SERIES 7210/7250 SUPPORT
UNITS SURFACE MOUNTED
Pull (Hinge) Side Mounting Rigid Slide Arm and
Track
Surface Mounted Support Units
Controlled Remotely by Area/Ceiling Detectors
Series 7210MPI: Infinite Hold-Open
Series 7210MPS: Selective Hold-Open
Series 7210MPI/7210MPS Surface Mounted
Closer-Holders
are surface mounted to the pull (hinge) side frame face.
The standard mounting for these units requires a minimum ceiling clearance of 4"
(102mm) and a maximum reveal of 1/8" (3mm).+ The slide track mounts
directly to the door.
Units can be installed as shipped to accommodate doors
opening to 180° with a maximum hold-open point of 175°. The buffer block assembly in the
track will accommodate doors opening to 125°. An auxiliary stop is required for doors
opening beyond 125°.
The Series 7210MPI/7210MPS are intended for use with
compatible U.L. listed ceiling alarm detection equipment.
+Double Egress Frames (Deep Reveals):
Where the pull (hinge) side frame reveal exceeds 1/8" (3mm), a special slide arm is
available to order. This arm will accommodate frame reveals in excess of 1/8" (3mm)
up to 3" (76mm) with a maximum allowable door swing of 110°. Order Series 7250MPI or
7250MPS.

1/8" (3mm) Maximum Frame Reveal with Standard Arm+

Door Sizes and List Numbers
| MAXIMUM* DOOR SIZE FT. IN.
(METERS) |
NORTON CATALOG NUMBER SURFACE
MOUNTED |
| INFINITE HOLD-OPEN |
SELECTIVE HOLD-OPEN |
| 3'-4" (1.00) |
7213MPI |
7213MPS |
| 3'-8" (1.10) |
7214MPI |
7214MPS |
| 4 '-0" (1.20) |
7215MPI |
7215MPS |
Minimum door size is 28" (.70M).
Electrical Data
| SUPPORT UNIT CATALOG NUMBER SURFACE MOUNTED
|
NUMBER POWER INPUT LINES* (PAIRS) |
OPERATING VOLTAGE (INPUT) |
AMPERAGE DRAW SOLENOID COIL (AMPERES) |
(CAN BE) USED IN CONJUNCTION WITH |
| 7210MPI-24 7210MPS-24 |
1 |
24VAC/DC |
.070@ 24VAC/DC |
COMPATIBLE SMOKE DETECTION EQUIPMENT |
| 7210MPI-120 7210MPS-120 |
1 |
120VAC |
.035@ 120VAC |
COMPATIBLE SMOKE DETECTION EQUIPMENT |
Maximum/Minimum Operating Voltage Parameters: +10%, -15%

|