SERIES 7210/7250 MASTER UNITS
Pull (Hinge) Side Mounting Rigid Slide Arm and
Track
Master Units with Integral Smoke Detector
Series 7210MPDI: Infinite Hold-Open
Series 7210MPDS: Selective Hold-Open
Executive Door Holder/Release
Series 7210RFI: Infinite Hold - Open
Series 7210RFS: Selective Hold-Open
Single Doors
Master Units with Integral Smoke Detector: Both
Series 7210MPDI and Series 7210MPDS are self-contained and can be installed to control a
single door.
Executive Door Holder/Release: Both Series 7210RFI and 7210RFS are
self-contained and can be installed to control a single door.
Pairs of Doors
Master Unit x Slave Unit: Smoke Detector
in the Master Unit controls its own closer-holder solenoid and the solenoid in the Slave
Unit.
Master Unit x Tandem Unit: Smoke Detector
in the Master Unit signals conditions (Stand-by, Trouble/Alarm) to an alarm systems panel.
This panel controls the signal to the hold-open solenoids in both the Master Unit and the
Tandem Unit.
Executive Door Holder x Slave Unit: Consult
the factory for details of this installation.
These Closer-Holders are surface mounted to the pull
(hinge) side frame face. These units require a minimum ceiling clearance of 4"
(102mm) and a maximum frame reveal of 1/8" (3mm).+ The slide track mounts
directly to the door. Units can be installed as shipped to accommodate doors opening to
180° with a maximum hold-open point of 175°. The buffer block assembly in the track will
accommodate doors opening to 125°. An auxiliary door stop is required for doors opening
beyond 125°.
+Double Egress Frames (Deep Reveals): Where
the pull (hinge) side frame reveal exceeds 1/8" (3mm), a special slide arm is
available to order. This arm will accommodate frame reveals in excess of 1/8" (3mm)
up to 3" (76mm) with a maximum allowable door swing of 110°. Order Series 7250MPD1,
7250MPDS, 7250RFI or 7250RFS.


Door Sizes and List Numbers
| Maximum* Door Size Ft. In.
(meters) |
NORTON CATALOG NUMBER |
| MASTER UNIT CLOSER-HOLDER |
EXECUTIVE DOOR/RELEASE |
| INFINITE HOLD/OPEN |
SELECTIVE HOLD/OPEN |
INFINITE HOLD/OPEN |
SELECTIVE HOLD/OPEN |
| 3'-4" (1.00) |
7213MPDI |
7213MPDS |
7213RFI |
7213RFS |
| 3'--8" (1.10) |
7214MPDI |
7214MPDS |
7214RFI |
7214RFS |
| 4'-0" (1.20) |
7215MPDS |
7215MPDS |
7215RFI |
7215RFS |
*Minimum Door Size Is 2'-4" (.70 M)
Electrical Data Master Units
| MASTER UNIT CATALOG NUMBER |
NUMBER POWER INPUT LINES*
(PAIRS) |
OPERATING VOLTAGE (INPUT) |
AMPERAGE DRAW (AMPERES) |
(CAN BE) USED IN CONJUNCTION
WITH |
| SMOKE DETECTOR |
SOLENOID COIL |
| STANDBY |
ALARM |
| 7210MPDI-24 7210MPDS-24 |
1 1 |
7213MPDS |
.016@ 24VDC |
.035@ 24VDC |
.070 @ 24VDS |
Slave Unit 7210MPSI-24 Slave Unit 721 0DMPSS-24 |
| 7210MPDI-120 7210MPDS-120 |
1 1 |
7214MPDS |
.070 @ 24VDS |
Slave Unit 7210MPSI-24 Slave Unit 721 0MPSS-24 |
| 7210MPDI-24 7210MPDS-24 |
2 2 |
24VAC/DC for Detection Input & 120VAC
for Solenoid Coil Input |
.035 @ 24VDS |
Tandem Unit 7210MPTI-120 Tamden Unit 7210MPTS-120 |
Electrical Data Door Holder/Release
| EXECUTIVE DOOR HOLDER/RELEASE
CATALOG NUMBER |
NUMBER POWER INPUT LINES*
(PAIRS) |
OPERATING VOLTAGE (INPUT) 24VDC
|
AMPERAGE DRAW (AMPERES) |
| SOLENOID COIL |
INTERRUPTING SWITCH |
| 7210RFI-120 |
1 |
120VAC |
.070 @ 24VDC |
015 @ 210VAC |
| 7210RFS-120 |
1 |
*Pairs of input lines required to supply Operating Voltage
or Voltages to the Unit. Pairs listed do not include signal wires to Alarm Panels nor
control wires to other units' solenoids. Maximum/Minimum Operating Voltage Parameters:
+10%, -15%

|