SERIES 7210/7250 SLAVE/TANDEM UNITS
Pull (Hinge) Side Mounting Rigid Slide Arm and
Track
Slave Units Controlled by Master Unit Smoke
Detector
Series 7210MPSI: Infinite Hold-Open
Series 7210MPSS: Selective Hold-Open
Tandem Units Controlled by Signal from Alarm Panel
Series 7210MPTI: Infinite Hold-Open
Series 7210MPTS: Selective Hold-Open
Pairs of Doors:
Master Unit x Slave Unit: Smoke Detector
in the Master Unit controls the closer-holder solenoids in both the Master Unit and the
Slave Unit.
Master Unit x Tandem Unit: Smoke Detector
in the Master Unit signals conditions (Stand-by, Trouble/ Alarm) to an alarm systems
panel. This panel controls the signal to the closer-holder solenoids in both the Master
Unit and the Tandem Unit.
These Closer-Holders are surface mounted to the Pull
(hinge) side frame face. The standard mounting for these units requires a minimum ceiling
clearance of 4" (102mm) and a maximum frame reveal of 1/8" (3mm) +
The slide track mounts directly to the door. Units can be installed as shipped to
accommodate doors opening to 180° with a maximum hold-open point of 175°. The buffer
block assembly in the track will accommodate doors opening to 125°. An auxiliary door
stop is required for doors opening beyond 125°.
+Double Egress Frames (Deep Reveals): Where
the pull (hinge) side frame reveal exceeds 1/8" (3mm), a special slide arm is
available to order. This arm will accommodate frame reveals in excess of 1/8" (3mm)
up to 3" (76mm) with a maximum allowable door swing of 110°. Order Series 7250MPSI
or 7250MPSS Slave Units; Series 7250MPTI or 7250MPTS Tandem Units.


Door Sizes and List Numbers
| Maximum* Door Size Ft. In.
(meters) |
NORTON CATALOG NUMBER |
| MASTER UNIT CLOSER-HOLDER |
TANDEM UNITS |
| INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
| 3'-4" (1.00) |
7213MPSI |
7213MPSS |
7213MPTI |
7213MPTS |
| 3'-8" (1.10) |
7214MPSI |
7214MPSS |
7214MPTI |
7214MPTS |
| 4'-0" (1.20) |
7215MPSI |
7215MPSS |
7215MPTI |
7215MPTS |
*Minimum door size is 2'-4" (.70 M).
Electrical Data
| TYPE OF UNIT & CATALOG
NUMBER |
NUMBER POWER INPUT LINES*
(PAIRS) |
OPERATING VOLTAGE |
AMPERAGE DRAW SOLENOID COILS
(AMPERES) |
(CAN BE) USED IN CONJUNCTION
WITH |
| Slave 7210MPSI Slave 7210DMPSS |
1 |
(INPUT) 24VAC/DC for Detection
Input. AND 120VAC for Solenoid Coil Input |
.070@ 24VDC |
7210MPDI-24 7210MPDI-120
7210MPDS-24
7210MPDS-120 |
| TANDOM 7201MPSI TANDOM 7201MPSS |
1 |
120VAC |
.035@ 24VDC |
7210MPDI-240 X 120 7210MPDS-240 X 120 |

|