51 |
45 |
50 |
45 |
41 |
| 6 |
56 |
47 |
41 |
55 |
46 |
40 |
45 |
40 |
36 |
| 7 |
52 |
42 |
36 |
51 |
42 |
36 |
41 |
35 |
32 |
| 8 |
48 |
38 |
32 |
47 |
38 |
32 |
37 |
31 |
28 |
| 9 |
44 |
34 |
28 |
43 |
34 |
28 |
33 |
28 |
24 |
| 10 |
41 |
31 |
25 |
40 |
31 |
25 |
30 |
25 |
21 |
| Visual
Comfort Probability Table Average 100 FC, Reflectance 80/50/20 |
| Room
Size |
0°
Plane Ceiling Ht. |
90°
Plane Ceiling Ht. |
| W |
L |
8.5 |
10.0 |
8.5 |
10.0 |
| 20 |
20 |
61 |
65 |
60 |
63 |
| 30 |
30 |
55 |
58 |
54 |
57 |
| 30 |
60 |
46 |
48 |
46 |
48 |
| 60 |
30 |
57 |
61 |
57 |
60 |
| 60 |
60 |
47 |
50 |
47 |
49 |
Average Luminance (Footlamberts) |
| Vertical |
Horizontal
Plane |
| Angle |
0° |
90° |
| 45 |
1317. |
1527. |
| 55 |
984. |
1165. |
| 65 |
757. |
813. |
| 75 |
810. |
801. |
| 85 |
770. |
765. |
EXAMPLE: RG23224-E01FARS (Static)
Select designators from chart to construct catalog number.
Example shown is for a static fixture. No air handling designators are used. For an
air model, use appropriate designators.
Examples:
RGT23224-E01FARA (Top slots)
RGS23224-E01FABS (Side slots)
RGC23224-E01FABS (Top and side)
For control vanes, add 'V'
RGT23224-E01FARA
(RGCV units fixtures furnished with side vanes only)
LAMPS:
40 - F40ES 32 - F032
BALLASTS:
BE - 430 ma Rapid Start Energy Saving
ET - 430 ma Electronic
CT - 430 ma Electronic (3 lamp)
OT - 265 ma Magnetic Octron
EO - 265 ma Electronic Octron
CO - 265 ma Electronic Octron (3 or 4 lamp)
Note: 3 or 4 lamp electronic fixtures, CO
designates a single 3 or 4 lamp ballast in fixture. CT designates one 3
lamp ballast. ET and EO designate 2 ballasts in fixture, with inboard
lamp(s) wired separately.
LENSES/LOUVERS:
FA - Pattern 12 Clear Acrylic .095" Lens
FB - Pattern 12 Clear Acrylic .125" Lens
HA - Holophane 8224 Lens
SP - 1/2" Sq. Molded Silver Parabolic Louver
Refer to RG 2x2 page or Lens/Louver Options page for
complete listing.
DOOR FRAMES:
RS - Full White Steel Door, Flush
RA - Heat Removal White Steel Door, Flush
BS - Floating White Steel Door, Flush
RH - Full White Aluminum Door, Regressed
Refer to RG 2x2 page or Door Frame Selection Guide For
complete listing.
OPTIONS:
Use the following suffix for:
-F1 Fusing, one per fixture
-F2 Fusing, one pr ballast
-RF1 Radio Interference Filter, one per fixture
-RF2 Radio Interference Filter, one per ballast
-FX1 Flex - 3/8 x 6 ft., 18/3 with two straight connectors
Emergency Ballast - Please consult options page for
complete listings.
Dimming Ballast - Please Consult the Factory.
 specifications and dimensional data subject to change without
notice.
|
 |
 |
| Ceiling Opening for
Flanged Models: 24-1/8" x 48-1/8" |
LUMAX INDUSTRIES, INC.
UTRASPEC.697 |